Note: 

That some installations require the

secondary of the Transformer to be Earth

Grounded. If this is the case, verify that

the Earth Ground connection is valid and

not shared between multiple pieces of

equipment.

Configurable output - analog mode is invalid

0–10 V output is set to 10–100%, but 0 V is at output

terminals 

and

 Output is in protection mode -a state

the analog portion of the configurable output goes

into when it detects a wiring problem. The analog

output is set to 0% regardless of the command

whenever a wiring fault is detected.

Possible Cause:

 Power polarity mismatch between

connected device and configurable output.

Correction:

 Ensure polarities of ~24 V COM/OCOM

match and that the connected end device uses the

same polarity.

Verification:

1.  Measure the output and verify that it matches

the command.

2.  Disconnect the connected device and verify the

commanded value is present.

Configurable output - analog mode is invalid

0–10V output has an undesirable offset of up to 1 V

and

 Common Reference is incorrect.

Possible Cause:

 OCOM terminal is not connected.

Correction:

 Connect OCOM terminal of the

configurable output to the common of the

connected end device.

Verification:

1.  Measure the output and verify that it matches

the command.

2.  Disconnect the connected device and verify the

commanded value is present.

LED status and states

Table 8: Status LEDs and description of LED states

LED label

LED color

Normal state

Descriptions of LED states

POWER

Green

On Steady

Off Steady = No power
On Steady = Power is supplied by primary voltage

FAULT

Red

Off Steady

Blink - 2 Hz = Download or startup in progress, not

ready for normal operation, SA Bus devices offline

(such as netsensors)
Rapid blink = SA Bus communications issue
Off Steady = No faults
On Steady = Device fault or no application loaded

FC BUS

Green

Blink - 2 Hz

Blink - 2 Hz = Data transmission (normal

communication)
Off Steady = No data transmission (auto baud in

progress)
On Steady = communication lost, waiting to join

communication ring

SA BUS

Green

Blink - 2 Hz

Blink - 2 Hz = Data transmission (normal

communication)
Off Steady = No data transmission (N/A - auto baud

not supported)
On Steady = Communication lost; waiting to join

communication ring

EOL

Amber

Off

On Steady = EOL is active
Off Steady = EOL is not active

VMA1615/1626/1628/1630 VAV Controllers Installation Guide

19

Содержание VMA1615

Страница 1: ...controllers The N2 capable FEC Family Controllers can be used as functional replacements for legacy N2 controllers The N2 capable FEC Family Controllers have the input and output I O quantities and c...

Страница 2: ...rminals for input and output wiring and crimping tool for spade mounted terminal blocks Small straight blade screwdriver for securing wires in the terminal blocks 8 mm 5 16 in wrench or 10 mm 3 8 in 1...

Страница 3: ...g for information on using the controller coupler 8 Coupler Bolt see Mounting for information on setting the coupler bolt Table 1 VMA1615 1626 1628 1630 Feature Callout Numbers and Descriptions Physic...

Страница 4: ...closure mount applications observe these additional guidelines Do not install the controller in an airtight enclosure Mount the controller so that the enclosure walls do not obstruct cover removal or...

Страница 5: ...led on VAV boxes The models have either a round shaft up to 13 mm in diameter or a 10 mm square shaft Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point...

Страница 6: ...Communications Bus Technical Bulletin LIT 12011034 VMA terminals and bus ports See for input and output terminal and bus port locations on the controllers Observe the following guidelines when wiring...

Страница 7: ...e Table for more information Figure 6 24 VAC supply power terminal block wiring Important Exercise caution while rewiring the power plug when replacing a VMA1610 or VMA1620 controller with a VMA1615 o...

Страница 8: ...ice address See Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1615 1626 1628 1630 controller with the Wireless Field Bus Syste...

Страница 9: ...ive Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1 secon...

Страница 10: ...pper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted wire 183 m 600 ft twisted wire A 0...

Страница 11: ...ngs Requirements Recommended cable type 1 1 FC Bus Communications COM Signal Reference Common for bus communications FC BUS 2 2 SHLD Isolated terminal optional shield drain connection 0 6 mm 22 AWG st...

Страница 12: ...er commons The 1 models only isolate this terminal from the FC bus common 0 8 mm to 1 0 mm 20 to 18 AWG 2 wire 1 See Table 3 to determine wire size and cable lengths for cables other than the recommen...

Страница 13: ...ures in this section for the applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input I...

Страница 14: ...ternal Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output V...

Страница 15: ...maging the controller Setting the device address Metasys field controllers are master devices on BACnet MSTP SA or FC Buses Before operating field controllers on a bus you must set a valid and unique...

Страница 16: ...R182x Pro Series Wireless Field Bus System Technical Bulletin LIT 12012356 or the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 for more information on device addresses in w...

Страница 17: ...connect the 24 VAC supply to the controller 6 Using an SA bus connection download the firmware and controller application file The download process asks to confirm switching the communication protocol...

Страница 18: ...C power supply causing protective devices such as breakers or fuses to trip make sure that the power connections on the VMA are not reversed The most common cause of this problem is when the 24 VAC po...

Страница 19: ...t connected Correction Connect OCOM terminal of the configurable output to the common of the connected end device Verification 1 Measure the output and verify that it matches the command 2 Disconnect...

Страница 20: ...imary to 24 VAC Secondary 40 VA Foot Mount Y65AS 20 32 cm 8 in Primary Leads and 76 2 cm 30 in Secondary Leads Class 2 Y65T42 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 40 VA Hub Mount...

Страница 21: ...3 and 128 255 are reserved and not valid field controller addresses Controller Addressing for N2 DIP switch set valid field controller device addresses 1 254 Communications Bus RS 485 selectable betw...

Страница 22: ...ing Laboratories BTL Protocol Revision 12 Listed BACnet Advanced Application Controller B AAC The performance specifications are nominal and conform to acceptable industry standard For application at...

Отзывы: