MENU ITEM
DEFINITION
DIRTY FILTER
This gives the status of the dirty filter switch. OFF indicates normal operation
and ON indicates a dirty filter.
DUCT HIGH STATIC
This gives the status of the duct high static switch. OFF indicates the duct static
pressure is above the setting of the switch. ON indicates normal operation.
DUCT STATIC 1 – "WC
This is the duct static pressure input from the number 1 duct static pressure
transducer.
DUCT STATIC 2 – "WC
This is the duct static pressure input from the number 2 duct static pressure
transducer.
DX B/P PRESS
This is the by-pass damper PID loop generated by comparing the differential
duct static pressure across the evaporator coil to the minimum duct static pres-
sure set point (FlexSys units only).
DX B/P S/A TMP
This is the by-pass damper PID loop generated by comparing the supply air tem-
perature to the supply air temperature set point (FlexSys units only).
ECON R/A TEMP
This is the return air economizer PID loop generated by comparing the return air
temperature to the AC/Econ-R/A SP.
ECON S/A DEW
This is the dew point economizer PID loop generated by comparing the dew
point temperature of the supply air to a derived dew point temperature set point
AC/Econ-S/A SP (FlexSys units only).
ECON S/A TEMP
This is the supply air economizer PID loop generated by comparing the supply
air temperature to the AC/Econ-S/A SP.
ECON VALVE
This item is used to force an analog output to the air side economizer damper
motor or the water side economizer control valve.
ECON VLV MIN
This item is used to program in the minimum position for the water side econo-
mizer valve.
ECON VLV MOD
This is the analog output to the economizer water valve on a water source
economizer or the economizer damper on an air side economizer.
ECON-R/A TMP EN
This item is used to enable or disable return air temperature economizer control.
ECON-S/A TMP EN
This item is used to enable or disable supply air temperature economizer control.
FAN OUTPUT
This gives the status of fan operation. The status is ON whenever the output to
CV or VAV supply fan is ON.
FAN SP BAS EN
This item turns on the ability to send a % speed input to the supply fan VFD by
a BAS system (FlexSys unit only).
FAN SPEED – %
This is the input from the supply fan VFD of the % speed it is running at.
FAN-S/A PRES SP
This item is used to set the supply air duct static set point for VAV units.
FAN-VAV/CV EN
This item is used to select either CV or VAV supply fan operation.
FAULT
The Status Screen will display this whenever an Alarm or Fault is active.
FLOOR STATIC
This is the static pressure under the floor (FlexSys units only).
FREEZE-STAT
This gives the status of the freeze-stat. ON indicates normal operation, OFF
indicates a fault.
HEAT MOD
This is the analog output to the modulating heat hydronic valve.
HEAT -R/A TMP EN
This item is used to enable and disable heating Return Air Temperature Control.
TABLE 20 – DEFINITIONS (CONT.)
7
Continued on next page
Содержание York VERSECON YSWD 012
Страница 12: ...12 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 58: ...58 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 106: ...106 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 112: ...112 JOHNSON CONTROLS FORM 145 05 NOM1 708 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 125: ...125 JOHNSON CONTROLS FORM 145 05 NOM1 708 FIG 12 ELEMENTARY CONTROL WIRING DIAGRAM YSWU LD13132 CV VAV FlexSys 8 ...
Страница 126: ...126 JOHNSON CONTROLS FORM 145 05 NOM1 708 FIG 13 ELEMENTARY POWER WIRING DIAGRAM YSWU LD13133 CV VAV FlexSys Service ...
Страница 127: ...127 JOHNSON CONTROLS FORM 145 05 NOM1 708 FIG 14 ELEMENTARY CONTROL WIRING DIAGRAM YSWU DOWNFLOW FlexSys LD13142 8 ...