3.1
Purpose
The sample water cooler is suited for the
use in heating circuits up to a heat water
temperature of maximum 100° C (212°F).
The sample water cooler serves the purpose
of removing hot water samples concerning
the feed water, the boiler water and the con-
densate.
4.
Installation
4.1
General
ATTENTION
(see chapter “Security Advices and Dan-
gers in Case of Non-compliance”)
The installation may only be effected by
trained personal.
The chapter “Intended Use” has obligatorily
be observed!
The pipe line has to be able to carry the
sample water cooler safely.
If not a mechanic damage to the pipe line
can occur right up to a breakage. Water
damages can result from this. Persons close
to the sample water cooler are exposed to a
health hazard.
The pipe lines have therefore to be addition-
ally fixated respectively supported.
For an easy operation and maintenance
the indicated distances have to be impera-
tively observed (see chapter “Installation Di-
mensions JPK 3”).
Above and below the sample water cooler
the free space should not be less than
250mm. These distances are necessary in
order to be in a position to effectuate and
easy operation and maintenance in a
proper way.
For the shut-off of the cooling water a sep-
arate cooling water intake valve [on site] is
required. It has to be mounted before the
sample water cooler.
For maintenance purposes the sampling
conduit before the sample water ball cock
should be capable of being shut-off by
means of a valve – on site.
The sample water cooler have to be pres-
sure free if the valve is being closed!.
4.1.1 Transport / Stocking
Transport:
The device has to be transported carefully!
Stocking:
Dry, frost-resistant storage location
Permitted storage temperature:
0°C up to 40° C (32°F up to 104°F)
4.1.2 Requirements concerning the
Mounting Place
The installation room has to be dry and
frost resistant! Unauthorized persons
mustn’t have access to the sample cooler!
4.1.3 The Build-in Position
ATTENTION
(see chapter “Security Advices and Dan-
gers in Case of Non-compliance”)
Install the sample water cooler always in
vertical position (± 5°)!
Indication
Other uses are considered as not
intended, and are not permitted.
The JUDO Water Treatment Com-