Art. No. 5071 TSM
Art. No. 5072 TSM
Art. No. 5073 TSM
Art. No. 5074 TSM
4.2.4.2.5 Scene extension function
For each rocker with the function set to "scene extension unit" the ETS indicates the "Function"
parameter which distinguishes between the following settings...
-
"Scene extension without storage function",
-
"Scene extension with storage function",
In the scene extension function, the push button sensor transmits a preset scene number
(1…64) via a separate communication object to the bus after a button-press. This feature
permits recalling scenes stored in other devices and also storing them, if the storage function is
used.
In the setting "Scene extension without storage function", a button-press triggers the simple
recall of a scene. If the status LED is configured as button-press display, it will be switched on
for the configured ON time. A long button-press has no further or additional effect.
In the setting "Scene extension with storage function", the push-button monitors the length of
the actuation. A button-press of less than a second results in a simple recall of the scene as
mentioned above. If the status LED is configured as button-press display, it will be switched on
for the configured ON time. After a button-press of more than five seconds, the push button
sensor generates a storage instruction. In so doing, a storage telegram is transmitted to the
bus. An operation lasting between one and five seconds will be discarded as invalid.
The parameter "Scene number..." specifies separately, for each button of the rocker switch,
which of the maximum of 64 external scenes is to be used after a button-press.
The status LEDs can be configured independently (see page 28).
Page 27 of 39
Software "Standard TSM 110x11"
Functional description