Setting a preloaded application

You can configure the controller to use one of the 10 preloaded applications using the MAP Gateway release 5.1 or later.

See Table 11 for the list of preloaded applications. For the application details, such as the sequence of operation and the

list of points, refer to the 

VAV1717 and VAV1732 Application Note (LIT-12013794)

.

Note:

The VAV1717 controllers ship with standard application number 1, cooling only.
The VAV1732 controllers ship with a default state feature for wiring validation, see 

Default state for wiring

validation

.

Table 11: Preloaded applications

VAV1717

VAV1732

No. Application name

Description

No. Application name

Description

1

Cooling only

Single duct, cooling only

1

Elec Reheat 3 Stg On/Off

Parallel Fan

Staged electrical heater with

three stages and single-speed

parallel fan

2

Elec Reheat 2 Stg

Staged electrical heater with

two stages

2

Incr HW Reheat On/Off

Parallel Fan

Incremental heating water

valve and single-speed

parallel fan

3

On/Off HW Reheat

On/off heating water valve

3

Elec Reheat 3 Stg On/Off

Series Fan

Staged electrical heater with

three stages and single-speed

series fan

4

Incr HW Reheat

Incremental heating water

valve

4

Incr HW Reheat On/Off Series

Fan

Incremental heating water

valve and single-speed series

fan

5

On/Off Parallel Fan

Single-speed parallel fan

5

Var Speed Series Fan

Variable-speed series fan

6

On/Off HW Reheat On/Off

Parallel Fan

On/off heating water valve

and single-speed parallel fan

6

Elec Reheat 3 Stg Var Speed

Series Fan

Staged electrical heater with

three stages and variable-

speed series fan

7

Elec Reheat 1 Stg On/Off

Parallel Fan

Staged electrical heater with

one stage and single-speed

parallel fan

7

On/Off HW Reheat Var Speed

Series Fan

On/off heating water valve

and variable-speed series fan

8

On/Off Series Fan

Single-speed series fan

8

Incr HW Reheat Var Speed

Series Fan

Incremental heating water

valve and variable-speed

series fan

9

On/Off HW Reheat On/Off

Series Fan

On/off heating water valve

and single-speed series fan

9

Elec Reheat 3 Stg

Staged electrical heater with

three stages

10

Elec Reheat 1 Stg On/Off

Series Fan

Staged electrical heater with

one stage and single-speed

series fan

10

Proportional HW Reheat

Proportional heating water

valve

Default state for wiring validation

The VAV1732 controllers ship with a default state that

can assist in validating the wiring of the input and output

terminals before the download of an application file.

When the controller is powered on in the default state, the

fault LED flashes in a pattern of two quick blinks and then

a long pause.
To use this feature, set the DIP switches to the correct

address, and wire the input and output terminals. Apply

power to the VAV1732 controller, and connect to the

controller with either a MAP Gateway or MS-DIS1710-0

Local Display to view the points in the controller. The

controller reports an operational status, even though a

blank application is loaded. In default state, the controller

displays an application name that consists of the address

of the controller, followed by the model of the controller

and the phrase 

Default State

. For example, a VAV1732

controller whose DIP switches are set to 8 has the default

state application name of 

8-VAV1732 Default State

.

In the default state, input and output points appear

for all connections on the input and output terminals.

All universal inputs (UIs) appear as Nickel temperature

sensors. All configurable outputs (COs) appear as binary

outputs (BOs) with an initial value of 0. In the default

state, the device also receives input from a network

sensor at address 199.

VAV1717 and VAV1732 VAV Controllers Installation Guide

17

Содержание VAV1717

Страница 1: ...ls provide a cost effective upgrade and modernization path for customers with existing N2 controllers For installation and commissioning support and tips for efficient and safe replacement refer to th...

Страница 2: ...Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input 0 ohm to 600k ohm qualified sensors 0 ohm to 2k ohm potentiometer RTD 1k Nickel 1k Platinum or A99B Si NTC 10k Type L 10k...

Страница 3: ...Callout Description and references 15 SA bus modular port RJ 12 6 pin modular jack see SA bus port 16 LED status indicators see LED states VAV1717 and VAV1732 VAV Controllers Installation Guide 3...

Страница 4: ...n see Mounting the controller 7 Controller coupler see Mounting the controller 8 Coupler bolt see Mounting the controller 9 Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input...

Страница 5: ...ontroller Mount the controller so that the power transformer and other devices do not radiate excessive heat to the controller To mount the controller complete the following steps 1 Set all the switch...

Страница 6: ...N Risk of Electric Shock Disconnect the power supply before making electrical connections to avoid electric shock Important Do not connect supply power to the controller before you finish wiring and b...

Страница 7: ...on the SA bus 2 Daisy chained device on the SA bus 3 Cable shield connection 4 Connection to another device on the SA bus TSTAT port The TSTAT port on the face of the controller is an RJ 45 8 position...

Страница 8: ...ontroller does not require an earth ground connection However when you need to ground the secondary of the 24 VAC transformer make only one ground connection near the transformer See the following fig...

Страница 9: ...n for all Universal IN terminals Note All Universal ICOMn terminals are isolated from all other commons Same as Universal INn OUTn Binary Output 24 VAC Triac Internal Power Sources internal 24 VAC pow...

Страница 10: ...BUS SA BUS RJ 12 6 position modular port that provides communications and 15 VDC power for the following devices NS and NSA Series network sensors MAP Gateway 4 2 or later Bluetooth Commissioning Conv...

Страница 11: ...tput point 1 0 mm 18 AWG stranded copper 229 m 750 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 137 m 450 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted...

Страница 12: ...controller Table 9 Termination diagrams Type of field device Type of input or output Termination diagrams Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered U...

Страница 13: ...External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low Externally Sourced CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Swi...

Страница 14: ...th Phone Jack Fixed Address 199 SA Bus Note The bottom jack J2 on the TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection Network Stat with Terminals Addressable SA Bus...

Страница 15: ...ock at the top of the controller see Physical features Device addresses 4 through 127 are the valid addresses for these controllers on an MS TP FC bus The DIP switch block has eight switches numbered...

Страница 16: ...ch to OFF Note When the EOL switch is set to ON the EOL LED on the front of the controller is illuminated Commissioning the controller About this task To commission the controller use the Controller C...

Страница 17: ...ries Fan On off heating water valve and variable speed series fan 8 On Off Series Fan Single speed series fan 8 Incr HW Reheat Var Speed Series Fan Incremental heating water valve and variable speed s...

Страница 18: ...LED status indicator information for troubleshooting the controllers Note If you experience short circuits in the 24 VAC power supply causing protective devices such as breakers or fuses to trip make...

Страница 19: ...nd COM Ensure that no short circuit occurs Note Some installations require the secondary of the transformer to be earth grounded If this is the case verify that the earth ground connection is valid an...

Страница 20: ...BCPro Controller Firmware Package Files required for CCT TL MAP1810 0PA Portable MAP Gateway Australia China India Japan Malaysia New Zealand Singapore South Korea Thailand TL MAP1810 0PM Portable MAP...

Страница 21: ...er TE730 Analog sensors with occupancy option TSTAT port NSA7000 Network sensors with occupancy option and RH display option NS7000 NS8000 Network sensors with occupancy option CO2 display option and...

Страница 22: ...ded between the supervisory controller and the VAV controller SA bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VAV controller to network sensors and other senso...

Страница 23: ...ns consult the local Johnson Controls office Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products Repair information If the controller fails to oper...

Страница 24: ...anty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license ope...

Отзывы: