JUMO dTRON 16.1 B 70.3011 Скачать руководство пользователя страница 1

J

dTRON 16.1

Compact microprocessor controller

B 70.3011

Operating Manual

07.01/00346816

Содержание dTRON 16.1 B 70.3011

Страница 1: ...JdTRON 16 1 Compact microprocessor controller B 70 3011 Operating Manual 07 01 00346816...

Страница 2: ...still arise during start up you are asked not to carry out any manipulations on the unit which are not permitted You could endanger your rights under the warranty Please contact the nea rest office or...

Страница 3: ...ing in position and removing the controller chassis 7 3 3 Cleaning the front panel 7 4 Electrical connection 8 4 1 Notes on installation 8 4 2 Connection diagram 10 5 Operation 11 5 1 Displays and key...

Страница 4: ...19 6 4 Controller 21 6 5 Limit comparators 25 6 6 Outputs 27 6 7 Display 29 6 8 Ramp function 30 6 9 Programme controller 32 6 10 Interface 34 6 11 Self optimisation 36 7 Appendix 38 7 1 Configuratio...

Страница 5: ...oportional controller with PID structure Self optimisation Ramp function Programme function Programmable input filter 2 limit comparators 5 outputs with freely assigned functions Process value output...

Страница 6: ...itching analogue 3 0 1 2 Proportional controller falling characeristic reverse action rising characteristic direct action 5 0 1 2 Process value input Code Pt 100 001 Pt 1000 006 Fe Con J 040 Cu Con U...

Страница 7: ...controller O function H X X X Single setpoint controller S function X C X X Double setpoint controller switching switching H C X X Double setpoint controlller analogue switching X C H X X Double setpo...

Страница 8: ...3 Installation 6 3 Installation 3 1 Dimensions...

Страница 9: ...t the back of the panel compressing the springs until the latches snap into the notches provided and it is securely fixed in position h Press together the knurled areas top and bottom on the front pan...

Страница 10: ...ntact with live parts is possible when working on the instrument it has to be isolated on both poles from the supply A current limiting resistor interrupts the supply circuit in case of a short circui...

Страница 11: ...to incorrect settings on the controller setpoint data of parameter and configuration levels internal adjustments Safety devices independent of the controller such as overpressure valves or temperatur...

Страница 12: ...4 Electrical connection 10 4 2 Connection diagram V The electrical connection must only be made by properly qualified personnel...

Страница 13: ...s 2 Setpoint display green 7mm 4 digits 3 PGM key to select the parameters 4 Decrement key to alter values 5 Increment key to alter values 6 EXIT key to quit the levels 7 LED for ramp programme functi...

Страница 14: ...with P h Return to standard display with X Standard display The displays show the process value and the ac tive setpoint or the programme ramp setpoint The active setpoint can be changed here v Sectio...

Страница 15: ...meter sets Display switching of the parameter sets is via parameter Pb 1 v Section 6 4 Configuration level The basic functions of the controller are set here Settings can only be made after leaving th...

Страница 16: ...he setpoint parameter with D The setpoint parameter is accepted automatically after ap prox 2 sec display flashes briefly h Abort the input with X The value alters only within the permitted range of v...

Страница 17: ...n and its selection possibility is described in the appropriate column Positions which are not rele vant for the function are marked with an X in the column h Familiarise yourself with the controller...

Страница 18: ...ter time constant to adapt the digital input filter 0sec filter off C111 Transducer X X X Pt 100 0 Pt 1000 1 Fe Con L 2 NiCr Ni K 3 Pt10Rh Pt S 4 Pt13Rh Pt R 5 Pt30Rh Pt B 6 Cu Con U 7 NiCrSi NiSi N 8...

Страница 19: ...it1 0 Start end of value range for standard signals Example 0 20 mA 20 200 C SCL 20 SCH 200 SCL and SCH are simultaneously the calibration for the process value output v Section 6 6 SCH 1999 to 9999 d...

