Co-linear Vent Installation

This appliance may be vented through a masonry or
Class A prefabricated chimney using a Co-linear Flexible
Vent system approved for use with a solid-fuel burning
fireplace. When installed in the manner described below,
this system can improve the performance of the appli-
ance in cold climate situations, as well as simplify the
vent installation. See fig. 9.

These installation requirements must be followed:

1.

1.

1.

1.

1. Prior to the installation the chimney flue must be

thoroughly cleaned and inspected by a qualified
chimney service person.

2.

2.

2.

2.

2. In a masonry chimney, a fireclay liner must be present

the entire length of the chimney.

3.

3.

3.

3.

3. Prefabricated chimneys must be UL 103 or ULC S-629

listed and have a minimum INSIDE diameter of 6
inches, (150 mm).

4

4

4

4

4..... No appliance can be installed into a chimney flue

serving any other appliance of any kind.

5

55

55.....

THE AIR INTAKE FLEX PIPE MUST EXTEND BEYOND THE
DAMPER AREA OF THE FIREPLACE. 

 If the intake flex

duct does not extend the full length of the chimney
and connect to both the unit and the termination cap,
A METAL BLOCK OFF PLATE MUST BE CONSTRUCTED
AND INSTALLED ABOVE THE UNIT PRIOR TO THE END
OF THE INTAKE FLEX AND MUST COMPLETELY SEAL
THE CHIMNEY FLUE FROM THE ROOM.

Consult with the local code authority having jurisdic-

tion before proceeding with this type of installation.

Refer to the vent manufacturer’s instructions for

specific installation requirements.

WARNING: FAILURE TO POSITION THE PARTS AND

STOVE IN ACCORDANCE WITH THESE  DIAGRAMS OR
FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED
FOR USE WITH THIS APPLIANCE, MAY RESULT IN PROP-
ERTY DAMAGE OR PERSONAL INJURY. BE SURE TO
MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES
AS DEFINED IN THIS MANUAL AND IN THE INSTRUCTIONS
PROVIDED WITH EACH VENT COMPONENT.

Figure 9.
Co-linear Adaptor installed through a masonry chimney.

Figure 10.  Simpson Dura-Vent #923GCL Co-linear Adaptor.

GF 100 DV II:

A :  16 3/4”

B :  20 3/4”

GF 200 DV II:

A :  18”

B :  22”

Add 2 1/4” with Long Legs.
Subtract 1” with Plinth

Venting Through a Fireplace

A

B

Intake Air

Exhaust Gas

High Wind

Cap

Max.

Co-linear

Height 15 ft.

(10.66 m)

Min.

Co-linear

Height 8

ft.

(2.44 m)

Air Intake Flex

pipe must

extend above

the damper.

Sealed

Damper

Max.

Offset 24”
(609 mm)

Содержание GF 100 DV II Nordic QT

Страница 1: ...gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not us...

Страница 2: ...2...

Страница 3: ...ment 18 Air Shutter Adjustment 19 Wall Thermostat 20 Remote Control 20 Log Set Installation 20 System Check 21 Operation 22 Maintenance 22 Glass Replacement 22 Optional Blower 24 Illustrated Parts Bre...

Страница 4: ...k Kit 155815 Fuel Conversion Kit NG 155629 Wall Thermostat 750003 Remote Control 129706 Mobile Home Floor Bracket Kit 154342 Universal Leg Leveler Kit 156096 The J tul GF 100 DV II Nordic QT is a Dire...

Страница 5: ...J tul GF 200 DV II Nordic QT is a Direct Vent gas heater designed as a sealed combustion air circulat ing gas appliance for residential applications This appliance is approved for installation using...

Страница 6: ...F ANY PART HAS BEEN UNDER WATER Call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which may have been under water Ne pas se se...

Страница 7: ...ection must extend the full width and depth of the appliance It is not necessary to remove carpeting vinyl or linoleum from underneath the floor protection See fig 1 Safety Information Your stove will...

Страница 8: ...4 in 603 mm Long Legs 27 in 686 mm J tul GF 100 DV II J tul GF 200 DV II Nordic QT Lillehammer A A A A A 49 in 1245 mm 51 1 2 in 1308 mm B B B B B 47 1 2 in 1206 mm 50 in 1270 mm C C C C C 46 in 1168...

Страница 9: ...M A SEAL BETWEEN THE INNER AND OUTER PIPES NEVER MODIFY ANY VENTING COMPONENT OR USE ANY DAMAGED VENTING PRODUCT THE GAS APPLIANCE AND VENT SYSTEM MUST BE VENTED DIRECTLY TO THE OUTSIDE OF THE BUILDIN...

Страница 10: ...these conditions Use approved vent manufacturer s Wall Straps to support an offset pipe run at three feet intervals to avoid excessive stress on the offsets A firestop is required at every floor Fire...

Страница 11: ...ngth of the chimney and connect to both the unit and the termination cap A METAL BLOCK OFF PLATE MUST BE CONSTRUCTED AND INSTALLED ABOVE THE UNIT PRIOR TO THE END OF THE INTAKE FLEX AND MUST COMPLETEL...

