Johnson Controls VRF Smart Gateway Скачать руководство пользователя страница 6

Note:

VRF Smart Gateway ships with a private
myvrfsg.com SSL certificate installed to ensure
secure communication with the VRF Smart
Gateway. However, this certificate does not
indicate that it is trusted in a browser. If you
wish to install your own certificate, refer to

Adding a Private Key and Certificate to VRF
Smart Gateway

in the

VRF Smart Gateway

Network and IT Guidance Technical Bulletin
(LIT-12012341)

.

3. Read and accept the VRF Smart Gateway license

agreement.

4. The first time you log in to the VRF Smart Gateway,

the Change Password and Passphrase web page
appears. You must change the Admin password and
Wi-Fi passphrase.

Important:

After you change the Wi-Fi passphrase
or SSID, the web server restarts and
you must rejoin the VRF Smart Gateway
Wi-Fi network using the new
passphrase. On some mobile devices,
you must select and forget the original
VRF Smart Gateway Wi-Fi network
before rejoining the network with the
new passphrase.

Change the default password in the

New Admin

Password

field. Confirm the change by entering the

new password in the

Verify New Admin Password

field.

Change the Wi-Fi Passphrase in the

New Wi-Fi

Passphrase

field and click

Save

.

Once you have established Wi-Fi connection to the VRF
Smart Gateway, you can begin to configure the gateway
settings in the Settings menu as explained in the Users
Guide. When the gateway is physically connected to the
H-Link network, the VRF Smart Gateway automatically
starts to discover the VRF system and devices. View the
Device List from the VRF Smart Gateway UI to see the
discovered VRF devices.

A software update may be available for your device. Visit

VRFPro.com

or contact your nearest Johnson Controls

representative for the latest version. Refer to the

VRF

Smart Gateway User's Guide (LIT-12012385)

for

instructions on applying updates.

Reset Button Operation and
Descriptions

If you lose your password or if you want to restore the
unit to factory defaults, the VRF Smart Gateway offers
two reset functions: a

Network Reset

function that resets

Wi-Fi and Ethernet settings, and a

Reset to Factory

Defaults

function that resets all unit settings (including

user-configured VRF equipment names and descriptions).
Reset to Factory Defaults also resets your SSL certificate
to the Johnson Controls self-signed certificate that is in
the device when it comes from the factory.

For information on resetting the unit, see

Table 1

.

Important:

To use a unit that is reset to factory defaults,
you must have the default login information
supplied in the Quick Start Guide that
shipped with the unit. The Reset to Factory
Defaults function

does not

change the

version of the application. If you did a
software upgrade, the VRF Smart Gateway
remains at the upgraded version rather than
resetting to the version that it was running
when it left the factory.

The reset button is on the side of the device, and it is
embedded into the VRF Smart Gateway housing so that
it cannot be activated by accident. To reach the reset
button, use a paper clip, pin, or similar tool.

Notes:

If you are connected to the network, using the reset
button disconnects you.

If you press the reset button for more than 9 seconds,
the reset operation is cancelled.

If a fault condition already exists, the reset button is
disabled.

6

VRF Smart Gateway Installation Instructions

Содержание VRF Smart Gateway

Страница 1: ...to be up to 30 m 100 ft line of sight away Power must be supplied using the provided external power supply North American Emissions Compliance United States This equipment has been tested and found to...

Страница 2: ...unit upside down which puts the labels upside down Location Considerations Observe the following guidelines when mounting a VRF Smart Gateway Mount the VRF Smart Gateway in areas free of corrosive vap...

Страница 3: ...ace to which the unit is mounted The screw holes on the VRF Smart Gateway can accommodate M3 5 and 6 screws For information on location considerations for maximizing signal strength see the Mounting s...

Страница 4: ...h you are connecting Wiring the H Link Network To wire the H Link Network of the VRF Smart Gateway Connect the two H Link cable wires to the left terminals indicated in the following figure If the VRF...

Страница 5: ...ne disconnection or isolation may be required to completely de energize equipment Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury o...

Страница 6: ...overed VRF devices A software update may be available for your device Visit VRFPro com or contact your nearest Johnson Controls representative for the latest version Refer to the VRF Smart Gateway Use...

Страница 7: ...Fi and Ethernet Settings 1 Press and hold the reset button for 6 seconds After 2 seconds the Fault LED displays Slow Flicker behavior This changes to Fast Flicker behavior after an additional 4 second...

Страница 8: ...sion On Steady Green Ethernet Off No Wi Fi signal or no devices currently connected over Wi Fi Wi Fi strength is indicated by the number of LEDs that are lit with one lit LED indicating weak wireless...

Страница 9: ...the corrupted key or certificate to be saved The server detects the error and returns the Error Saving SSL Settings message While this correctly prevents the bad key or certificate from being used it...

Страница 10: ...d Access Pre Shared Key mode Temporal Key Integrity Protocol WPA2 EAP PEAP WPA2 EAP TLS Wireless Security One H Link port 4 pin port Network and Serial Interfaces 145 4 x 85 4 x 40 1 mm 5 72 x 3 36 x...

Страница 11: ...1 ETSI EN301 489 3 Class 2 IEC 60730 1 EN 60730 1 1 Last digit x represents non US country requirements The performance specifications are nominal and conform to acceptable industry standard For appli...

Страница 12: ...Fan Dry Cool Status MI Actual System Mode SYSTEM S 25 High Medium Low Status MI Actual Supply Fan Speed SF SPD 26 50 99 C 58 210 F Value AI Zone Temperature ZN T 27 Dirty Clean Status BI Filter Statu...

Страница 13: ...e INV HRS 11 0 655 350 Hours Value AI Compressor 2 Runtime COMP HRS 12 0 255 Hz Value AI Inverter Compressor Frequency INV FREQ 13 0 65 535 Hz Value AI Total Frequency TOTAL FREQ 14 0 100 Value AI Out...

Страница 14: ...s Enum Value Thermo off 1 Pump down 2 SW on start 3 Thermo on start 4 After defrost 5 Start control 1 6 Start control 2 7 Normal 8 Oil return 9 Defrost ready 1 10 Defrost ready 2 11 Differential press...

Страница 15: ...f synchronism 21 Na4 22 Na5 23 Normal acceleration 24 Normal deceleration 25 Constant speed 26 Overload after the acceleration 27 Overload after the deceleration 28 Overload after constant speed 29 Po...

Страница 16: ...NO 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY Building Technologies Solutio...

Отзывы: