![Johnson Controls York YCRL0064 Скачать руководство пользователя страница 153](http://html1.mh-extra.com/html/johnson-controls/york-ycrl0064/york-ycrl0064_installation-operation-and-maintenance_2023468153.webp)
JOHNSON CONTROLS
153
SECTION 10 – MAINTENANCE
FORM 150.27-NM1
ISSUE DATE: 09/30/2015
10
6/11/2010
123456789
10
POINT DESCRIPTION
ITEM REF
NUM
BACnet NAME
Point List Code
MODBUS ADDRESS
MODBUS
Data
Type Supported
ENG UNITS
BACnet
Object/Inst
ance
READ WRITE
S=Standard; O = Optional; N = Not Available
40
S2_EEV_OUT
AI_23
536
03,04
seconds
R
Sys 2 Suction Superheat ( EEV Models Only)
SSSSSSSSSS
41
NUM_COMPS
AI_24
537
03,04
count
R
Number of Compressors
SSSSSSSSSS
42
S1_OP_CODE
AI_25
538
03,04
index
R
Sys 1 Operational Code (Definition in
Table A)
SSSSSSSSSS
43
S1_FLT_CODE
AI_26
539
03,04
index
R
Sys 1 Fault Code (Definition in
Table B)
SSSSSSSSSS
44
S2_OP_CODE
AI_27
540
03,04
index
R
Sys 2 Operational Code (Definition in
Table A)
SSSSSSSSSS
45
S2_FLT_CODE
AI_28
541
03,04
index
R
Sys 2 Fault Code (Definition in
Table B)
SSSSSSSSSS
46
S1_DBG_CODE
AI_29
542
03,04
index
R
Sys 1 Debug Code
SSSSSSSSSS
47
S1_FAN_STAGE
AI_30
543
03,04
count
R
Sys 1 Condenser Fan Stage
SSSSSSSSSS
48
S2_DBG_CODE
AI_31
544
03,04
index
R
Sys 2 Debug Code
SSSSSSSSSS
49
S2_FAN_STAGE
AI_32
545
03,04
count
R
Sys 2 Condenser Fan Stage
SSSSSSSSSS
50
CONTROL_MODE
AI_33
546
03,04
count
R
Unit Control Mode
(0=Leaving Water, 1=Return Water, 2=Discharge Air, 3=Suction Press,
4=Cooling, 5=Heating)
SSSSSSSSSS
51
AR_TIME
AI_34
547
03,04
seconds
R
Anti-Recycle Time (Programmed)
SSSSSSSSSS
52
LCHLT_CUT
AI_35
548
03,04
F
°
R
Leaving Chilled Liquid Temp Cutout
SSSSSSSSSS
53
LOW_AMB_CUT
AI_36
549
03,04
F
°
R
Low Ambient Temperature Cutout
SSSSSSSSSS
54
SUCT_P_CO_HT
AI_37
550
03,04
PSIG
R
Low Suction Pressure Cutout Heating (HP Only)
SSSSSSSSSS
55
L_SUCT_P_CO
AI_38
551
03,04
PSIG
R
Low Suction Pressure Cutout (Cooling on HP units )
SSSSSSSSSS
56
H_DSCH_P_CO
AI_39
552
03,04
PSIG
R
High Discharge Pressure Cutout
SSSSSSSSSS
57
COOL_SETP
AI_40
553
03,04
F
°
R
Setpoint
SSSSSSSSSS
58
SP_SETP_S1
AI_41
554
03,04
F
°
R
Setpoint 1 (SP Control)
SSSSSSSSSS
59
CONTROL_RG
AI_42
555
03,04
F
°
R
Cooling Range
SSSSSSSSSS
60
SP_CTL_RG_S1
AI_43
556
03,04
F
°
R
Cooling Range 1 (SP Control)
SSSSSSSSSS
61
SP_SETP_S2
