Wärtsilä JOVYTEC PNT 1000VA
–
3000VA BAX 3313_en
- 32 -
13.
Maintenance
In case of longer standstill of the UPS (>4 weeks) the battery has to be charged monthly. For this charging you
only have to connect the UPS to the mains for a charging time of at least 8 hours.
However we recommend a charging time for about 24 hours.
The battery in its standard version is maintenance-free. Please note the hints of the battery-manufacturer in
case of using a special battery.
The ventilation slots front- and backsides of the UPS have to be clean, without any dust or something soiling
to prevent a reduced air-exchange. Please observe the necessary distance to surrounding walls of at least
100 mm
.
Half a year you have to check up the perfect function of the UPS. Therefore you have to disconnect the UPS
from the mains with connected load / consumers.
We recommend the use of a remote control system in case of UPS systems which can’t be controlled
directly.
The lifetime of the fans is indicated with typical 20.000h. We recommend a punctual replacement.