![Johnson Controls York YCRL0064 Скачать руководство пользователя страница 125](http://html1.mh-extra.com/html/johnson-controls/york-ycrl0064/york-ycrl0064_installation-operation-and-maintenance_2023468125.webp)
JOHNSON CONTROLS
125
SECTION 7 – UNIT CONTROLS
FORM 150.27-NM1
ISSUE DATE: 09/30/2015
7
Option 12 – Power Fail Restart
P O W E R F A I L R E S T A R T
A
U T
O
M
A T I C
Chiller auto restarts after a power failure.
P O W E R F A I L R E S T A R T
M
A
N
U
A L
After a power failure, the UNIT switch must be toggled
before restart at the unit is allowed.
Normally MANUAL restart should not
be selected.
Option 13 – Soft Start Enable/Disable
S O F T S T A R T
D I S A B L E D
SOFT START “DISABLED” MUST be selected on all
chillers.
This message may not be viewable on non-European
chillers.
Option 14 – Unit Type
U N I T T Y P E
L I Q U I D C H I L L E R
The UNIT TYPE message cannot be modified under
the UNIT keys.
“LIQUID CH
ILLER” must be displayed,
or damage to compressors or other compo-
nents will occur if operated in the HEAT
PUMP or CONDENSING UNIT modes.
F A N C O N T R O L
A M B I E N T & D S C H P R E S S
Does not apply to a YCRL chiller.
Option 10 – Manual Override Mode
M A N U A L O V E R R I D E M O D E
D I S A
B L E
D
This option allows overriding of the Daily Schedule
that is programmed. MANUAL OVERRIDE MODE –
DISABLED indicates that override mode has no effect.
or
M A N U A L O V E R R I D E M O D E
E
N
A
B L E
D
Manual Override Mode is enabled. This is a service
function and when enabled, will allow the unit to start
when shut down on the Daily Schedule. It will auto-
matically be disabled after 30 minutes.
Option 11 – Current Feedback Options
Installed
C U R R E N T F E E D B A C K
N
O
N
E
This mode should be selected when the panel is not
equipped with current sensing capability.
or
C U R R E N T F E E D B A C K
O N E P E R U N I T
This mode should be selected when an optional 2ACE
Module is installed to allow combined current moni-
toring of all systems by sensing current on the incom-
ing line.
or
C U R R E N T F E E D B A C K
O N E P E R S Y S T E M
This mode should be selected when an optional 2ACE
module is installed to allow individual current moni-
toring of each system. SYS 1 input is to J7 of the I/O.
SYS 2 input is to J8 of the I/O.