2-WAY CASSETTE
TC-16002-rev.1
2-13
(*1) Motion sensor settings on the wired controller are “Sensor”, “If Absent”, “Check Interval”
and “Simultaneous Operation / Individual Operation”.
The amount of human activity is according to the following information detected by the motion sensor.
None: No Human Activity (Absent)
Small: Little Human Activity
Large: Much Human Activity
Normal Operation
Mode 1
Mode 2
Running
Stand-by
Stop
Normal Operation
Operation: OFF
“If absent” Setting
: Running
“If absent” Setting
: Stand-by
“If absent” Setting
: Stop
Mode 3
Little or no human activity is
sensed for 10 minutes.
No human activity is
sensed for 10 minutes.
When the wired controller is set to one of the
following or at Test Run Mode.
1. Motion Sensor setting: OFF
2. Motion Sensor setting: Cooling/Dry, with
operation mode in Heating or Automatic
Cooling Heating in Heating Operation.
3. Motion Sensor setting: Heating, with
operation mode in Cooling, Dry, Fan or
Automatic Cooling Heating in Heating
Operation.
Motion Sensor : ON
Motion Sensor : OFF
Operation Stop
Control by Wired Controller
When “If Absent” is set as “Stop” on the wired controller and
all the indoor units with motion sensors connected to the same wired controller
are moved to “Mode 3, then the operation is stopped from the wired controller.
Operation Stop
Operation Start
Much human activity is accumulated for five times within a 10-minute period,
or the setting is changed for the motion sensor on the wired controller.-
Much human activity is discerned for three minutes within a
10-minute period, or the setting is changed for the motion sensor
on the wired controller.
No human activity is
sensed for 10 minutes.
No human activity is
continued for selected time in “Check Interval” .
Much or little human activity is discerned for three minutes within a
10-minute period, or the setting is changed for the motion sensor
on the wired controller.
Much or little human activity is discerned
for three minutes within a 10-minute period,
or the setting is changed for the motion sensor
on the wired controller.
When the wired controller is set to one of the
following and not at Test Run Mode.
1. Motion Sensor setting: ON
2. Motion Sensor setting: Cooling/Dry, with operation
mode in Cooling, Dry, Fan or Automatic Cooling
Heating in Cooling Operation.
3. Motion Sensor setting: Heating, with operation mode
in Heating or Automatic Cooling Heating in
Cooling Operation.
■ Control for Motion Sensor (with Decorative Panel P-AP90DNA)