SHEVS Control Centre RWZ 1 b
10
6
Technical data
6.1
Version
Type
RWZ 1-4b
Product code
8100 1204 0000
Output current
4
A (24
V
-
/ 192
W)
Current input
0,7
A / 230
V~
Lead-acid accumulators, VdS approved
2 x 2
Ah / 12
V
I / U charging
0,2
A (28,8
V) / 27,4
V
Dimensions in mm (W x H x D)
330 x 330 x 110
The Control Centre complies with the requirements of the 2006/95/EC and 2004/108/EC Directives (emission:
EN 61000-6-3 and EN 55022, immunity: EN 61000-6-2 and EN 50130-4).
6.2
Performance data and characteristics
General
Line voltage supply
Internal voltage supply / standby time
230
V~ / 50 - 60
Hz
24
V
-
/ 72 hrs. (mains failure)
Cable feed
from above, below or behind
Environmental Class 1 / III (to EN 12101-10 / VdS 2581)
Relative humidity
Enclosure protection rating (to DIN EN 60529)
-5
°C
…
+40
°C
20
%
…
80
%, non-condensing
IP30
For mounting dimensions, see plan “Line voltage, mounting and accumulators”.
Not suitable for use outdoors. Protect from direct sunlight, humidity and excessive formation of dust!
Preferably, the installation should be carried out in dry, heated rooms.
Signal lines
Line monitoring
wire-break, short-circuit
Line
T
:
Automatic fire detectors:
Smoke detector / heat detector (
RM 2
/
TM 2
or
RM 3 / TM 3
)
or
Fire Alarm Control Panel
−
Terminating resistor
−
Alarm resistor
20 pieces, of which
max. 10 heat detectors
1
normally open contact
10
k
(
10
%, ¼
W)
1
k
…
1.5
k
(
10
%, ½
W)
Line
t
, manual call points:
−
Secondary alarm point (
RT 2-*
)
−
Main alarm point (
RT 2-*-BS
)
−
Main alarm point (
RT 2-*-BS-A
, with indication
A
)
−
Main alarm point (
RT 2-*-BS-AA
, with buzzer
S
)
total of 10 pieces, of which
max. 3 pieces with buzzer
In- / Outputs
Ventilation button (
LT
)
Ventilation button with indication of position
A
(
LT-A
)
unlimited
10 pieces
Wind and Rain Control (type
WRS
)
normally closed contact
2
External malfunction
normally closed contact
1
Heat detectors:
TM 2-D
(65-55000-122),
TM 2-M
(65-55000-137),
TM 3-D
(FD-851RE),
TM 3-M
(FD-851HTE),
RM 3-OT
(SD-851-TE),
Optical detectors:
RM 2-O
(65-55000-317),
RM 3-O
(SD-851-E)
2
In the WRC, use a separate contact for each connected Control Centre