6 Safety Manual
53
8
Set limit value of the relay (function AF7) in the middle of the configured measuring
range. Connect positive terminal of a voltage source (24 V ±5 %, 500 mA) to the
terminal connection 22 via a resistor (240
Ω
, 5 W).
Connect the ground connection of the voltage source with the relay contact con-
nections 21 and 23.
Simulate an input signal close to the measuring range start using a resistance de-
cade, and verify whether the specified signal and the transformed analog output
signal correspond to the value expected (display value, current meter).
Measure the voltage between the connections 22(+) and 21(-), as well as between
22(+) and 23(-) using the voltage meter.
The measured voltage value between terminals 22 and 21 must be < 0.1 V, and
must be 22.8 V to 25.2 V between terminals 22 and 23.
Verification that the relay has not
switched below the configured
limit value.
9
Simulate an input signal close to the measuring range end using a resistance de-
cade, and verify that the input signal corresponds to the value expected (display
value). Measure the voltage between the connections 22(+) and 21(-), as well as
between 22(+) and 23(-) using the voltage meter. The measured voltage value be-
tween terminals 22 and 21 must be 22.8 V to 25.2 V, and be < 0.1 V between termi-
nals 22 and 23.
Verification that the relay has not
switched above the configured
limit value.
10
Disconnect line to the measurement input connection 51. The test piece must sig-
nal an error (display and LED). The current meter must display a value
≤
3.6 mA as
an analog output signal. Measure the voltage between the connections 22(+) and
21(-), as well as between 22(+) and 23(-) using the voltage meter. The measured
voltage value between 22 and 21 must be < 0.1 V, and must be 22.8 V to 25.2 V
between 22 and 23.
The relay therefore drops out.
Verification in the event of a mal-
function that the analog output
signal corresponds to failure in-
formation A, NE43, and the relay
has dropped out.
Step
Action
Please note
Содержание dTRANS T06
Страница 16: ...3 Mounting 16 3 Mounting 3 1 Dimensions...
Страница 18: ...3 Mounting 18 3 4 Dismounting Place screwdriver in release catch and press upwards 1 Remove housing upwards 2...
Страница 30: ...5 Startup of the device 30 Here is a summary of the parameters from the figure above...
Страница 31: ...5 Startup of the device 31...
Страница 40: ...6 Safety Manual 40 0 0 6 6 0 0 6 6 7 0 0 6 0 0 6 0 0 6 0 0 6 8...
Страница 59: ...6 Safety Manual 59...
Страница 79: ...8 Device info 79...
Страница 103: ...12 What to do if 103...
Страница 104: ...13 Certificates 104 13 Certificates SEBS A 093409 14 V1 0...
Страница 110: ...13 Certificates 110...
Страница 111: ......