![Johnson Controls VB09 Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/johnson-controls/vb09/vb09_installation-operation-and-maintenance-manual_2024200029.webp)
29
SECTION 1 - INSTALLATION
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
1
10. Continue to bleed the system until the water leav-
ing the drain is clear, no less than 2 hours.
11. Completely drain the piping system.
Cleaning the System
1.
After the initial flushing, chemically clean the
system. Repeat the method in
Flushing the System
on page 28
to refill the system and circulate the
cleaning solution.
It is recommended to use the services of a pro-
fessional water treatment company for the type of
solution to be used and the duration of the clean-
ing application.
2. Once the cleaning process is complete, shut off
the circulating pump and completely drain the
system.
3.
Refill the system with clean water to prepare for
refrigeration chassis connection and system start-
up.
It is recommended that a professional wa-
ter treatment company perform ongoing
maintenance of the water loop including
chemical analysis and flushing, if neces
-
sary. The water loop testing should be per-
formed at intervals recommended by the
professional water treatment consultant.
It is recommended that the water loop
testing be performed at least once a year.
Standard practice is once a month or
quarterly.
The customer is responsible for complet-
ing adequate water loop maintenance
over the lifespan of the units. Otherwise,
damage to the units may occur.
Stub-outs
to chassis
Hose or piping
connecting
supply & return
runouts
Supply
Riser
Return
Riser
Hose or piping
connecting supply
and return runouts
Stub-outs to
chassis
Supply
Riser
Return
Riser
LD19685
FIGURE 20 -
SYSTEM FLUSHING AND CLEANING
Содержание VB09
Страница 44: ...44 FORM 145 18 IOM1 ISSUE DATE 8 30 2018 Section 3 Maintenance THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 45: ...45 FORM 145 18 IOM1 ISSUE DATE 8 30 2018 APPENDIX LD23571 Figure 29 PSC MOTOR WIRING DIAGRAM...
Страница 46: ...46 FORM 145 18 IOM1 ISSUE DATE 8 30 2018 Appendix LD23572 Figure 30 ECM WIRING DIAGRAM...
Страница 47: ...47 Appendix FORM 145 18 IOM1 ISSUE DATE 8 30 2018 LD27633 Figure 31 CONTINUOUS FAN WITH ECM WIRING DIAGRAM...
Страница 48: ...48 FORM 145 18 IOM1 ISSUE DATE 8 30 2018 Appendix LD23574 Figure 32 MOTORIZED DAMPER ECM WIRING DIAGRAM...