Страница 20: ...tion 0 Standard signal 0 20mA 1 Standard signal 4 20mA 2 Standard signal 0 10V 3 Standard signal 2 10V 4 k factory setting X position functionally not relevant Parameter Value range factory set Notes...

Страница 21: ...possible No access to parameter and configuration level No start of self optimisation Programme ramp stop Programme ramp running when configured Programme ramp stopped Programme ramp start Programme r...

Страница 22: ...unction 0 0 Key inhibit 1 1 Level inhibit 2 2 Programme ramp stop 3 3 Programme ramp start 4 4 Setpoint switching 5 5 Parameter set switching 6 6 Enabling limit comparators 7 7 k factory setting X pos...

Страница 23: ...arameter sets a logic input can be used to switch between them Both parameter sets can be displayed for setting the parameters h Change between the display of the parameter sets with P when parameter...

Страница 24: ...t 0 the controller has no D action rt 0 9999 sec 350 sec Reset time Influences the I action of the controller If rt 0 the controller has no I action Cy 1 0 5 999 9 sec 20 0 sec Duration of switching c...

Страница 25: ...ntroller output 1 Differential 2 controller output 2 For controllers with Pb 0 HYS 2 0 9999 digit1 1 0 y 0 100 100 0 Working point Output at x w Parameter Value range factory set Notes 1 On the displa...

Страница 26: ...nction 0 Single setpoint controller S function 1 Double setpoint controller 2 Proportional controller with falling characteristic indirect action 3 Proportional controller with rising characteristic d...

Страница 27: ...two inputs can be monitored with reference to the setpoint or a fixed value using two limit comparators Functions of the limit comparators lk2 lk3 lk4 lk5 lk6 lk7 lk8 lk1 lk1 lk6 Monitoring referred...

Страница 28: ...12 Limit comparator 1 LK1 and 2 LK2 LK1 LK2 X X no function 0 0 lk 1 process value input 1 1 lk 2 process value input 2 2 lk 3 process value input 3 3 lk 4 process value input 4 4 lk 5 process value i...

Страница 29: ...put 1 A A Limit comparator output 2 b b Programme end C C k factory setting X position functionally not relevant C112 Output signal on overrange X X X Output 0 limit comparators OFF 0 Output 100 limit...

Страница 30: ...X X K3 no function 0 Controller output 1 function 0 20mA 0 10V switching 1 Controller output 2 function 0 20mA 0 10V switching 2 Limit comparator output 1 function switching 3 Limit comparator output...

Страница 31: ...t and software version h Display the software version and unit of the process value with P I hold keys down C112 Decimal places unit X X X no decimal place degree Celsius 0 one decimal place degree Ce...

Страница 32: ...SP2 When the ramp end point is reached then the ramp setpoint is equal to SP Action on sensor break On sensor break the ramp function is interrupted The out puts act as for overrange or underrange can...

Страница 33: ...amp stop Re starting the ramp h Re start the ramp with D I or via the logic input Parameter Value range factory set Notes rASd 0 999 digit h or digit min1 0 ramp gradient 1 In the display with one or...

Страница 34: ...s possible to implement a setpoint programme with up to 4 profile segments The segment set points SP00 SP03 and the segment times t00 t03 are set at the operating level The time base can be configured...

Страница 35: ...amme end signal can be output and the programme can be held v Section 6 6 Outputs Action on sensor break On sensor break the programme is interrupted The outputs act as for overrange or underrange can...

Страница 36: ...ollers and instruments slaves The interface is a serial interface to RS485 standard The MODbus protocol serves as the data protocol C113 Programme function X X X Programme controller off 0 Programme c...

Страница 37: ...s 0 0 0 Address 1 0 1 Address 99 9 9 Interface parameters 9600 baud no parity 0 9600 baud odd parity 1 9600 baud even parity 2 4800 baud no parity 3 4800 baud odd parity 4 4800 baud even parity 5 k fa...

Страница 38: ...between process value and set point when SO is activated a switching level is determined about which the process variable performs a forced oscilla tion during the SO procedure The switching level is...

