SECTION 10 – MAINTENANCE
FORM 150.27-NM1
ISSUE DATE: 09/30/2015
10
The table below shows the minimum, maximum, and default values.
TABLE 27 -
MINIMUM, MAXIMUM AND DEFAULT VALUES
DESCRIPTION
MINIMUM
MAXIMUM
DEFAULT
De Modifier Address
-1
41943
-1
De Modifier Offset
-1
99
-1
P1 Baud Rate
1200
76800
4800
1200, 4800, 9600, 19200, 38400, 76800, Auto Selectable
P2 Baud Rate
1200
57600
1200
1200, 4800, 9600, 19200, 38400, 57600 Selectable
P1, P2 Manual Mac Address
-1
127
-1
P1, P2 Parity
None
Ignore
None
None, Even, Odd, Ignore Selectable
P1 Protocol
BACNET
API
BACNET
BACNET, API Selectable
P2 Protocol
Terminal
Modbus Client
API
Terminal, Modbus Io, Modbus Server, API, Modbus Client Selectable
P1, P2 Stop Bits
1
2
1
Reset Real Time Error
No
Yes
No
035-02550-xxx I/O Board
FIGURE 40 -
MICRO PANEL CONNECTIONS
LD14318