Johnson Controls VB09 Скачать руководство пользователя страница 10

10

FORM 145.18-IOM1 

ISSUE DATE: 8/30/2018

SECTION 1 - INSTALLATION

Inspection and Storage

Store cabinets, chassis, and risers the same way they 

were shipped. Ensure the storage area is dry and pro-

tected from the environment. Keep the units in their 

upright position. If the risers are stored at the job site, 

ensure the pipe ends are capped to prevent foreign ob-

ject debris and contamination. 
In areas where construction is not complete (including 

dry wall, plaster, paint, and where any emission of dust 

particulates or fumes from outgassing are present), all 

precautions must be taken to protect the cabinet, open-

ings, and chassis from contamination or physical damage.
Upon delivery, perform the following inspections:

1.  Inspect the unit for shipment damage. Notify the 

Transportation Company of any damage and note 

the damage on the shipping receipt.

Rough handling may dislocate and dam-

age internal components.

2.  Inspect the riser projections at each end of the 

cabinet for misalignment or end damage that 

would prevent making an acceptable connection.

3.  Inspect the thermostats and other accessories that 

have been shipped separately for quantity and 

transit damage.

Store the refrigeration chassis in the normal upright 

orientation to maintain oil in the compressor sump.

Preparations for Installing the Unit

Before installing the unit, perform the following prep-

arations:

•  Verify the model number on the unit nameplate 

with the ordering and shipping information to en-

sure the correct unit has been shipped. 

•  Carefully inspect each unit before delivery to the 

installation site. All cabinets may not be equipped 

with the same size riser or the same air supply 

grille arrangement. In most cases, each cabinet is 

individually tagged for a specific location in the 

building. 

•  Keep the cabinet sealed with the shipping materi-

als until all plastering, painting, and construction 

work is complete. 

•  Remove the inner service panel and manually 

check the blower wheel for free rotation.

•  Match the refrigeration chassis to the proper cabi-

nets by referring to the cabinet and chassis name-

plate and label information.

•  Remove the chassis refrigeration access panel 

(top cover) and inspect the unit. Ensure that the 

refrigerant tubing is free from obvious physical 

damage and kinks, and check that piping does not 

touch other unit components. 

•  Ensure the compressor is mounted on neoprene 

isolators with metal spacing sleeves inside. Se-

cured it with nuts that are snug against the metal 

spacer sleeves.

•  Inspect all electrical connections. Connections 

must be clean and tight at the terminals. 

Do NOT use the risers to lift the cabinet 

assembly.

Do NOT install this unit outdoors.

A compressor/unit comprises a pressur-

ized system. Never loosen threaded joints 

while the system is under pressure, and 

never open pressurized system parts.

Before servicing, open and tag all discon-

nect switches.

Do NOT install units in a flammable 

environment due to the danger of an 

explosion.

Содержание VB09

Страница 1: ...8 HIGH EFFICIENCY VSCS SERIES VERTICAL STACKED WATER SOURCE HEAT PUMP CABINET MODEL VB VM VS09 36 AND CHASSIS MODEL VSCS09 36 INDOOR PACKAGED EQUIPMENT Installation Operation and Maintenance Supersede...

Страница 2: ...with all applicable industry and governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in this document to alert the reader to specifi...

Страница 3: ...If there is any question regarding the applicability of these documents rigging lifting and operating service personnel should verify whether the equipment has been modified and if current literature...

Страница 4: ...1 6 265 60 1 CABINET OPTIONS Cabinet Height No OA Options Left Top OA Entry 4 inch Round Left Top OA Entry 4 inch Round with Motorized Damper Right Top OA Entry 4 inch Round Right Top OA Entry 4 inch...

Страница 5: ...USGPM L 6 0 USGPM M 7 0 USGPM N 8 0 USGPM P 9 0 USGPM R 10 0 USGPM AIRSIDE OPTIONS A Standard Airside Coil C Corrosion Protective Coating WATERSIDE OPTIONS C Standard Water Coil B Standard Water Coil...

Страница 6: ...Installation 20 Acoustic Return Air RA Panel 20 Supply Air SA Ductwork 24 Horizontal Supply Air 24 Top Discharge Supply Air 24 Top Mounted Fresh Air Intake 27 Top Mounted Fresh Air Intake with Motori...

Страница 7: ...h Unit Cabinet Installation Dimensions 21 FIGURE 12 RA Panel Cross Section Installation at Floor Level 22 FIGURE 13 RA Panel Dimensions 22 FIGURE 14 Optional RA Panel with ADA Mounted Thermostat 23 FI...

Страница 8: ...s 19 TABLE 5 Unit Supply Opening Sizes 26 TABLE 6 Unit Supply Face Velocity FPM 26 TABLE 7 Operating Limits 36 TABLE 8 PSC Standard Blower Performance CFM 37 TABLE 9 PSC High Static Blower Performance...

Страница 9: ...ges may require that the NRTL or testing facility review and re approve the product by means of a field or site inspection and certification Modifications may invalidate product certifications or viol...

