Jung DWPM17360AL Скачать руководство пользователя страница 1

LB management

Motion and presence detector

Motion and presence detector
Art. no.: DWPM17360WW
Motion and presence detector
Art. no.: DWPM17360AL

Operating instructions

1

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.

Serious injuries, fire or property damage possible. Please read and follow manual fully.

Danger of electric shock. Always disconnect before carrying out work on the device or load. In
so doing, take all the circuit breakers into account, which support dangerous voltages to the
device and or load.

Danger of electric shock. The device is not suitable for disconnection from supply voltage. De-
pending on the insert used, the load is not electrically isolated from the mains, even when the
device is switched off.

Do not press on the sensor window. Device can be damaged.

The device is not suitable for use as a burglar alarm or other alarm.

These instructions are an integral part of the product, and must remain with the end customer.

2

Device components

Figure 1: Device components

(1)

FM insert

(2)

Sensor top

(3)

Brightness sensor

(4)

Button Bluetooth 

Ʃ

(5)

Sensor window and status LEDs

(6)

Decor ring

1 / 13

82599323

25.10.2019

J0082599323

Содержание DWPM17360AL

Страница 1: ...o account which support dangerous voltages to the device and or load Danger of electric shock The device is not suitable for disconnection from supply voltage De pending on the insert used the load is not electrically isolated from the mains even when the device is switched off Do not press on the sensor window Device can be damaged The device is not suitable for use as a burglar alarm or other al...

Страница 2: ... from LB management Ceiling installation on flush mounted insert Product characteristics Functions directly on the cover Extension of the detection area in combination with 3 wire extension Operation with 2 wire or 3 wire extension rotary dimmer extension or push button Dimming light via extension with dimming insert Resetting to factory setting Push on cover for limiting the detection field Funct...

Страница 3: ...ert or press the Bluetooth button 4 for longer than 4 seconds The following applies during the self test The red status LED is illuminated The load is switched off Movements are not detected The device can be operated via extensions 4 Commissioning Install app on a mobile end device Requirement for operation via app is a mobile end device with Bluetooth interface running the Android operating syst...

Страница 4: ... restarted Adjust the brightness only in combination with dimming insert Long press on button cover at the top or bottom or push button Save switch on brightness only in combination with dimming insert Adjust the brightness Press the button cover over entire surface for longer than 4 seconds An push button cannot be used to save the switch on brightness Delete switch on brightness only in combinat...

Страница 5: ...se as a presence detector the device is installed for example above a workplace and monitors the surface below it For use as a motion detector the device is installed for example in the hallway Select a vibration free installation location Vibrations can lead to unwanted switching Avoid interference sources in the detection area Interference sources can trigger the mo tion detector e g heat source...

Страница 6: ...ows This reduces the effects of scattered light Fitting the cover Connect flush mounted insert properly and mount in accordance with the desired orienta tion of the cover see instructions for flush mounted insert Fit the cover on the flush mounted insert Switch on mains voltage If the red status LED flashes three times at repeated intervals the cover was previously connected to another insert If t...

Страница 7: ...ors cut out push on cover along the marked lines as required Push on push on cover Alternatively the detection field can also be limited via the app by reducing the sensitivity or switching off individual sensors Expanding the detection field To expand the detection field connect a 3 wire extension with presence or motion detector cover The main device also evaluates signals of the extension and i...

Страница 8: ...not be possible Briefly disconnect the device from the mains voltage Red LED lights up self test runs Within 1 minute after switching on the mains voltage press the Bluetooth Ʃ button for longer than 20 seconds At the conclusion of the self test or after 4 seconds the blue LED flashes slowly Coupling mode is active keep the Bluetooth Ʃ button pressed After approx 20 seconds the blue LED goes out a...

Страница 9: ...ity Adjustable in 5 steps for each sensor A C To restrict the detection field switch off indi vidual sensors To do this set the sensitivity to 0 Walking test On Checking the detection field The function automatically terminates after 5 minutes Reduced basic sensitivity On Reduced basic sensitivity for use in environ ments with interference sources Brightness set ting Switch on threshold Motion det...

Страница 10: ...ce simu lation is activated the lighting is switched on at the saved times depending on the bright ness Switch off takes place after the run on time has elapsed Detected motions prolong the run on time or the light is switched on de pending on brightness Times are not saved The dynamic run on time is not taken into ac count Alarm function On Off Default setting Off This function is used to monitor...

Страница 11: ...mediately after the run on time has elapsed The light is first dimmed to minimum bright ness within 30 seconds The run on time is thereby pro longed by approx 30 seconds If motion is detected dur ing the switch off warning then the run on time is re started and the light switches back to the switch on brightness Minimum bright ness 1 67 Default setting 5 Specifies the minimum settable brightness M...

Страница 12: ...ightness value with the app Cause 2 Device does not detect any motions Increase sensitivity with the app Switch on all sensors with the app Cause 3 Off for 0 5 5 hours or Continuous off is activated Activate the automatic mode with the app Device switches on without motions Cause 1 Presence simulation is activated Device switches at saved times Switch off the presence simulation with the app Cause...

Страница 13: ...he device Couple the devices Cause 2 The Bluetooth interface on the mobile end device is not switched on Switch on the Bluetooth interface 10 Conformity Albrecht Jung GmbH Co KG hereby declares that the radio system type art no DWPM17360 meets the directive 2014 53 EU You can find the full article number on the device The complete text of the EU Declaration of Conformity is available under the Int...

Отзывы: