
10
138301_Rev_G 10.4.11
Approved B-Vent Configurations
Listed B-Vent Termi-
nation Cap required.
Maximum
total horizontal
anywhere
in venting
configuration
is 4 feet.
Listed B-Vent
Termination
Cap required.
Max. Four, 45°
or Three, 90°
Elbows
Figure 10.
Figure 9.
Figure 8.
Figure 7.
Listed B-Vent
termination cap
required.
Minimum
chimney height
from Draft Hood
is 7 feet.
Maximum
horizontal off-
set anywhere
in venting
configuration
is 4 feet.
Listed B-Vent
termination cap
required.
Max. Four, 45°
or Three, 90°
Elbows
Minimum
chimney height
from Draft Hood
is 7 feet.
Minimum
chimney height
from Draft Hood
is 7 feet.
Maximum
chimney
height off
Draft Hood is
35 feet.
Minimum
chimney
height off
Draft Hood is
7 feet.
NOTE:
Installation at
altitude greater
than 2000’ re-
quires
minimum
12 ft.
vertical rise
from Draft Hood.
Maximum
total horizontal
offset anywhere
in venting
configuration is
4 feet.
NOTE:
Installation at
altitude greater
than 2000’ re-
quires
minimum
12 ft.
vertical rise
from Draft Hood.
NOTE:
Installation at
altitude greater
than 2000’ re-
quires
minimum
12 ft.
vertical rise
from Draft Hood.
NOTE:
Installation at
altitude greater
than 2000’ re-
quires
minimum
12 ft.
vertical rise
from Draft Hood.