Jøtul GF 400 BV Sebago Скачать руководство пользователя страница 16

16

138301_Rev_G   10.4.11

Optional Wall Thermostat or 

Remote Control

Use only a 750 millivolt DC two-wire circuit thermostat 

with this appliance. The thermostat should be placed 

in the same room as the heater, typically 5 feet off the 

floor. Avoid drafty areas or any area that may affect the 

accuracy of the thermostat. 

The thermostat should be connected to the stove us

-

ing a minimum of 16 gauge wire with a maximum length 

of 25 feet of wire.

Connect the two thermostat wire leads to the two 

left terminals on the terminal block located directly 

above the ignitor button.  Do not overtighten the con-

nections.  

IT IS NOT NECESSARY TO DISCONNECT ANY 

OTHER WIRES.

 See Fig. 26.

For thermostatic operation, the On/Off/T-Stat switch 

on the back of the stove must be in the T-stat position, 

and the pilot light must be running, as it is the power 

source for the thermostat.

At the thermostat, the two wires should be connect-

ed to the two connection screws on the thermostat base 

plate per the manufacturer’s instructions.

Remote Control

 When using a remote, the remote receiver should be 

wired to the terminal block the same way the thermo-

stat would be. See the instructions above. 

Follow the operating instructions included with the 

Remote Control unit.

CAUTION:
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN 

SERVICING THE CONTROLS.  WIRING ERRORS CAN CAUSE 

IMPROPER OR DANGEROUS OPERATION.  ALWAYS VERIFY 

PROPER OPERATION AFTER SERVICING THE APPLIANCE. 

Figure 26.  Valve and Accessory wiring diagram.

Flame Appearance / Air Shutter 

Adjustment

This stove is shipped from the factory equipped to burn 

Natural gas. If the stove has been converted for use with 

propane, the Air Shutter may require adjustment to 

achieve the desired flame appearance. Other installation 

related variables can also affect the flame picture. The Air 

Shutter may be opened or closed to provide the best flame 

picture for your specific installation.

Too large an air opening

 - the appliance will generate a 

flame that is blue and transparent, or an “anemic” flame.

Too small an air setting

 - the appliance will generate 

very long yellow flames resulting in soot.  Sooting pro-

duces black deposits on the logs, on the inside walls of the 

appliance, and potentially on the exterior termination cap. 

Sooting is caused by incomplete combustion in the flames 

and lack of combustion air entering the air shutter open-

ing.

Air Shutter Adjustment should be done only by a qualified 

gas technician.

 

1.   Reach under the right side of the stove and loosen the 

wingnut located closest to you. See fig. 25. Slide the 

wingnut stud forward to open the air shutter and back 

to provide less air. Make adjustments in small incre

-

ments. 

2.  Tighten the wingnut to secure the shutter at the de-

sired setting.

3.  Allow the stove to burn for 30 minutes on the HIGH set-

ting, observing the flame continuously. If the flame ap-

pears weak, slow, or sooty, repeat the process described 

above until the flame is as desired. 

Figure 25.    Loosen the wingnut to adjust the air shutter.

TH

TP
TH

TP

ON

OFF

TSTAT

Yellow

Purple

White

Orange

Red

Black

White

Black

Содержание GF 400 BV Sebago

Страница 1: ...r future reference QUEFAIRESIVOUSSENTEZUNEODEURDEGAZ Ne pas tenter d allumer l appareil Ne touchez aucum interrupteur Ne pas vous servir des t l phones se trouvant dans le b timent o vous trouvez Appe...

Страница 2: ...d air intake must be used Installation shall be in strict compliance with the manufacturer s instructions A copy of the installation instructions must remain with the appliance or equipment at the com...

Страница 3: ...space below You may also wish to attach your purchase receipt to this page for future reference MODEL NAME J tul GF 400 BV Gas Stove SERIAL NUMBER _______________________________ DATE OF PURCHASE ____...

Страница 4: ...E APPLIANCE IS INSTALLED SEE PG 11 With Short Legs reduce height by 2 1 4 51 mm 13 330 mm Rear Exit 23 1 2 597 mm C L 6 3 4 171 mm 24 609 mm 28 711 mm 26 3 4 679 mm 13 330 mm 4 1 2 114 mm 13 1 4 336 m...

Страница 5: ...ing if a proposed installation is acceptable Any requirement that is requested by the local authority having jurisdiction that is not specifically addressed in this manual defaults to local code In th...

Страница 6: ...doivent tre avertis des dangers des temp ratures de surface lev es et devraient rester l cart pour viter les br lures ou l inflammation des v tements Young children should be supervised while they ar...

Страница 7: ...Maintain clearances to combustibles as noted above Width 32 81 cm Depth 24 61 cm Height 61 155 cm Approved Wall Pass Through Use only 4 Simpson Dura Vent Wall Thimble 3143 to pass the vent pipe throu...