AI_44
557
03,04
F
°
R
Setpoint 2 (SP Control)
SSSSSSSSSS
62
HEAT_SETP
AI_45
558
03,04
F
°
R
Heating Setpoint (HP Only)
SSSSSSSSSS
63
SP_CTL_RG_S2
AI_46
559
03,04
F
°
R
Cooling Range 2 (SP Control)
SSSSSSSSSS
64
HEAT_RANGE
AI_47
560
03,04
F
°
R
Heating Range (HP Only)
SSSSSSSSSS
65
S1_DSCH_TEMP
AI_48
561
03,04
F
°
R
Sys 1 Discharge Temperature (EEV Only)
SSSSSSSSSS
66
S1_DSCH_SHEAT
AI_49
562
03,04
F
°
R
Sys 1 Discharge Superheat (EEV Only)
SSSSSSSSSS
67
S2_DSCH_TEMP
AI_50
563
03,04
F
°
R
Sys 2 Discharge Temperature (EEV Only)
SSSSSSSSSS
68
S2_DSCH_SH
AI_51
564
03,04
F
°
R
Sys 2 Discharge Superheat (EEV Only)
SSSSSSSSSS
69
LEAVING_HOT
AI_52
565
03,04
F
°
R
Leaving Liquid Hot Temp (R-410a)
SSSSSSSSSS
70
RETURN_HOT
AI_53
566
03,04
F
°
R
Return Liquid Hot Temp (R-410a)
SSSSSSSSSS
71
R_COOL_SETP
AI_54
567
03,04
F
°
R
Remote Setpoint
NNNNNNN
S
S
S
72
R_SP_SETP_S1
AI_55
568
03,04
F
°
R
Remote Setpoint 1 (SP Control)
NNNNNNN
S
S
S
73
R_SP_SETP_S2
AI_56
569
03,04
F
°
R
Remote Setpoint 2 (SP Control)
NNNNNNN
S
S
S
74
R_HEAT_SETP
AI_57
570
03,04
F
°
R
Remote Heating Setpoint (HP and YCWL HP)
NNNNNNN
S
S
S
75
76
77
S1_ALARM
BI_1
1282
01,02,03
0, 1
R
Sys 1 Alarm
SSSSSSSSSS
78
S2_ALARM
BI_2
1283
01,02,03
0, 1
R
Sys 2 Alarm
SSSSSSSSSS
79
EVAP_HTR
BI_3
1284
01,02,03
0, 1
R
Evaporator Heater Status
SSSSSSSSSS
80
EVAP_PUMP
BI_4
1285
01,02,03
0, 1
R
Evaporator Pump Status
SSSSSSSSSS
81
S1_C1_RUN
BI_5
1286
01,02,03
0, 1
R
Sys 1 Comp 1 Run
SSSSSSSSSS
82
S2_C1_RUN
BI_6
1287
01,02,03
0, 1
R
Sys 2 Comp 1 Run
SSSSSSSSSS
83
S1_LLSV
BI_7
1288
01,02,03
0, 1
R
Sys 1 Liquid Line Solenoid Valve
SSSSSSSSSS
84
S1_MODE_SV
BI_8
1289
01,02,03
0, 1
R
Sys 1 Mode Solenoid Valve (HP Only)
SSSSSSSSSS
85
S1_HGBV
BI_9
1290
01,02,03
0, 1
R
Sys 1 Hot Gas Bypass Valve
SSSSSSSSSS
86
S1_BHS
BI_10
1291
01,02,03
0, 1
R
Bivalent Heat Source (YLAE HP Only), Tray Heater (YLPA HP only)
SSSSSSSSSS
87
S1_C2_RUN
BI_11
1292
01,02,03
0, 1
R
Sys 1 Comp 2 Run
SSSSSSSSSS
88
S2_C2_RUN
BI_12
1293
01,02,03
0, 1
R
Sys 2 Comp 2 Run
SSSSSSSSSS
BINARY MONITOR ONLY POINTS
STC Scroll Native Bacnet_Modbus
Property of JCI/York International. Subject to change without notice
Small Tonnage Scroll IPU II NATIVE BACnet _Modbus Data Maps_ Rev A_09.xls
Page 2 of 3
TABLE 30 -
BACNET AND MODBUS COMMUNICATIONS DATA MAP (CONT’D)
6/1
1/2010