Страница 12: ...illustrated in fig 7 Vent Termination Diagram The horizontal termination cap must maintain a 3 clearance to any overhead combustible projections 2 1 2 or less It must also maintain 12 clearance from p...

Страница 13: ...m the rear shroud of the stove 2 Align the holes in the wall shield with the holes in the rear shroud 3 Secure the wall shield to the stove with the two 1 4 hex head screws See fig 16 Figure 14 Termin...

Страница 14: ...s particularly where windy conditions pevail In accordance with CSA B149 1 Installation Codes In accordance with the current ANSI Z223 1 NFFPA 54 National Fuel Gas Code Note Local Codes and Regulation...

Страница 15: ...N STRUCTION AND SAFETY STANDARD TITLE 24 CFR PART 3280 THIS APPLIANCE IS ONLY FOR USE WITH THE TYPE OF GAS THAT IS INDICATED ON THE STOVE S RATING PLATE A GAS CONVERSION KIT IS PROVIDED WITH THE NORDI...

Страница 16: ...ew variable regulator tower being sure that the gasket is properly positioned and tighten screws securely 13 Install the identification labels to the stove so that they can be seen by any person that...

Страница 17: ...ANSI Z223 1 NFPA 54 OR CAN B149 All codes require a gas shut off valve gas cock and union to be installed in the supply line and in the same room as the appliance This allows for the disconnection of...

Страница 18: ...TECHNICIAN IN ACCORDANCE WITH THE MANUFACTURER S INSTRUCTIONS AND ALL CODES AND REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION THE INFORMATION LABEL MUST BE FILLED OUT BY THE INSTALLER AND APPLIED...

Страница 19: ...ttom of the firebox directly behind the gas valve See fig 26 2 Push the stem back to decrease air or pull it forward to increase air Make adjustments in small increments 1 8 and allow the burner to se...

Страница 20: ...ove Follow the operating instructions included with the Remote Control unit CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING THE CONTROLS WIRING ERRORS CAN CAUSE IMPROPER OR DANGEROUS OPE...

Страница 21: ...uld project out of the pilot hood 1 at all three ports See figs 30 3 BURNER ADJUSTMENT This stove is equipped with a variable gas control valve that allows easy adjust ment of the flame height appeara...

Страница 22: ...ABRASIVE SOLUTIONS These can cause stains Coffee tea and fruit juices will also stain Avoid contact with metal objects Trivets kettles or pots can damage the enamel Operation Familiarize yourself wit...

Страница 23: ...asket to expose the adhesive 4 Apply the gasket to the panel wrapping the adhe sive side down around the panel edge See fig 34 5 Insert the gasketed glass panel into the frame and press the retainer c...

Страница 24: ...ENT ANSI NFPA 70 NATIONAL ELECTRICAL CODE OR CSA C22 1 CANADIAN ELECTRICAL CODE THIS UNIT IS SUPPLIED WITH A THREE PRONG GROUNDING PLUG FOR PROTECTION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIRECT...

Страница 25: ...ER AND DANGEROUS OPERATION VERIFY OPERATION AFTER SERVICING ATTENTION AU MOMENT DE L ENTRENTIEN DES COMMANDES ETIQUIETEZTOUS LE FILS AVANT LE DEBRANCHEMENT ES ERREURS DE CEBLAGE PEUVENT ENTRATUN FONCT...

Страница 26: ...down Firebox Assembly Figure 39 A 1 2 3 4 4 4 4 4 4 5 6 7 8 10 11 12 13 33 24 28 27 25 26 24 29 30 31 20 21 22 17 16 15 14 23 19 22 22 18 63 47a 48 49 50 51 52 53 4 54 55 56 57 39 60 61 40 59 41 42 43...

Страница 27: ...s Frame Matte Black 22136592 Glass Frame J tul Iron 22136585 Glass Replacement Kit 155599 Parts List GF 100 DV II GF 200 DV II Firebox Assembly ALWAYS USE REPLACEMENTS PARTS PROVIDED BY AN AUTHORIZED...

Страница 28: ...28 J tul GF 200 DV II Lillehammer Illustrated Parts Breakdown Cast Iron and Associated Hardware J tul GF 100 DV II Nordic QT 2 7 8 6 5 9 4 3 1 12 11 10 10 10 2 10 Figure 41 Figure 40 1 3 4 2 2 4...

Страница 29: ...195247 10195248 6 Left Door 10425592 10425527 10425529 10425536 10425585 10425546 10425547 10425548 7 Right Door 10425692 10425627 10425629 10425636 10425685 10425646 10425547 10425548 Front Assembly...

Страница 30: ...and forward so that no gaps are evident at the panel joints as in Fig 44 8 Install the other Side Panel while holding the Upper Panel in position Adjust the panels so that the mortar joints align with...

Страница 31: ...water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 1 1 1 1 STOP Read thesafet...

Страница 32: ...he installation it is important that the these instructions be carefully read and understood J tul maintains a policy of continual product development Consequently products may differ in specification...

Отзывы: