5.2 Commissioning
Testing the detection area
Figure 4: Test setting
The motion detector is fitted and connected.
o
Pull off push-on cover (10)
o
Pull off decor ring (9).
o
Set
sens
adjuster (3) to
max
(figure 4).
o
Set
time
adjuster (4) to
test
.
o
Set
lux
adjuster (5) to
3
for brightness-independent switching.
o
Switch on mains voltage.
The motion detector carries out a brief calibration process. The LED display behind the
lens lights up during the calibration process. After that test mode is active and the lighting
is switched on for approx. 1 second. As long as motions are detected, switch-on will take
place again after a lockout time of approx. 3 seconds.
In test operation the motion detector operates independently of the brightness.
o
Leave the detection area and observe the switching behaviour.
If the motion detector switches on, then sources of interference must be hidden (see
Limiting the detection area).
o
Measure the detection area.
If the detection area is too large, limit the detection area (see Limiting the detection area).
If the detection area is too small, expand the detection area using an extension.
o
Make the operating settings for the run-on time, brightness threshold and sensitivity in
order to establish readiness for operation.
o
Attach decor ring (9).
5/8
82563813
J:0082563813
17.11.2011