Страница 8: ...e B cap is required See diagrams page 10 Venting on the Sebago CANNOT be less than 4 in diameter or greater than 4 in diameter Any unused flue or masonry enclosure can be used as a passage way for ven...

Страница 9: ...NENT When installing at an altitude above 2000 the mini mum vertical rise becomes 12 from the draft hood Figure 6 Venting through a masonry chimney Listed termi nation cap required Storm collar requir...

Страница 10: ...90 Elbows Minimum chimney height from Draft Hood is 7 feet Minimum chimney height from Draft Hood is 7 feet Maximum chimney height off Draft Hood is 35 feet Minimum chimney height off Draft Hood is 7...

Страница 11: ...IAN IN ACCORDANCE WITH THE MANUFACTURER S INSTRUCTION AND ALL CODES AND REQUIRE MENTS OF THE AUTHORITY HAVING JURISDIC TION FAILURE TO FOLLOW THESE INSTRUC TIONS COULD RESULT IN SERIOUS INJURY OR PROP...

Страница 12: ...two support brackets at the front of the firebox and push the plate back toward the rear of the firebox 11 CHANGE THE PILOT ORIFICE From within the firebox remove the Pilot Head by pulling it straight...

Страница 13: ...rews securely 16 Install the identification labels to the stove so that they can be seen by any person that may be servicing the stove Label A apply to back of stove Label B apply to stove s rating pl...

Страница 14: ...2 0 14 9 The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing on that system at test pressures in excess of 1 2 psig 3 5 kP...

Страница 15: ...T THE PILOT ASSEMBLY OPENING Do not pile the embers against the burner skirt edges See fig 24 Figure 20 Engage the holes in the underside ot the Right Log with the peg in the burner skirt Figure 22 In...

Страница 16: ...PLIANCE Figure 26 Valve and Accessory wiring diagram Flame Appearance Air Shutter Adjustment This stove is shipped from the factory equipped to burn Natural gas If the stove has been converted for use...

Страница 17: ...ob located in the center of the valve face Fire intensity can be adjusted up to 50 between the LOW and HIGH settings See fig 29 NO SMOKE OR SOOT SHOULD BE PRESENT CHECK LOG PLACEMENT IF ANY SOOT OR SM...

Страница 18: ...he stove is cold and there are NO hot embers 5 Remember this appliance has a continuous burning pilot flame Exercise caution when using products having combustible vapors Always shut off gas supply wh...

Страница 19: ...ealed according to the manufac turer s instructions provided at the initial installation Burner and Logset Periodically inspect the Firebox Valve Compartment Convection Airways and optional Blower to...

Страница 20: ...6 flange head hex bolts as shown in fig 34 4 Attach the Duct Deflectors using the two 7 x 1 2 screws together with the finger guard mounting screws already in place See 7 and 11 in fig 33 5 Install th...

Страница 21: ...ically when the stove cools down If automatic blower circulation is not desired place the blower control switch in the MANUAL position Figure 37 Blower Wiring Diagram Figure 36 Blower Controls CAUTION...

Страница 22: ...eir own against the wall Push them back against the Rear Panel 6 Reinstall the Logset See page 21 BE CERTAIN THAT NO EMBERS ARE BLOCKING THE PILOT ASSEMBLY OPENING 7 Replace the Glass Frame Slide the...

Страница 23: ...APPAREIL CONVERTI EST CHEQUE SUIVANT LES CRITERES ETABLIS DANS LES INSTRUCTIONS DE PROPRIETAIRE PROVISIONNEES AVEC L EQUIPEMENT Derating Procedure 1 Follow Steps 1 10 of the Fuel Conversion procedure...

Страница 24: ...24 138301_Rev_G 10 4 11 ONLY USE REPLACEMENT PARTS PROVIDED BY AN AUTHORIZED J TUL DEALER Figure 44 J tul GF 400 BV Sebago Illustrated Parts Breakdown...

Страница 25: ...on Kit to Natural Gas 156006 High Altitude Adjustment Kit LP 155885 High Altitude Adjustment Kit NG 155895 45 Gasket Pilot Asy 129670 48 Control Door 2211892 49 Spacer 118040 50 Fender Washer 1 50 dia...

Страница 26: ...osts associated with the repair of gas controls plumbing burners log set or sheet metal firebox beyond the warranty period 5 Damage caused by unauthorized modification use or repair 6 Damage to enamel...

Страница 27: ...knob Never use tools If the knob will not push in or turn by hand do not try to repair it Call a qualified technician Force or attempted repair may result in a fire or explosion D Do not use this appl...

Страница 28: ...beginning the installation it is important that these instructions be carefully read and understood J tul maintains a policy of continual product development Consequently products may differ in speci...

Отзывы: