38
JOHNSON CONTROLS
FORM 145.05-NOM1 (708)
Borders mark typical operating ranges that can be expected
for suction and discharge pressures under moderate to full
load, 44°F setpoint, with ambient air temperatures between
90-100°F. This is only a guideline and readings beyond these
ranges will occur.
Vapor entering compressor should be superheated 12-15°F.
Liquid from condenser should be subcooled 12-15°F.
This chart shows characteristics of Refrigerant R-22 (Monochlorodifluoromethane) when in the ‘saturated’ state.
Temperature (F)
Pressure (PSI
92
173.7
94
179.1
96
184.6
98
190.2
100
195.9
102
201.8
104
207.7
106
213.8
108
220.0
110
226.4
112
232.8
114
239.4
116
246.1
118
252.9
120
259.9
122
267.0
124
274.3
126
281.6
128
289.1
130
296.8
132
304.6
134
321.5
136
320.6
138
328.3
140
337.3
142
345.8
144
354.5
146
363.3
148
372.3
150
381.5
152
390.8
154
400.3
156
410.0
158
419.8
160
429.8
Temperature (F)
Pressure (psig)
0
24.0
2
25.6
4
27.3
6
29.1
8
30.9
10
32.8
12
34.7
14
36.7
16
38.7
18
40.9
20
43.0
22
45.3
24
47.6
26
50.0
28
52.4
30
54.9
32
57.5
34
60.1
36
62.8
38
65.6
40
68.5
42
71.5
44
74.5
46
77.6
48
80.8
50
84.0
52
87.4
54
90.2
56
94.3
58
97.9
60
101.6
62
105.4
64
109.3
66
113.2
68
117.3
70
121.4
72
125.7
74
130.0
76
134.5
78
139.0
80
143.6
82
148.4
84
153.2
86
158.2
88
163.2
90
168.4
SUCTION
DISCHARGE
TABLE 11 – TEMPERATURE/PRESSURE CHART – REFRIGERANT R-22
Startup
Содержание York VERSECON YSWD 012
Страница 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 58: ...58 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 112: ...112 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 125: ...125 JOHNSON CONTROLS FORM 145 05 NOM1 708 FIG 12 ELEMENTARY CONTROL WIRING DIAGRAM YSWU LD13132 CV VAV FlexSys 8 ...
Страница 126: ...126 JOHNSON CONTROLS FORM 145 05 NOM1 708 FIG 13 ELEMENTARY POWER WIRING DIAGRAM YSWU LD13133 CV VAV FlexSys Service ...
Страница 127: ...127 JOHNSON CONTROLS FORM 145 05 NOM1 708 FIG 14 ELEMENTARY CONTROL WIRING DIAGRAM YSWU DOWNFLOW FlexSys LD13142 8 ...