Страница 10: ...fy the model number on the unit nameplate with the ordering and shipping information to en sure the correct unit has been shipped Carefully inspect each unit before delivery to the installation site A...

Страница 11: ...ER INSTALLATION Do NOT use the risers to lift or move the cabinets Refer to Figure 3 on page 14 which shows the correct location of the cabinet in relation to the floor sleeve and risers Risers are no...

Страница 12: ...o assure proper unit operation and condensate drainage 6 Anchor the cabinets into place using rubber iso lated sheet metal angles Approved and tested sheet metal angles are available from factory It i...

Страница 13: ...146 3 14 3 14 3 14 3 14 3 14 3 14 Water Coil Type Enhanced Surface Co Axial Standard Blower Motor Double Width Double Inlet DWDI Forward Curved Centrifugal Permanent Split Capacitor PSC Direct Drive...

Страница 14: ...ening Supply Riser Opening Supply Riser Opening Back View inches inches Condensate Riser Opening 48 inches Riser Opening Knock Outs All 3 Sides 4 5 inches Return Air Flange Standard 1 inch B A 7 inche...

Страница 15: ...or 2 inch Insertion into Swage End Supply and Return Riser Max 120 inches Condensate Riser Max 120 inches As Req d Reduce Up Riser Max 120 inches Reducer Reducer Reduce Down Riser Max 120 inches Cappe...

Страница 16: ...ve connections require a special hose kit The kit comes complete with a NPT to NPSH swiv el adapter on the shut off valve and chassis connection to mate with factory hoses see Figure 7 on page 18 Tabl...

Страница 17: ...raight Hose NPSH connection LD18126 Figure 5 STANDARD FACTORY SUPPLIED NPSH HOSE KITS AND RISERS LD18127 1 2 INCH OR 3 4 INCH MALE NPSH 1 2 INCH OR 3 4 INCH NPSH THREADS 1 2 INCH OR 3 4 INCH FLEXIBLE...

Страница 18: ...h unit with its own separate electrical cir cuit means of circuit protection and electrical discon nect switch Follow current NEC ANSI NFPA 70 CSA C22 1 C E C Part 1 and state and local codes Failure...

Страница 19: ...re the thermostat is mounted di rectly above the return air RA panel select cabinet control option P for example VB12P The thermostat Molex pigtail harness shipped loose is field wired to thermostat t...

Страница 20: ...t cabinet or sleeve Maintain a sufficient gap between RA panel frame and cabinet Build a closet enclosure for the cabinet that incorpo rates the RA panel size while maintaining a sufficient gap betwee...

Страница 21: ...configuration determined by the location of the door hinge Vertical Stack Cabinet Top View Return Air Flange Standard 1 inch Optional OA Fresh Air 4 25 inches Wall Stud Drywall to Fastener Based on 0...

Страница 22: ...nches A 54 75 inches ALL DIMENSIONS ARE IN INCHES MODEL A B C D ROUGH IN WIDTH ROUGH IN HEIGHT VSCS09 12 22 75 20 50 16 25 18 50 20 75 52 75 VSCS15 24 25 75 23 50 19 25 21 50 23 75 52 75 VSCS30 36 29...

Страница 23: ...location Cut out for routing ADA thermostat harness LEFT HAND OPENING SHOWN 1 50 LD19320 NOTES 1 Powder coated in appliance white 2 Inside panel lined with 0 5 inch acoustical insulation 3 Hinged pan...

Страница 24: ...ch neoprene tape field supplied around the perimeter of the volume damper prior to inserting it into the supply opening See Figure 15 on page 24 for an example This assists in reducing noise transmis...

Страница 25: ...mper Wall Stud Factory Supplied 1 inch Duct Flange Detail A Optional Framing Studs for Supply Opening 2 25 inch Minimum Unit Supply Duct Flange to 0 5 inch Drywall Face B C Vertical Stack Cabinet Top...

Страница 26: ...rywall installation 5 Top opening size does not change When combined with any other discharge arrangement it is included in determining horizontal opening grille size 6 Openings marked Not Available r...

Страница 27: ...4 1 4 inch supply plaster flange Top Mounted Fresh Air Intake with Motorized Damper This include the same features as the top mounted fresh air intake option with the addition of a motorized damp er...

Страница 28: ...If the building has more than ten floors connect the supply and return stub outs in the last two units to divide the water flow and reduce pressure drop at the pump see Figure 20 on page 29 3 Open th...

Страница 29: ...clean water to prepare for refrigeration chassis connection and system start up It is recommended that a professional wa ter treatment company perform ongoing maintenance of the water loop including...

Страница 30: ...g Knock Outs All Three Sides Front Supply Optional Optional 24V Molex Connection for Surface Mount Remote Mounted Thermostat Unit Switch Plate B CABINET DIMENSIONS INCHES MODEL A B C 09 12 17 8 12 15...

Страница 31: ...nit Switch Plate Fresh Air Discharge Collector Box 3 inches 61 7 8 inches 7 8 inch Power Entrance 7 8 inch Control Entrance Knock Out Both Sides Riser Opening Knock Outs All Three Sides CABINET DIMENS...

Страница 32: ...ion hose kits are NPT type tapered thread Refer to Riser Loop on page 16 for more information For Units with NPSH Valve Connection and Hose Sets NPSH flexible connection hoses do not require any pipe...

Страница 33: ...assis with the opening of the cabinet Tilt the chassis sufficiently for the base of the chassis to clear the mounting rails on the cabinet drain pan see Figure 23 on page 33 4 Insert the chassis midwa...

Страница 34: ...8 Without touching the flanges on either side en sure the chassis alignment in the cabinet is cen tered in the cabinet opening see Figure 27 on page 34 9 Complete the electrical connections to the cha...

Страница 35: ...r and the drain pan stub INITIAL UNIT START UP During installation testing servicing and troubleshooting of this product it may be necessary to work with live electri cal components Failure to follow...

Страница 36: ...eating capacity High system loop temperatures may nega tively affect unit performance efficiency maintenance and reliability and noise levels Table 7 OPERATING LIMITS COOLING HEATING MINIMUM EWT 30 0...

Страница 37: ...TATIC BLOWER PERFORMANCE CFM UNIT SIZE MOTOR SPEED RATED CFM MIN CFM EXTERNAL STATIC PRESSURE IN W G 0 0 0 05 0 1 0 15 0 2 0 25 0 3 0 35 0 4 0 45 0 5 0 55 0 6 0 65 0 7 0 75 0 8 09 HIGH 340 220 375 370...

Страница 38: ...861 Table 11 ECM HIGH STATIC BLOWER PERFORMANCE CFM UNIT SIZE MOTOR SPEED RATED CFM MIN CFM EXTERNAL STATIC PRESSURE IN W G 0 0 0 05 0 1 0 15 0 2 0 25 0 3 0 35 0 4 0 45 0 5 0 55 0 6 0 65 0 7 0 75 09 H...

Страница 39: ...34 500 466 445 424 396 367 340 312 3 659 623 587 564 541 511 482 462 441 419 397 372 346 320 4 760 726 693 667 642 615 587 574 561 529 497 469 441 412 5 891 863 835 809 784 757 730 689 648 601 554 518...

Страница 40: ...nd ends the call for cooling Continuous Blower With the room thermostat fan switch set to AUTO and the system switch set to either AUTO or HEAT the blower energizes whenever a cooling or heating opera...

Страница 41: ...re than 5 seconds the microprocessor control de energizes the compressor initiates the ASCD and stops the compressor a soft lockout If the call for cooling is still present after the ASCD the micropro...

Страница 42: ...t the micropro cessor correctly functions the control boards flash for 1 second on 1 second off also known as a heart beat Do not confuse this with an error flash code To pre vent confusion a 1 flash...

Страница 43: ...ew odors 4 Annually check the fan motor and blower assem bly All units employ permanently lubricated fan motors DO NOT OIL FAN MOTORS Vacuum any accumulation of dirt from the motor ventila tion slots...

Страница 44: ...44 FORM 145 18 IOM1 ISSUE DATE 8 30 2018 Section 3 Maintenance THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 45: ...45 FORM 145 18 IOM1 ISSUE DATE 8 30 2018 APPENDIX LD23571 Figure 29 PSC MOTOR WIRING DIAGRAM...

Страница 46: ...46 FORM 145 18 IOM1 ISSUE DATE 8 30 2018 Appendix LD23572 Figure 30 ECM WIRING DIAGRAM...

Страница 47: ...47 Appendix FORM 145 18 IOM1 ISSUE DATE 8 30 2018 LD27633 Figure 31 CONTINUOUS FAN WITH ECM WIRING DIAGRAM...

Страница 48: ...48 FORM 145 18 IOM1 ISSUE DATE 8 30 2018 Appendix LD23574 Figure 32 MOTORIZED DAMPER ECM WIRING DIAGRAM...

Страница 49: ...IT HAVE AN INTERNAL PUMP YES NO ____ SUPPLY AIRFLOW MEASUREMENT CFM _________ Please attach a sketch of the duct s run with this form when returned to the Applied Ducted Systems PTS team JOB _________...

Страница 50: ...Coaxial Coil Reversing Valve Internal Pump Voltage L1 L2 Internal Pump Amp Draw L1 L2 If installed Fan Amp Draw L1 L2 May only need L1 and L2 lines L3 Fan Voltage L1 L2 L3 Fan Motor Speed F Liquid Li...

Страница 51: ...at least 700 psig high side and 180 psig low side with a 550 psig retard All hoses must have a service pressure rating of 800 psig Leak detectors must be designed to detect HFC refrigerants Systems m...

Страница 52: ...USA 17406 8469 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2018 www johnsoncontrols com ALL RIGHTS RESERVED Form 145 18 IOM1 818 Issue Date August 30 20...

Отзывы: