Operator responsibility – Safety instructions
16
Immersion cooler
FT902
FT903
Working temperature range
°C
-90 ... 30
Temperature stability
°C
±1
Temperature selection
digital
Temperature indication
LED
Resolution
°C
0.1
Temperature control
PID1
Cooling capacity FT903
°C
20
10
0
-10
-20
-30
(Medium ethanol)
kW
0.3
0.29
0.27
0.26
0.25
0.24
Cooling capacity FT903
°C
-40
-50
-60
-70
-80
(Medium ethanol)
kW
0.23
0.21
0.18
0.13
0.05
Cooling capacity FT902
°C
20
10
-20
-40
-80
(Medium ethanol)
kW
0.3
0.27
0.24
0.2
0.07
Cooling compressor
2-stage
Refrigerant 230 V / 50 Hz
115 V / 60 Hz
R404A/R23
R404A/R23
Electrical connections:
Pt100 external sensor
Pt100
Overall dimensions (WxDxH)
cm
38x55x60
Immersion probe (Lxdia.)
cm
-------
see dimensions page 18
Immersion probe, flexible
(Lxdia.)
cm
65x1.5
Connection tubing (L)
cm
160
Noise level, distance 1 m
dBA
60
Weight
kg
50
50
Ambient temperature
°C
5 ... 35
5 ... 40
Mains power connection
V/Hz
230/50/60
Current input
A
6
6
Mains power connection
V/Hz
115/60
-
Current input
A
12
-
All measurements have been carried out a: rated voltage and frequency. Ambient temperature
20 °C.
Содержание FT401
Страница 8: ...Operator responsibility Safety instructions 8 2 2 EC Declaration of Conformity...
Страница 9: ...Immersion Coolers 9...
Страница 10: ...Operator responsibility Safety instructions 10...
Страница 12: ...Operator responsibility Safety instructions 12...
Страница 13: ...Immersion Coolers 13 2 3 1 Warranty conditions...