Product characteristics 

Automatic switch standard 

Sensitivity and brightness threshold settable  

Manual switch-on possible via extension insert, 2-wire, or installation button 

18 lens segments in 2 recording levels 

Extension of the detection area in combination with the 3-wire extension insert 

Detection area can be limited using cover plate 

Dimming inserts can only execute switching functions. 

Automatic switch universal 

Run-on time, sensitivity and brightness threshold settable  

Teach function to save the current brightness as the new brightness threshold. 

Operating mode switch for Automatic operation, Continuous on or Continuous off 

Short-time operation, e.g. to control acoustic signal encoders 

Manual switch-on possible via extension insert, 2-wire, or installation button 

With the dimmer insert, it is possible to change the brightness using a 2-wire extension 
insert 

Switch-on brightness can be saved with the dimmer insert 

With the dimmer insert, the dim-down function is possible at the end of the run-on time 

18 lens segments in 2 recording levels 

Extension of the detection area in combination with the 3-wire extension insert 

Detection area can be limited using cover plate 

High protection against ambient light 

Automatic operation  

The controller detects heat motions of people, animals and objects. 

The light is switched on if a person enters the monitored detection area and the brightness 
is below the set threshold.  
Each detected movement restarts the run-on time. 

The light is switched off if no more movement is detected in the detection area and the run-
on time has elapsed.  

Light oscillations e.g. due to the cooling of bulbs are prevented via interlock times in the 
automatic switch. No switching commands are performed during the interlock. 
Automatic switch standard approx. 3 seconds
Automatic switch universal: 0.2 to 3 seconds, dynamic. 
Automatic switch universal: The day/night and night/day switch-over is performed only after the 
brightness is above or below the threshold for approx. 10 seconds. This  prevents the motion 
detector from switching to Night mode is there is brief shadow or to Day mode if there is brief 
light. 

Behaviour in case of mains failure for automatic switch standard 

Less than 0.2 seconds: the old switching position is restored after mains return.  

0.2 seconds to approx. 1 seconds: when the power returns, the lighting is switched on 
again for the run-on time. 

Longer than 1 second: when the power returns, the motion detector carries out a self test 
for approx. 60 seconds. The lighting is switched on during the self test. Then the lighting 
switches off for the length of the run-on time.  

Behaviour in case of mains failure for automatic switch universal 

Less than 0.2 seconds: the old switching position is restored after mains return. 

0.2 seconds to approx. 2 seconds: when the power returns, the lighting is switched on 
again for the run-on time. 

Longer than 2 seconds: when the power returns, the motion detector carries out a self test 
for approx. 90 seconds. The lighting is switched on during the self test. Then the lighting 
switches off briefly, and then on again for the length of the run-on time.  

In the Continuous on and Continuous off operating modes, the light is switched on or off 
after the self-test. 

A power failure of longer than 2 seconds causes the loss of the switch-on brightness and 
the brightness threshold saved via the Teach function. 

3/14 

32540233 
J:0082540233 

26.07.2010 

Light Management  

Automatic switch 180° 1.10 m 

Содержание 1180 Series

Страница 1: ...r load At the same time take into account all circuit breakers that supply dangerous voltage to the device or load Danger of electric shock Device is not suitable for disconnection from supply voltage...

Страница 2: ...rating mode switch 8 Adjuster run on time 3 Function Intended use Automatic switching of lighting depending on the heat motion and ambient brightness Operation with concealed insert for dimming switch...

Страница 3: ...f bulbs are prevented via interlock times in the automatic switch No switching commands are performed during the interlock Automatic switch standard approx 3 seconds Automatic switch universal 0 2 to...

Страница 4: ...s 5 o Snap cover on 5 Automatic switch universal operation Switch on the light via extension A 2 wire extension or an installation button NO contact is connected o Press button for less than 0 4 secon...

Страница 5: ...r confirmation the lighting switches off briefly and then on again to the saved switch on brightness i The saved switch on brightness is deleted after a power failure Setting the operating modes pictu...

Страница 6: ...urrent brightness If the lighting is switched off then the switch on brightness is set i Switching or dimming via an extension is not possible Setting the Automatic operating mode o Move slide switch...

Страница 7: ...or the next minute so that it can measure the current brightness without being shaded For confirmation of saving the lighting is switched on for 3 seconds The motion detector then switches to the set...

Страница 8: ...h the dimmer inserts 6 Information for electrically skilled persons 6 1 Fitting and electrical connection DANGER Electrical shock when live parts are touched Electrical shocks can be fatal Before carr...

Страница 9: ...etection area Installing the motion detector cover i Use a surface mounted housing for surface installation i Electrical connection of the flush mounted insert see instructions for the insert The inst...

Страница 10: ...design cover 11 see Limiting the detection area o Press design cover 11 onto the motion detector cover 3 o Snap on slide switch 4 Installation for AS A ranges and SL500 picture 11 Installation AS A r...

Страница 11: ...m the insert by hand Expanding the detection area To expand the detection area connect a 3 wire extension insert with motion detector cover The motion detector of the main unit also evaluates motion s...

Страница 12: ...using an extension o Make the operating settings for the sensitivity and brightness threshold o Snap cover on Testing the detection area with automatic switch universal The insert is installed and th...

Страница 13: ...ration Follow up time approx 2 min Sensitivity 20 100 Installation height 1 10 m Detection angle 180 Detection area approx 10 x 12 m Universal automatic switch 180 1 10 m Art No 1180 1 Ambient tempera...

Страница 14: ...a description of the defect to our central customer service office ALBRECHT JUNG GMBH CO KG Service Center Kupferstr 17 19 D 44532 L nen Service Line 49 0 23 55 80 65 51 Telefax 49 0 23 55 80 61 89 m...

Отзывы: