6 C
o
nf
ig
urat
io
n
36
6.11
Self-optimisation
Self-optimisation determines the controller parameters for PID or PI controllers.
The following controller parameters are defined: rt, dt, Pb1, Pb2, Cy1, Cy2, dF
If there is a large deviation between process value and set-
point when SO is activated, a switching level is determined
about which the process variable performs a forced oscilla-
tion during the SO procedure. The switching level is chosen
so that the process value does not exceed the setpoint, if
possible.
With a small deviation between setpoint and process value,
e.g. when the control loop has stabilised, a forced oscillation
about the setpoint is produced.