background image

5.  Note the direction, clockwise (CW) or

counterclockwise (CCW), required to close the

damper. Grasp the damper shaft firmly with

pliers, and either manually close the damper for

90° boxes or manually open the damper for 45°

or 60° boxes.

6.  Push down and hold the Manual Override

button (see ) and turn the controller coupler

until it contacts the mechanical end-stop at

either the full-closed (90° boxes) or full-open

(45° and 60° boxes) position.

7.  If the damper for a 90° box closes CCW, rotate

the coupler to the CCW mechanical limit. If

the damper for a 90° box closes CW, rotate

the coupler to the CW mechanical limit. The

open end-stop is automatically set for 90°

boxes. For 45° and 60° boxes, hard stops must

be provided at both full-closed and full-open

damper positions. By installing the controller at

the full-open position, the controller provides

the open stop for 45° and 60° boxes. The closed

damper seal provides the full-closed stop.

Note: 

The integrated actuator has a

stroke time of 60 seconds for 90° of travel.

The stroke time is the amount of time

(in seconds) that it takes the actuator

to move from the fully closed to fully

opened position or from fully open to fully

closed position. For proper operation, the

actuator stroke time must be configured

in the CCT application based on the actual

time it takes the actuator to drive the

damper. The default setting is 60 seconds

(for 90° VAV boxes). For 45° and 60° VAV

boxes, the actuator stroke time must be

adjusted. Refer to 

Controller Tool Help

(LIT-12011147)

 for instructions on setting

the actuator stroke time in the application.

8.  All models are compact in size and can be

easily installed on VAV boxes. The models have

either a round shaft up to 13 mm in diameter

or a 10 mm square shaft. Tighten the square

coupler bolt to the shaft using an 8 mm (5/16

in.) wrench or 10 mm (3/8 in.) 12-point socket.

Tighten to 10.5 to 11.5 N·m (95 to 105 lb·in).

9.  (

Skip this step if you are installing the

VMA1626 model

) Loop the pneumatic tubing

(supplied by field personnel) to include a

trap for condensation. Attach the needed

length of tubing (supplied and installed by

field personnel) to the dual port fitting on the

controller and the other ends of the tubing

to the pressure transducer in the VAV box

application.

Note: 

 The controller uses a digital non-

flow pressure sensor with bidirectional

flow operation. You can connect the high-

and low-pressure DP tubes to either

barbed fitting on the controller. You do not

need to make a specific high- or low-side

connection when you attach the tubing to

the barbed fittings on the controller.

10.  Push the Manual Override button, and turn the

actuator coupling manually to ensure that the

actuator can rotate from full-closed to full-open

positions without binding.

11.  Complete the mounting by rotating the damper

to the full-open position.

 CAUTION

Risk of Property Damage

Rotate the damper to the full-open position before

starting the air handler. Failure to rotate the damper to

the full-open position may result in damage to the VAV

box or ductwork when the air handler is started.

 ATTENTION

Risque de dégâts matériels

Faire pivoter le registre pour le placer en position

d'ouverture complète avant de démarrer l'unité de

traitement d'air. Le non-respect de cette directive

risque d'endommager le caisson de l'unité à volume

d'air variable (VAV) ou le réseau de conduites au dé-

marrage de l'unité de traitement d'air.

VMA1617 and VMA1632 VAV Controllers Installation Guide

5

Содержание VMA1617

Страница 1: ...ning support and include tips for efficient and safe replacement Refer to the N2 Compatibility Options chapter of the Controller Tool Help LIT 12011147 for information about mapping N2 Objects in cont...

Страница 2: ...25 mm 1 in screw Materials and special tools needed Several 6 mm 1 4 in female spade terminals for input and output wiring and crimping tool for spade mounted terminal blocks Small straight blade scr...

Страница 3: ...pler Bolt see Mounting for information on setting the coupler bolt 9 Universal Input Voltage Analog Input 0 10 VDC Resistive Analog Inputs 0 600k ohm 0 2k Potentiometer RTD 1k Nickel 1k Platinum or A9...

Страница 4: ...ng the sheet metal screw from the original installation preferred option On panel or enclosure mount applications observe these additional guidelines Do not install the controller in an airtight enclo...

Страница 5: ...y installed on VAV boxes The models have either a round shaft up to 13 mm in diameter or a 10 mm square shaft Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in...

Страница 6: ...For detailed information on configuring and wiring a SA Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 VMA terminals and bus ports See for input and output terminal and bus...

Страница 7: ...Wiring Important Exercise caution while rewiring the power plug when replacing a VMA1610 or VMA1620 controller with a VMA1617 or VMA1632 controller The supply power terminal on a new VMA is a two posi...

Страница 8: ...to the appropriate device address Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1617 or VMA1632 controller with the Wireless...

Страница 9: ...tive Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1 seco...

Страница 10: ...e Size Gauge and Type Maximum Cable Length and Type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 297 m 975 ft twisted w...

Страница 11: ...sted wire B 24 AWG stranded copper 107 m 350 ft twisted wire 61 m 200 ft twisted wire 100 mV maximum voltage drop Depending on the cable length and the connected input or output device you may have to...

Страница 12: ...er VAV Balancing Tool One to One Wireless Receiver Network Sensor 24 AWG 4 pair CAT 5 Cable 30 5 m 100 ft HOT 24 VAC Power Supply Hot Supplies 20 30 VAC Nominal 24 VAC 24 COM 24 VAC Power Supply Commo...

Страница 13: ...gures in this section for the applicable termination diagrams Table 6 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input...

Страница 14: ...External Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output...

Страница 15: ...damaging the controller Setting the device address Metasys field controllers are master devices on BACnet MSTP SA or FC Buses Before operating field controllers on a bus you must set a valid and uniqu...

Страница 16: ...ZFR182x Pro Series Wireless Field Bus System Technical Bulletin LIT 12012356 or the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 for more information on device addresses in...

Страница 17: ...F 5 Reconnect the 24 VAC supply to the controller 6 Using an SA bus connection download the firmware and controller application file The download process asks to confirm switching the communication pr...

Страница 18: ...efer to the Controller Tool Help LIT 12011147 and Controller Provisioning with Tools LIT 12013247 for detailed information about commissioning field controllers Note The MAP Gateway serves as a replac...

Страница 19: ...must be no short circuit Note Some installations require the Secondary of the Transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not shared betw...

Страница 20: ...Gateway Refer to the Mobile Access Portal Gateway Catalog Page LIT 1900869 to identify the appropriate product for your region MS DIS1710 0 Local Controller Display MS BTCVTCBL 700 Cable Replacement S...

Страница 21: ...F 1000 326 Flexible Tubing Extension with Barbed Fitting for VMA1617 and VMA1632 35 56 cm 14 in Length Bulk Pack of 20 MS VMAACT 701 VMA Actuator Assembly Gearbox Replacement Kit TE730 29C 0 Sensor wi...

Страница 22: ...or N2 DIP switch set valid field controller device addresses 1 254 Communications Bus RS 485 selectable between BACnet MSTP or N2 FC Bus 0 6 mm 22 AWG standard 3 wire twisted shielded cable recommende...

Страница 23: ...Testing Laboratories BTL Protocol Revision 7 Listed BACnet Application Specific Controller B ASC The performance specifications are nominal and conform to acceptable industry standard For application...

Страница 24: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Отзывы: