LED status and states

Table 10: Status LEDs and description of LED states

LED label

LED color

Normal state

Descriptions of LED states

POWER

Green

On Steady

Off Steady = No power
On Steady = Power is supplied by primary voltage

FAULT

Red

Off Steady

Blink - 2 Hz = Download or startup in progress, not

ready for normal operation, SA Bus devices offline

(such as netsensors)
Rapid blink = SA Bus communications issue
Off Steady = No faults
On Steady = Device fault or no application loaded

FC BUS

Green

Blink - 2 Hz

Blink - 2 Hz = Data transmission (normal

communication)
Off Steady = No data transmission (auto baud in

progress)
On Steady = communication lost, waiting to join

communication ring

SA BUS

Green

Blink - 2 Hz

Blink - 2 Hz = Data transmission (normal

communication)
Off Steady = No data transmission (N/A - auto baud

not supported)
On Steady = Communication lost; waiting to join

communication ring

EOL

Amber

Off

On Steady = EOL is active
Off Steady = EOL is not active

Accessories

Table 11: VMA1617 and VMA1632 Controller Accessories (Order Separately)

Product code number

Description

IOM Series Controllers

Refer to the 

 Metasys

®

 System Field Equipment Controllers and Related Products Product Bulletin

(LIT-12011042)

 for a complete list of available IOM Series Controllers.

Mobile Access Portal (MAP) Gateway

Refer to the 

Mobile Access Portal Gateway Catalog Page

 (LIT-1900869) to identify the

appropriate product for your region.

MS-DIS1710-0

Local Controller Display

MS-BTCVTCBL-700

Cable Replacement Set for the MS-BTCVT-1 or the NS-ATV7003-0; includes One 1.5 m (5 ft)

Retractable Cable

Y64T15-0

Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 92 VA, Foot Mount, 72.2 cm (30

in.), Primary Leads and 76.2 cm (30 in.) Secondary Leads, Class 2

Y65A13-0

Transformer, 120 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount (Y65AS), 20.32 cm (8

in.), Primary Leads and 76.2 cm (30 in.) Secondary Leads, Class 2

Y65T42-0

Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Hub Mount (Y65SP+),

20.32 cm (8 in.), Primary Leads and Secondary Screw Terminals, Class 2

Y65T31-0

Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount (Y65AR+),

20.32 cm (8 in.), Primary Leads and Secondary Screw Terminals, Class 2

AP-TBK1002-0

2-position Screw Terminal that plugs onto VMA Output Point Spade Lugs

AP-TBK1003-0

3-position Screw Terminal that plugs onto VMA Output Point Spade Lugs

AP-TBK4SA-0

Replacement MS/TP SA Bus Terminal, 4-Position Connector, Brown, Bulk Pack of 10

AP-TBK4FC-0

Replacement MS/TP FC Bus Terminal, 4-Position Connector, Blue, Bulk Pack of 10

AP-TBK2PW-0

Replacement Power Terminal, 2-Position Connector, Gray, Bulk Pack of 10

AS-CBLTSTAT-0

Cable adapter for connection to 8-pin TE-6700 Series sensors

VMA1617 and VMA1632 VAV Controllers Installation Guide

20

Содержание VMA1617

Страница 1: ...ning support and include tips for efficient and safe replacement Refer to the N2 Compatibility Options chapter of the Controller Tool Help LIT 12011147 for information about mapping N2 Objects in cont...

Страница 2: ...25 mm 1 in screw Materials and special tools needed Several 6 mm 1 4 in female spade terminals for input and output wiring and crimping tool for spade mounted terminal blocks Small straight blade scr...

Страница 3: ...pler Bolt see Mounting for information on setting the coupler bolt 9 Universal Input Voltage Analog Input 0 10 VDC Resistive Analog Inputs 0 600k ohm 0 2k Potentiometer RTD 1k Nickel 1k Platinum or A9...

Страница 4: ...ng the sheet metal screw from the original installation preferred option On panel or enclosure mount applications observe these additional guidelines Do not install the controller in an airtight enclo...

Страница 5: ...y installed on VAV boxes The models have either a round shaft up to 13 mm in diameter or a 10 mm square shaft Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in...

Страница 6: ...For detailed information on configuring and wiring a SA Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 VMA terminals and bus ports See for input and output terminal and bus...

Страница 7: ...Wiring Important Exercise caution while rewiring the power plug when replacing a VMA1610 or VMA1620 controller with a VMA1617 or VMA1632 controller The supply power terminal on a new VMA is a two posi...

Страница 8: ...to the appropriate device address Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1617 or VMA1632 controller with the Wireless...

Страница 9: ...tive Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1 seco...

Страница 10: ...e Size Gauge and Type Maximum Cable Length and Type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 297 m 975 ft twisted w...

Страница 11: ...sted wire B 24 AWG stranded copper 107 m 350 ft twisted wire 61 m 200 ft twisted wire 100 mV maximum voltage drop Depending on the cable length and the connected input or output device you may have to...

Страница 12: ...er VAV Balancing Tool One to One Wireless Receiver Network Sensor 24 AWG 4 pair CAT 5 Cable 30 5 m 100 ft HOT 24 VAC Power Supply Hot Supplies 20 30 VAC Nominal 24 VAC 24 COM 24 VAC Power Supply Commo...

Страница 13: ...gures in this section for the applicable termination diagrams Table 6 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input...

Страница 14: ...External Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output...

Страница 15: ...damaging the controller Setting the device address Metasys field controllers are master devices on BACnet MSTP SA or FC Buses Before operating field controllers on a bus you must set a valid and uniqu...

Страница 16: ...ZFR182x Pro Series Wireless Field Bus System Technical Bulletin LIT 12012356 or the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 for more information on device addresses in...

Страница 17: ...F 5 Reconnect the 24 VAC supply to the controller 6 Using an SA bus connection download the firmware and controller application file The download process asks to confirm switching the communication pr...

Страница 18: ...efer to the Controller Tool Help LIT 12011147 and Controller Provisioning with Tools LIT 12013247 for detailed information about commissioning field controllers Note The MAP Gateway serves as a replac...

Страница 19: ...must be no short circuit Note Some installations require the Secondary of the Transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not shared betw...

Страница 20: ...Gateway Refer to the Mobile Access Portal Gateway Catalog Page LIT 1900869 to identify the appropriate product for your region MS DIS1710 0 Local Controller Display MS BTCVTCBL 700 Cable Replacement S...

Страница 21: ...F 1000 326 Flexible Tubing Extension with Barbed Fitting for VMA1617 and VMA1632 35 56 cm 14 in Length Bulk Pack of 20 MS VMAACT 701 VMA Actuator Assembly Gearbox Replacement Kit TE730 29C 0 Sensor wi...

Страница 22: ...or N2 DIP switch set valid field controller device addresses 1 254 Communications Bus RS 485 selectable between BACnet MSTP or N2 FC Bus 0 6 mm 22 AWG standard 3 wire twisted shielded cable recommende...

Страница 23: ...Testing Laboratories BTL Protocol Revision 7 Listed BACnet Application Specific Controller B ASC The performance specifications are nominal and conform to acceptable industry standard For application...

Страница 24: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Отзывы: