Table 7: Wireless field bus device address

Device address Address description

4 to 127

(Switch 128 ON)

Valid for MSTP Master field controllers on

wireless FC Buses only

.

Note: 

Do 

not

 connect a 

Metasys

 controller

with these device addresses to an active

wired

 SA or FC Bus. When a controller

with one of these device address is

connected to a wired field bus, the field

bus is rendered inoperable until the

controller is disconnected or Switch 128 is

set to OFF.

Setting the N2 Controller address to
be greater than 127

N2-configured controllers support the full range

of possible N2 device addresses provided by the

N2 protocol standard (1–254). However, these

controllers require special configuration for

addresses above 127.

Use the following instructions for controllers greater

than 127.

Note: 

This special configuration is required

because controller addresses above 127 were

originally intended for use with the Wireless

Field Bus system.

Note: 

Prior to performing this procedure,

be sure the controller has been converted

from BACnet to N2 protocol first. Refer to the

Modernization Guide for Legacy N2 Controllers

(LIT-12012005)

 for more information.

1. Disconnect the 24 VAC supply from the

controller.

2. Remove the FC Bus connector from the

controller.

3. Set the address switch set to the desired N2

address.

4. Set the address switch segment labeled 128 to

OFF.

5. Reconnect the 24 VAC supply to the controller.

6. Using an SA bus connection, download the

firmware and controller application file. The

download process asks to confirm switching the

communication protocol to N2.

7. Click 

OK

.

8. After the download is finished, disconnect the

24 VAC supply to the controller.

9. Set the address switch segment labeled 128 to

ON.

10. Reattach the FC Bus connector to the controller.

11. Reconnect the 24 VAC supply to the controller.

Setting the EOL switch

Each field controller has an EOL switch, which,

when set to ON (up), sets the field controller as

a terminating device on the bus. See Figure 1 for

the EOL switch location on the field controller. The

default EOL switch position is OFF (down). The

amber EOL LED illuminates to show the EOL is

active.

Figure 10: EOL switch positions

To set the EOL switch on a field controller:

1.  Determine the physical location of the

controller on the SA or FC Bus.

2.  Determine if the controller must be set as a

terminating device on the bus.

Note: 

The EOL termination rules for

SA Buses and FC Buses are different.

Refer to the 

MSTP Communications Bus

Technical Bulletin (LIT-12011034) 

for detailed

information regarding EOL termination

rules and EOL switch settings on SA and FC

Buses.

3.  If the controller is a terminating device on

the FC Bus, set the EOL switch to ON. If the

controller is not a terminating device on the

bus, set the EOL switch to OFF.

Note: 

When the EOL switch is set to ON,

the LED light on the face of the controller

is illuminated.

VMA1615/1626/1628/1630 VAV Controllers Installation Guide

17

Содержание VMA1615

Страница 1: ...controllers The N2 capable FEC Family Controllers can be used as functional replacements for legacy N2 controllers The N2 capable FEC Family Controllers have the input and output I O quantities and c...

Страница 2: ...rminals for input and output wiring and crimping tool for spade mounted terminal blocks Small straight blade screwdriver for securing wires in the terminal blocks 8 mm 5 16 in wrench or 10 mm 3 8 in 1...

Страница 3: ...g for information on using the controller coupler 8 Coupler Bolt see Mounting for information on setting the coupler bolt Table 1 VMA1615 1626 1628 1630 Feature Callout Numbers and Descriptions Physic...

Страница 4: ...closure mount applications observe these additional guidelines Do not install the controller in an airtight enclosure Mount the controller so that the enclosure walls do not obstruct cover removal or...

Страница 5: ...led on VAV boxes The models have either a round shaft up to 13 mm in diameter or a 10 mm square shaft Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point...

Страница 6: ...Communications Bus Technical Bulletin LIT 12011034 VMA terminals and bus ports See for input and output terminal and bus port locations on the controllers Observe the following guidelines when wiring...

Страница 7: ...e Table for more information Figure 6 24 VAC supply power terminal block wiring Important Exercise caution while rewiring the power plug when replacing a VMA1610 or VMA1620 controller with a VMA1615 o...

Страница 8: ...ice address See Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1615 1626 1628 1630 controller with the Wireless Field Bus Syste...

Страница 9: ...ive Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1 secon...

Страница 10: ...pper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted wire 183 m 600 ft twisted wire A 0...

Страница 11: ...ngs Requirements Recommended cable type 1 1 FC Bus Communications COM Signal Reference Common for bus communications FC BUS 2 2 SHLD Isolated terminal optional shield drain connection 0 6 mm 22 AWG st...

Страница 12: ...er commons The 1 models only isolate this terminal from the FC bus common 0 8 mm to 1 0 mm 20 to 18 AWG 2 wire 1 See Table 3 to determine wire size and cable lengths for cables other than the recommen...

Страница 13: ...ures in this section for the applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input I...

Страница 14: ...ternal Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output V...

Страница 15: ...maging the controller Setting the device address Metasys field controllers are master devices on BACnet MSTP SA or FC Buses Before operating field controllers on a bus you must set a valid and unique...

Страница 16: ...R182x Pro Series Wireless Field Bus System Technical Bulletin LIT 12012356 or the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 for more information on device addresses in w...

Страница 17: ...connect the 24 VAC supply to the controller 6 Using an SA bus connection download the firmware and controller application file The download process asks to confirm switching the communication protocol...

Страница 18: ...C power supply causing protective devices such as breakers or fuses to trip make sure that the power connections on the VMA are not reversed The most common cause of this problem is when the 24 VAC po...

Страница 19: ...t connected Correction Connect OCOM terminal of the configurable output to the common of the connected end device Verification 1 Measure the output and verify that it matches the command 2 Disconnect...

Страница 20: ...imary to 24 VAC Secondary 40 VA Foot Mount Y65AS 20 32 cm 8 in Primary Leads and 76 2 cm 30 in Secondary Leads Class 2 Y65T42 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 40 VA Hub Mount...

Страница 21: ...3 and 128 255 are reserved and not valid field controller addresses Controller Addressing for N2 DIP switch set valid field controller device addresses 1 254 Communications Bus RS 485 selectable betw...

Страница 22: ...ing Laboratories BTL Protocol Revision 12 Listed BACnet Advanced Application Controller B AAC The performance specifications are nominal and conform to acceptable industry standard For application at...

Отзывы: