5.  Note the direction, clockwise (CW) or

counterclockwise (CCW), required to close the

damper. Grasp the damper shaft firmly with

pliers, and either manually close the damper for

90° boxes or manually open the damper for 45°

or 60° boxes.

6.  Push down and hold the Manual Override

button (see 

Physical features

) and turn

the controller coupler until it contacts the

mechanical end-stop at either the full-closed

(90° boxes) or full-open (45° and 60° boxes)

position.

7.  If the damper for a 90° box closes CCW, rotate

the coupler to the CCW mechanical limit. If

the damper for a 90° box closes CW, rotate

the coupler to the CW mechanical limit. The

open end-stop is automatically set for 90°

boxes. For 45° and 60° boxes, hard stops must

be provided at both full-closed and full-open

damper positions. By installing the controller at

the full-open position, the controller provides

the open stop for 45° and 60° boxes. The closed

damper seal provides the full-closed stop.

Note: 

The integrated actuator has a

stroke time of 60 seconds for 90° of travel.

The stroke time is the amount of time

(in seconds) that it takes the actuator

to move from the fully closed to fully

opened position or from fully open to fully

closed position. For proper operation, the

actuator stroke time must be configured

in the CCT application based on the actual

time it takes the actuator to drive the

damper. The default setting is 60 seconds

(for 90° VAV boxes). For 45° and 60° VAV

boxes, the actuator stroke time must be

adjusted. Refer to 

Controller Tool Help

(LIT-12011147)

 for instructions on setting

the actuator stroke time in the application.

8.  All models are compact in size and can be

easily installed on VAV boxes. The models have

either a round shaft up to 13 mm in diameter

or a 10 mm square shaft. Tighten the square

coupler bolt to the shaft using an 8 mm (5/16

in.) wrench or 10 mm (3/8 in.) 12-point socket.

Tighten to 10.5 to 11.5 N·m (95 to 105 lb·in).

9.  (

Skip this step if you are installing the

VMA1626 model

) Loop the pneumatic tubing

(supplied by field personnel) to include a

trap for condensation. Attach the needed

length of tubing (supplied and installed by

field personnel) to the dual port fitting on the

controller and the other ends of the tubing

to the pressure transducer in the VAV box

application.

Note: 

 The controller uses a digital non-

flow pressure sensor (all models except

the VMA1626) with bidirectional flow

operation. You can connect the high-

and low-pressure DP tubes to either

barbed fitting on the controller. You do not

need to make a specific high- or low-side

connection when you attach the tubing to

the barbed fittings on the controller.

10.  Push the Manual Override button, and turn the

actuator coupling manually to ensure that the

actuator can rotate from full-closed to full-open

positions without binding.

11.  Complete the mounting by rotating the damper

to the full-open position.

 CAUTION

Risk of Property Damage

Rotate the damper to the full-open position before

starting the air handler. Failure to rotate the damper to

the full-open position may result in damage to the VAV

box or ductwork when the air handler is started.

 ATTENTION

Risque de dégâts matériels

Faire pivoter le registre pour le placer en position

d'ouverture complète avant de démarrer l'unité de

traitement d'air. Le non-respect de cette directive

risque d'endommager le caisson de l'unité à volume

d'air variable (VAV) ou le réseau de conduites au dé-

marrage de l'unité de traitement d'air.

VMA1615/1626/1628/1630 VAV Controllers Installation Guide

5

Содержание VMA1615

Страница 1: ...controllers The N2 capable FEC Family Controllers can be used as functional replacements for legacy N2 controllers The N2 capable FEC Family Controllers have the input and output I O quantities and c...

Страница 2: ...rminals for input and output wiring and crimping tool for spade mounted terminal blocks Small straight blade screwdriver for securing wires in the terminal blocks 8 mm 5 16 in wrench or 10 mm 3 8 in 1...

Страница 3: ...g for information on using the controller coupler 8 Coupler Bolt see Mounting for information on setting the coupler bolt Table 1 VMA1615 1626 1628 1630 Feature Callout Numbers and Descriptions Physic...

Страница 4: ...closure mount applications observe these additional guidelines Do not install the controller in an airtight enclosure Mount the controller so that the enclosure walls do not obstruct cover removal or...

Страница 5: ...led on VAV boxes The models have either a round shaft up to 13 mm in diameter or a 10 mm square shaft Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point...

Страница 6: ...Communications Bus Technical Bulletin LIT 12011034 VMA terminals and bus ports See for input and output terminal and bus port locations on the controllers Observe the following guidelines when wiring...

Страница 7: ...e Table for more information Figure 6 24 VAC supply power terminal block wiring Important Exercise caution while rewiring the power plug when replacing a VMA1610 or VMA1620 controller with a VMA1615 o...

Страница 8: ...ice address See Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1615 1626 1628 1630 controller with the Wireless Field Bus Syste...

Страница 9: ...ive Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1 secon...

Страница 10: ...pper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted wire 183 m 600 ft twisted wire A 0...

Страница 11: ...ngs Requirements Recommended cable type 1 1 FC Bus Communications COM Signal Reference Common for bus communications FC BUS 2 2 SHLD Isolated terminal optional shield drain connection 0 6 mm 22 AWG st...

Страница 12: ...er commons The 1 models only isolate this terminal from the FC bus common 0 8 mm to 1 0 mm 20 to 18 AWG 2 wire 1 See Table 3 to determine wire size and cable lengths for cables other than the recommen...

Страница 13: ...ures in this section for the applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input I...

Страница 14: ...ternal Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output V...

Страница 15: ...maging the controller Setting the device address Metasys field controllers are master devices on BACnet MSTP SA or FC Buses Before operating field controllers on a bus you must set a valid and unique...

Страница 16: ...R182x Pro Series Wireless Field Bus System Technical Bulletin LIT 12012356 or the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 for more information on device addresses in w...

Страница 17: ...connect the 24 VAC supply to the controller 6 Using an SA bus connection download the firmware and controller application file The download process asks to confirm switching the communication protocol...

Страница 18: ...C power supply causing protective devices such as breakers or fuses to trip make sure that the power connections on the VMA are not reversed The most common cause of this problem is when the 24 VAC po...

Страница 19: ...t connected Correction Connect OCOM terminal of the configurable output to the common of the connected end device Verification 1 Measure the output and verify that it matches the command 2 Disconnect...

Страница 20: ...imary to 24 VAC Secondary 40 VA Foot Mount Y65AS 20 32 cm 8 in Primary Leads and 76 2 cm 30 in Secondary Leads Class 2 Y65T42 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 40 VA Hub Mount...

Страница 21: ...3 and 128 255 are reserved and not valid field controller addresses Controller Addressing for N2 DIP switch set valid field controller device addresses 1 254 Communications Bus RS 485 selectable betw...

Страница 22: ...ing Laboratories BTL Protocol Revision 12 Listed BACnet Advanced Application Controller B AAC The performance specifications are nominal and conform to acceptable industry standard For application at...

Отзывы: