11
1 Introduction
Relay module 4-channel
Analog input module 4-channel
Analog input module 8-channel
•
Four relay outputs controlled via the system bus by digital sig-
nals
•
Each relay is equipped with a changeover contact
AC 230 V / 3 A
•
Separate terminal strip per relay output
•
Automatic configuration after the module insert has been ex-
changed during service work
•
Dimensions (W x H x D): 22.5 mm x 103.6 mm x 101.5 mm
(without connection elements)
For further information: Refer to data sheet 705015
•
Four universal analog inputs
•
Supported measuring probes: Thermocouples, RTD tempera-
ture probes, resistance transmitters, resistance/potentiome-
ters or standard signals (current or voltage)
•
The analog inputs are electrically isolated from each other
•
Customer-specific linearization possible by using a formula or
up to 45 pairs of values
•
Limit value monitoring
•
Automatic configuration after the module insert has been ex-
changed during service work
•
A digital input (DC 0/24 V) is also provided
•
Dimensions (W x H x D): 22.5 mm x 103.6 mm x 101.5 mm
(without connection elements)
For further information: Refer to data sheet 705020
•
Eight analog inputs for RTD temperature probes Pt100, Pt500
or Pt1000 in 2-wire circuit
•
The analog inputs are not electrically isolated from each other
•
Limit value monitoring
•
Automatic configuration after the module insert has been ex-
changed during service work
•
A digital input (DC 0/24 V) is also provided
•
Dimensions (W x H x D): 22.5 mm x 103.6 mm x 101.5 mm
(without connection elements)
For further information: Refer to data sheet 705021
Содержание mTRON T
Страница 2: ......
Страница 5: ...5 Contents 8 2 System expansion system version 02 71 8 3 Training courses seminars 72 ...
Страница 6: ...Contents 6 ...
Страница 50: ...5 Installation 50 ...
Страница 62: ...6 Electrical connection 62 ...
Страница 66: ...7 Startup and configuration 66 ...
Страница 73: ......