38
Operating Manual: FRWM-IP-GATE - IP-Gateway
EN
(3)
Install a new smoke alarm device
(see chapter 6.2 “Adding a smoke
alarm device to a radio group” on
page 26).
8.5 Gateway cannot be integrated
in the radio group
4
No connection between gateway
and an existing radio group.
4
Radio button (A) is illuminated red.
(A)
Possible causes:
Gateway is incorrectly positioned
•
Gateway is installed too close
or too far away from other
smoke alarm devices
Remedy:
(1)
Reset the radio module on the gate-
way (see chapter 5.1 “Gateway reset”
on page 25, step 2).
(2)
Correct the position of the gateway.
(3)
Reconnect the gateway, with power.
Radio group no longer in learning mode
•
Learning mode will be switched
off after 10 minutes
Remedy:
f
Return the radio group to learning
mode.
f
Use the splint pin (activation backup)
to press the radio button on the
smoke alarm device or the radio
button (A) on the gateway until the
signal LED lights up and then goes off
again, and then release.
5
Smoke alarm device in learning
mode.
5
Gateway in learning mode.
(A)