JOHNSON CONTROLS
83
SECTION 5 – TECHNICAL DATA
FORM 150.27-NM1
ISSUE DATE: 09/30/2015
55
UNIT DIMENSIONS - ENGLISH - FOUR COMPRESSOR
RELIEF
VALVE
INLET
OUTLET
H* - for 200/230 volt units, which require a larger electrical enclosure
YCrL
(4 Comp)
0064HE
0074HE
0084HE
0118HE
W
32.5
33.7
33.7
33.7
H
56.6
63.6
63.6
63.3
L
121.5
120.5
123.2
120.5
A
13.8
13.8
13.8
13.8
B
27.5
27.5
27.5
27.5
D
11.8
16
16
16
E
8.6
8.6
8.6
8.6
F
24.5
29
29
29
G
29
29
29
29
J
17.7
17.7
17.7
17.7
K
12.3
12.8
12.8
12.8
M
12.3
12.3
12.3
12.3
N
12.3
12.3
12.3
12.3
R
85
83
83
83
YCrL
(4 Comp)
0064HE
0074HE
0084HE
0118HE
S
3.5
4.5
4.5
4.5
T
116.7
115.7
118.3
115.7
U
24.7
23.7
26.3
22.1
X
21
22.2
22.3
22.2
AA
21
21
21
21
BB
50
50
50
50
CC
13.5
13.5
13.5
14
DD
30.7
33
33
33
EE
81.1
82.1
78.7
79.1
FF
37.3
34.9
34.4
34.8
GG-1
39.5
39.5
39.5
41
GG-2
39.5
39.5
39.5
41
HH
18.3
14.7
14.7
14.9
Notes:
1. Recommended service clearances:
Rear to wall - 20" (508mm)
Front to wall - 36" (915mm)
Top - 43" (1092mm)
Tube cleaning and removal - 132" (3353mm) either end
2. Relief valve connection sizes.
Low side (suction line) - 1/2" flare