Operation
SUPRAECO W – 6 720 646 161 (2012/04)
21
Fig. 28 „Combi“ mode
This mode permits setting the water temperature anywhere between
30 °C and 70 °C.
8.5.2 „Prog“ function - Timetable operation programming
The „Prog“ function permits the heat pump to be programmed for
operation based on the desired timetable only.
Fig. 29 „Prog“ function
The „Prog“ function provides access to the following menus:
•
„P1“ period (days 1 to 5)
•
„P1“ period (days 6 to 7)
•
„P2“ period (days 1 to 5)
•
„P2“ period (days 6 to 7)
•
„P3“ period (days 1 to 5)
•
„P3“ period (days 6 to 7)
„P1“ period
The heat pump functions during the predetermined factory times. No
other type of alteration is possible:
Days 1 - 5: [00:00
Æ
06:00] and [16:00
Æ
19:00]
Days 6 - 7: [02:00
Æ
08:00]
Fig. 30 „P1“ period
„P2“ and „P3“ periods
The heat pump functions at times preset by the user.
Fig. 31 „P2“ and „P3“ periods
Setting the operating periods to „P2“ and „P3“
4 operating periods will be set in each of the functions:
•
2 periods for days „1 to 5“
•
2 periods for days „6 to 7“
Definition of operating periods
B
Access the „P2“ or „P3“ functions (
Æ
section 8.3).
B
Press „ok“.
Display shows the start schedule of the 1
st
operating period in blink
mode.
Fig. 32 Start of 1
st
operating period
B
Use the „+“ and „-“ keys to define the operating start schedule.
B
Press „ok“.
Blinking display shows operating stop schedule for the 1
st
period.
B
Use the „+“ and „-“ keys to define the operating duration.
B
Press „ok“.
Blinking display shows the start schedule for the 2
nd
operating
period.
Fig. 33 Beginning of the 2
nd
operating period
If the water temperature inside the tank is less than 60 °C
and the incoming air temperature is between -10 °C and
+35 °C, the heat pump will be used as the sole heat
source. The electrical power will be activated when
these conditions are not achieved.
6720646160-09.1V
6720646160-15.1V
6720646160-16.1V
If the start of the 2
nd
operating period is defined within
the operating period of the 1
st
period, the end of
operation of the 1st period will be adjusted to the newly
defined value.
6720646160-35.1V
6720646160-39.1V
6720646160-40.1V