6 Technical
data
Meas. input
Designation
Range
Meas. accuracy
1
/
ambient tempera-
ture error
Recognition of ...
Probe short-
circuit
Probe break
Resistance
thermometer
Pt100 EN 60 751
-200 to +600°C
0.1%/
≤
100ppm/°C
yes
yes
Pt1000 EN 60 751
-200 to +600°C
0.1%/
≤
100ppm/°C
yes
yes
KTY2X-6 (PTC)
-50 to +150 °C
1%/
≤
100ppm/°C
yes
yes
Resistance 0 — 3000
Ω
customer table
3
0.1%/
≤
100ppm/°C
3
= 0
Ω
yes
Measuring current with Pt100: 0.2 mA, with Pt1000, KTY2X-6 and resistance: 0.02 mA
Lead compensation is settable via the parameter Lead compensation resistance
.
Total resistance (lead) must not exceed 320
Ω
with Pt100 and 3200
Ω
with Pt1000, KTY2X-6 and resistance.
Thermo-
couples
Fe-Con J EN 60 584
-200 to +999 °C
0.4%/
≤
100ppm/°C
2
no
yes
Fe-Con L DIN 43 710
-200 to +900 °C
0.4%/
≤
100ppm/°C
2
no
yes
NiCr-Ni K EN 60 584
-200 to +999 °C
0.4%/
≤
100ppm/°C
2
no
yes
-10 to 60 mV
customer table
3
0.1%/
≤
100ppm/°C
3
no
yes
For the voltage input (-10 to 60 mV), the terminal temperature compensation for thermocouples can be used.
Internal terminal temperature compensation can be switched off through the setup program (0°C).
Содержание B 70.1050.0
Страница 1: ......
Страница 6: ...2 Mo 2 Montage 55 C 90 1 2 Demontage...
Страница 23: ......
Страница 24: ......
Страница 25: ......
Страница 26: ...Overview of operation...
Страница 30: ...2 Asse 2 Assembling 55 C 90 1 2 Disassembling...
Страница 32: ...3 Electrica 3 2 Connection diagram V The electrical connection must only be carried out by specialist personnel...
Страница 41: ...5 Operation...
Страница 47: ......
Страница 48: ......
Страница 49: ......
Страница 54: ...2 Mo 2 Montage 55 C 90 1 2 D montage...
Страница 71: ......
Страница 72: ......