CHAP.09 FAULT DIAGNOSIS AND TROUBLESHOOTING
09.1 PROBLEMS
PROBLEM
MAIN CHECKS TO BE PERFORMED
Much condensation
originates inside the stove
• Check the quality of the fuel used.
• Check the draught.
• Insufficient air intake size.
Smoke escapes when the
door is opened, the wood
burn poorly, or the glass
gets dirty
• If the fireplace is installed in a room in communication with a stairwell, with major depression that exists in the
local, close off the stairwell by installing a door.
• There are other appliances that use room air, creating low pressure. Use the fireplace when the other
appliances are off (excluded of the type “C” according to UNI 10683).
• Load the wood when there is no flame.
• The outside air inlets and/or the flue are partially or completely obstructed. Clean or remove the obstructions.
• Air inlet and/or canalisations not correctly done.
• Insufficient flue draught: there are horizontal sections or 90° bends, or the chimney cap is located under the
ridge of the roof (installation errors). Replace the horizontal sections with sections at 45°; raise the chimney
cap, or fit an antiwind cap.
• Check that the flue conforms to the indications given in
CHAP.07.1 - FLUE OR FUME EXHAUST
SYSTEM
, clean the flue and smoke baffle, open the damper, open the door slowly.
In accordance with the laws in force on safety for electrical appliances, a specialised Technical Service Center
or qualified personnel must obligatorily be contacted for all installation, maintenance or interventions that require access to
electrical parts.
WARNING
Do not use the device if the draft is not regular, and if combustion is not great.
WARNING