6 Operation
32
Locked =
No manual mode, control via JUMO AQUIS 500.
Momentary =the outputs are active as long as the
or
key is pressed.
action
Switching = the outputs are active if the
or
key is pressed. If the
corresponding key is pressed again, the output becomes inactive
again.
Activate
manual mode
The device is in display mode
✱
Press the
and
keys for less than 2 seconds.
The word MANUAL appears in the status line of the display.
Control is no longer through the JUMO AQUIS 500. The output level of the
controller channels is 0%.
Controller channel 1 is activated by the
key. In this case the output level of
controller channel 1 is 100%.
Controller channel 2 is activated by the
key. In this case the output level of
controller channel 2 is 100%.
Deactivation
✱
Press the
key.
Control is once again through the outputs of the device.
The word MANUAL appears in the status line of the display.
Overview of
MANUAL/
Simulation
mode
You can display which outputs and/or controllers are in MANUAL mode.
The device is in "normal display" mode.
Press the
key several times for less than 2 seconds (the number of times
varies depending on the equipment and configuration of the device).
Output level of
controller
channels
The device is in "normal display" mode
Press the
key several times for less than 2 seconds (the number of times
varies depending on the equipment and configuration of the device).
EXIT
If the
and
keys are pressed for longer than 3 seconds, the device goes
into HOLD mode.
Then the outputs of the device respond according to the default settings.
To exit HOLD mode, press the
and
keys for longer than 3 seconds.
EXIT
EXIT
EXIT