Art. No. 5071 TSM
Art. No. 5072 TSM
Art. No. 5073 TSM
Art. No. 5074 TSM
If an operation deactivates the energy saving mode, the device always executes the configured
operating function immediately as well (e.g. switching, dimming, etc.).
i
The communication object of the energy saving mode can either be used just for activation,
or alternatively just for deactivation, or if required, for the combined activation and
deactivation, too. In all cases, the telegram polarity can be configured in the ETS. Only
different polarities can ever be configured (e.g. "0" = mode inactive / "1" = mode active ) for
the combined activation and deactivation.
i
If the transmission flag is set, then other devices can be informed of the deactivation of
energy-saving mode through operation on the local device, causing them also to leave
energy-saving mode (precondition: all the devices are linked to the same group address
and the deactivation via an object must be possible in the parameterisation of the other
devices). When energy-saving mode is deactivated when the transmission flag is set, the
device sends an "Energy-saving mode deactivated" telegram to the bus, according to the
inverted activated telegram polarity.
i
Programming connections to the device and broadcast telegrams cause energy-saving
mode to be deactivated automatically.
Page 30 of 39
Software "Standard TSM 110x11"
Functional description