Page 28 of 49
20320 1S IPS R
Configuration
Function
Options
Description
Output value (scene)
1 .. 64
Value which is sent to the extension
scene (KO195) by activation of the
light scene.
Activate shading scene
Goodbye?
active/inactive
When active, the shading scene
will be activated by activation of
the Welcome scene. The following
value will be sent to the extension
scene (KO215) by this.
Output value (scene)
1 .. 64
Value which is sent to the extension
scene (KO215) by activation of the
light scene.
Switching to operation mode
room controller Goodbye
active/inactive
When active, operation mode
of room controller will be sent
by activation of scene Welcome
according to parameter “Output
value (operation mode)”.
Output value (operation
mode)
Automatic (0)/
Comfort mode (1)/
Standby mode
(2)/
Night mode (3)/
Frost/heat protection (4)
Value which is sent to operation
mode of room controller (KO234)
by activation of Welcome scene.
6.5 Object table
i
Depending on the parametrization some objects might not be available.
ID
Name
Object function
Length Type
Flags
1
General
Reset of bus voltage
– Input
1 bit
[1.009] DPT_Trigger
C-W---
Object for triggering a bus reset.
6
Logic 1 - input -
presence monitoring
Trigger 1 (1 bit)
1 bit
[1.009] DPT_OpenClose C-WT--
Input object for the logic of presence detection. Can be linked e.g. with a door contact or with a
switch.
7
Logic 1 - input -
key card holder
Trigger 2 (1 bit)
1 bit
[1.001] DPT_Switch
C-WT--
Input object for the logic of presence detection with key card holder.
8
Logic 1 - input -
presence detector 1
Trigger 2 (1 bit)
1 bit
[1.018] DPT_Occupancy C-WT--
Input object for the logic of presence detection with presence detector.
9
Logic 1 - input -
presence detector 2
Trigger 2 (1 bit)
1 bit
[1.018] DPT_Occupancy C-WT--
Input object for the logic of presence detection with presence detector.