OPTIONAL PARTS
3-6
TC-16002-rev.1
NOTES:
1. This product is designed for standard air conditioning only.
Do not use this product for specific purposes, such as oil drifts, etc.
2. The dust collection efficiency is against the general airborne dust (Dust Concentration: 0.15mg/m
3
).
It is not the collection efficiency for bacteria and mold. (*1)
3. The life period may differ depending on the environment. If dust accumulates on the filter, the antibacterial
efficiency may decrease.
4. Change the filter if its life period is over.
5. Select the function selection mode with the remote control switch and set the high speed mode to “High
Speed 1” before using this antibacterial long life air filter.
Refer to the “Installation and Maintenance Manual” for details of high speed mode.
6. When the high speed mode “HIGH” or “HIGH 2” is used, the noise level may increase.
7. For this antibacterial long life air filter, the airflow volume “HIGH 2” will be equal to “HIGH”.
8. The life period of the filter using the air volume “HIGH 2” is somewhat shorter than that of the filter using
“HIGH.”
Specifications
Model
Item
F-90MD-K1
Applicable Indoor Unit Model
((H,Y,C)IC2**B21S)
018 and 024
Dust Collection Efficiency
%
65 (Gravimetric Method *1)
Airflow
cfm (m
3
/min.)
688 (19.5)
Initial Pressure Loss
in WG (Pa)
0.07 (17.0)
End Pressure Loss
in WG (Pa)
0.22 (55.9)
Color (Filter/Frame)
White/Brown
Life Period
8 Years (with maintenance per 2,500 hours)
Cleaning
Not Available (change the filter if its life period is over)
Accessory
Installation Manual
Weight
lbs (kg)
2.0 (0.9)
Performance
Prevent Bacteria and Mold from Multiplying
Filter Material
Antibacterial Fiber
Synthetic Fiber Non-woven Fabric
13-7/8 (352)
32-1/16 (814)
1-9/16
(40)
1-9/16
(40)
P
air
P SEK Mark
Paper
Frame
Filter
Media
Model / Airflow Direction
2-11/16 (68)
1-15/1
6
(49)
2-3/8 (60)
16-7/16 (417)
11
-13/16 (300)
5/16 (8
)
24-13/16 (630)
Filter Holder
*1
Indoor Unit
Antibacterial
Long Life Air Filter
Filter Box (Option)
Ceiling
Decorative Panel
Long Life Filter
(Attached with
Optional Decorative Panel)
Air Inlet
Flat Grille
Installation
Height
Insert the antibacterial long life filter into the filter box; then fix with filter holder.
*1
Min. 3/8 (10)
800
400
1200
0
Pressure Loss (in WG)
0.10
0.05
0.15
0.20
Air Volume (cfm)
3.3 Antibacterial Long Life Air Filter: F-90MD-K1
Unit: inch (mm)
Dimensional Data
Installation State