Страница 39: ...longer self optimisation is termi nated and the controller functions with the parameters which have been established h Store the parameters with X Hold down key for at least 2 sec H Starting SO is not...

Страница 40: ...t input no function 0 0 20mA 1 4 20mA 2 0 10V 3 2 10V 4 Logic input 1 BE1 and 2 BE2 BE1 BE2 no function 0 0 Key inhibit 1 1 Level inhibit 2 2 Programme ramp stop 3 3 Programme ramp start 4 4 Setpoint...

Страница 41: ...t 5 5 lk 6 process value input 6 6 lk 7 process value input 7 7 lk 8 process value input 8 8 lk 7 external setpoint 9 9 lk 8 external setpoint A A Output signal on overrange Output 0 LK1 2 OFF 0 Outpu...

Страница 42: ...0 0 Controller output 1 1 1 Controller output 2 2 2 Limit comparator output 1 3 3 Limit comparator output 2 4 4 Programme end 5 5 Programme function Programme controller ramp function off 0 Programme...

Страница 43: ...switching 4 Programme end switching 5 Controller output 1 4 20mA 2 10V 6 Controller output 2 4 20mA 2 10V 7 Process value output 0 20mA 0 10V 8 Process value output 4 20mA 2 10V 9 Instrument address...

Страница 44: ...tory set Notes SCL 1999 to 9999 digit1 0 Start value of value range for standard signals SCH 1999 to 9999 digit1 100 End value of value range for standard signals SPL 1999 to 9999 digit1 200 Display s...

Страница 45: ...band 2 controller output 2 dt 0 9999 sec 80 s Derivative time rt 0 9999 sec 350 s Reset time Cy 1 0 5 999 9 sec 20 0 s Switching cycle time 1 controller output 1 Cy 2 0 5 999 9 sec 20 0 s Switching cy...

Страница 46: ...7 Appendix 44 7 2 Setpoint priorities Input of setpoint...

Страница 47: ...in accordance with the configuration of the outputs The process value display indicates the process value The setpoint display flashes 1999 Over underrange of the external setpoint Limit comparators...

Страница 48: ...Pt 1002 200 850 C 0 1 25ppm C X X Pt 10002 200 850 C 0 1 25ppm C X X Fe Con L3 200 900 C 0 25 100ppm C X Fe Con J3 200 1200 C 0 25 100ppm C X NiCr Ni K3 200 1372 C 0 25 100ppm C X Cu Con U3 200 600 C...

Страница 49: ...circuit lead compensa tion can be provided by an external lead compensation resistor Rcomp Rline In addition the lead resistance can be compensated in software through process value cor rection 3 Tem...

Страница 50: ...Relay output K3 option Changeover contact Rating 3A 250V AC on resistive load Contact life more than 5 105 operations at rated load 3 Analogue output K3 option 0 2 10V Rload 500 min 0 4 20mA Rload 450...

Страница 51: ...ntroller Data back up EEPROM Supply 110 240V 10 15 AC 48 63Hz or 20 53V AC DC 48 63Hz Power consumption 5VA approx Electrical connection through screw terminals for wires up to 1 5mm2 and core end sle...

Страница 52: ...Electromagnetic compatibility EN 61 326 Interference emission Class B Immunity to interference Industrial requirements Housing for flush panel mounting to DIN 43 700 base material PC with plug in con...

Страница 53: ......

Страница 54: ......

Страница 55: ...0 0 23 43 y 1 100 24 43 y 2 100 24 43 dF 0 6 16 43 rASd 0 31 43 Configuration level Page C111 0000 16 18 20 27 38 C112 0000 26 27 29 39 C113 0010 24 28 40 C114 0100 28 41 SCL 0 17 42 SCH 100 17 42 SP...

Страница 56: ...Fax 49 661 60 03 6 07 E mail mail jumo net Internet www jumo de JUMO Instrument Co Ltd JUMO House Temple Bank Riverway Harlow Essex CM20 2TT UK Phone 44 12 79 63 55 33 Fax 44 12 79 63 52 62 E mail sal...