background image

eNet radio dimming actuator 1-gang mini

Parameters

Setting options, Basic setting

Explanations

command restarts the time for
the switch-off warning.
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.

Priority, lock-out protection

0...4
Basic setting: 1

Specifies the priority for recall-
ing and removing a scene of
type Lock-out protection for
the channel.
Note: 1 is the highest priority
and 4 the lowest. 0 means no
priority.

Activate lock-out protection
brightness value

0…100 %
Basic setting: 0 %

Defines the behaviour of the
output on activating the lock-
out protection.

Deactivate lock-out protection
brightness value

0…100 %
Basic setting: 0 %

Defines the behaviour of the
output on deactivating the
lock-out protection. Only vis-
ible when the priority for the
lock-out protection is 0.

Priority, restraint

0...4
Basic setting: 2

Specifies the priority for recall-
ing and removing a scene of
type Restraint for the channel.

Activate forced operation
brightness value

0…100 %
Basic setting: 100 %

Defines the behaviour of the
output on activating the forced
operation.

Deactivate forced operation
brightness value

0…100 %
Basic setting: 0 %

Defines the behaviour of the
output on deactivating the
forced operation. Only visible
when the priority for the forced
operation is 0.

Priority, wind alarm

0...4
Basic setting: 3

Specifies the priority for recall-
ing and removing a scene of
type Wind alarm for the chan-
nel.

Activate wind alarm brightness
value

0…100 %
Basic setting: 0 %

Defines the behaviour of the
output on activating the wind
alarm.

Deactivate wind alarm bright-
ness value

0…100 %
Basic setting: 0 %

Defines the behaviour of the
output on deactivating the
wind alarm. Only visible when
the priority for the wind alarm
is 0.

Priority, sun protection

0...4
Basic setting: 0

Specifies the priority for recall-
ing and removing a scene of
type Sun protection for the
channel.

12 / 16

82580733

14.10.2019

J0082580733

Содержание FM J 50700 UP

Страница 1: ...ty transformers ac cording to EN 61558 2 6 may be used These instructions are an integral part of the product and must remain with the end customer 2 Intended use Switching and dimming of lighting Ope...

Страница 2: ...er operation and signalling could vary from what is de scribed here 4 Information for electrically skilled persons 4 1 Fitting and electrical connection DANGER Mortal danger of electric shock Before c...

Страница 3: ...nsformers for halogen or LED lamps HV LED leading edge phase control Setting for incandescent lamps HV halogen lamps elec tronic transformers with halogen or LED lamps that can be dimmed according to...

Страница 4: ...than 4 seconds The status LED 4 flashes after 3 seconds The actuator is in programming mode for approx 1 minute Switch radio transmitter to programming mode see radio transmitter instructions Trigger...

Страница 5: ...for approx 5 seconds The actuator is reset to default setting Setting the minimum brightness The minimum brightness can be set within a range of approx 1 67 if e g the light flickers at low brightnes...

Страница 6: ...dissipation Operate inductive transformers with at least 85 nominal load For ohmic inductive mixed load maximum 50 proportion of ohmic load Otherwise in correct calibration of the dimmer may result P...

Страница 7: ...smitters and the Prog button are ignored Continuous off The output switches to con tinuously Off All operations of radio transmitters and the Prog button are ignored Advanced device settings Parameter...

Страница 8: ...on after a delay Repeated switch on commands restart the delay time If the load has not yet been switched on due to the delay when a switch off com mand comes then the load will remain off Note The s...

Страница 9: ...r remain on perman ently but only for the length of the run on time The run on time is restarted if actuation is repeated This parameter is directly connected to the Manual switch off of run on time p...

Страница 10: ...l LED trailing edge phase con trol Leading edge phase control Trailing edge phase control Basic setting Universal Specifies the dimming prin ciple for the selected output Universal Automatic calibrati...

Страница 11: ...value is above the set maximum brightness or below the minimum bright ness then the system will switch to the appropriate limit value Behaviour after the end of the disabling function On Off no chang...

Страница 12: ...Basic setting 2 Specifies the priority for recall ing and removing a scene of type Restraint for the channel Activate forced operation brightness value 0 100 Basic setting 100 Defines the behaviour o...

Страница 13: ...n is 0 Switch off brightness over shoot On Off Basic setting On Allows automatic switch off according to the brightness If the parameter is On then the light controller switches off automatically when...

Страница 14: ...Check manufacturer s instructions Exchange lamps for another type Cause 2 Dimming principle and lamps do not optimally match Check operation in another dimming principle reduce connected load as well...

Страница 15: ...current Cause 5 load failure Check load replace lamp For inductive transformers check primary fuse and replace if necessary Lamps flicker or buzz proper dimming not possible device buzzes Cause 1 Inco...

Страница 16: ...dimming actuator 1 gang mini ALBRECHT JUNG GMBH CO KG Volmestra e 1 58579 Schalksm hle GERMANY Telefon 49 2355 806 0 Telefax 49 2355 806 204 kundencenter jung de www jung de 16 16 82580733 14 10 2019...

Отзывы: