8 Programming
76
8.4.6 Plotarea (zoom)
Defines the range of the input signal to be
recorded on the chart. The complete range
or an enlarged section can be recorded. In-
put is in percent. The low value designates
the point of the measurement range which
becomes the new zero. The high value des-
ignates the new end value. The entire
measurement range (scaling start to scaling
end) corresponds to 100%.
The low value is calculated as follows:
The high value is calculated as follows:
The difference between low and
high value must be at least 10%.
Display
Edit
Selection/input
with keys
Enter
Continue with
PLOTAREA
E
2 PLOTAREA
Select recording channel
h
,
R
E
2
2
2 LOW: 010 %
Input start of
presentation range of
measurement value
(in percent of the
measurement range)
h
,
R
,
l
,
r
E
Check:
0
≤
start
≤
90%
3
3
2 HIGH: 100 %
Input end of presentation
range of measurement
value (in percent of the
measurement range)
h
,
R
,
l
,
r
E
Check:
end
≤
100%
and end–start
≥
10%
h
forwards
R
backwards
(smallest value to be recorded – start of scaling) /
(end of scaling – start of scaling)
h
100%
(largest value to be recorded – start of scaling) /
(end of scaling – start of scaling)
h
100%
Содержание LOGOLINE 500d
Страница 106: ...9 Consumables 106 9 2 Removing and replacing the chart cassette S F ENTER E S F ENTER E...
Страница 108: ...9 Consumables 108 9 2 1 Changing the roll chart 1 5 2 6 3 7 4 8...
Страница 109: ...9 Consumables 109 9 2 2 Changing the fanfold chart 1 4 2 5 3...
Страница 110: ...110 10 Extra Codes and accessories 10 1 Converting the chart cassette 1 3 2 4...
Страница 113: ...10 Extra Codes and accessories 113 ER 8 Error Power L L L1 N 97 98 99 TxD RxD RxD TxD GND 8 1 8 2 8 3...
Страница 136: ......
Страница 137: ......
Страница 138: ......
Страница 139: ......