5 Electrical connection
✱
✱
Insulate the screen at the cable end with heat shrink tube.
✱
Apply core ferrules to the ends of the conductors.
Core ferrule dimensions see Chapter 5.1 “Installation notes”, page 15.
Connecting
the cables
The electrical connection for the surface-mountable housing is easily
accessible when the device is folded out.
~
20
(1)
The connection cable between sensor and transmitter must be a shielded cable
with a diameter of 8 mm max.
The device contains a guide plate that ensures an optimum cable path. After
laying the cables, the cable cover (1) must be attached until it clicks, like
shown above. This is important to ensure the electrical safety!
The sensor cables are run to the plug-in screw terminals and must have a strain
relief.
The cable clip (3) must only be screwed down (see next page) by a 3.5x6.5 pan
head screw! A longer screw may cause a hazardous voltage to be contacted to
the shielding!