Communication bus and supply power terminal blocks, ratings, and requirements

Table 7: Communication bus and supply power terminal blocks, functions, ratings, requirements, and cables

Terminal block or port label

Terminal labels

Function, electrical ratings and

requirements

Recommended cable type

1

1

+
-

FC bus communications

COM

Signal reference (common) for bus

communications

FC BUS

2

2

SHLD

Isolated terminal (optional shield drain

connection)

0.6 mm (22 AWG) stranded, 3-wire

twisted, shielded cable recommended

+
-

SA bus communications

COM

SA bus signal reference and 15 VDC

common

SA BUS

2

POWER

15 VDC supply power for devices on the

SA bus

0.6 mm (22 AWG) stranded, 4-wire

(2 twisted-pairs), shielded cable

recommended

Note: 

The + and - wires are one

twisted pair, and the COM and

SA PWR wires are the second

twisted pair.

TSTAT

TSTAT

RJ-45 8-position modular connector that

provides communications and +15 VDC

power

24 AWG 4-pair CAT 5 Cable <30.5 m

(100 ft)

SA BUS

SA BUS

RJ-12 6-position modular port that

provides communications and +15 VDC

power for the following devices:

NS and NSA Series network

sensors

MAP Gateway 4.2 or later

Bluetooth Commissioning
Converter (BTCVT)

3

3

VAV Balancing Tool

24 AWG 3-pair CAT 3 Cable <30.5 m

(100 ft)

HOT

24 VAC Power Supply - Hot

Supplies 20 VAC to 30 VAC (Nominal 24

VAC)

24~

COM

24 VAC Power Supply Common

The terminal is isolated from the FC bus

common.

0.8 mm to 1.0 mm
(20 to 18 AWG) 2-wire

1

To determine wire size and cable lengths for cables other than the recommended cables, see 

Cable and wire length guidelines

.

2

The SA Bus and FC Bus wiring recommendations in this table are for MS/TP Bus communications at 38.4k baud. For more

information, refer to the 

MS/TP Communications Bus Technical Bulletin (LIT-12011034)

.

3

The BTCVT is supported, but no longer available for purchase. The MAP Gateway serves as a replacement for the BTCVT.

Cable and wire length guidelines

The following table defines cable length guidelines for the various wire sizes that you can use to wire low voltage (<30 V)

inputs and outputs.

VAV1717 and VAV1732 VAV Controllers Installation Guide

10

Содержание VAV1717

Страница 1: ...ls provide a cost effective upgrade and modernization path for customers with existing N2 controllers For installation and commissioning support and tips for efficient and safe replacement refer to th...

Страница 2: ...Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input 0 ohm to 600k ohm qualified sensors 0 ohm to 2k ohm potentiometer RTD 1k Nickel 1k Platinum or A99B Si NTC 10k Type L 10k...

Страница 3: ...Callout Description and references 15 SA bus modular port RJ 12 6 pin modular jack see SA bus port 16 LED status indicators see LED states VAV1717 and VAV1732 VAV Controllers Installation Guide 3...

Страница 4: ...n see Mounting the controller 7 Controller coupler see Mounting the controller 8 Coupler bolt see Mounting the controller 9 Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input...

Страница 5: ...ontroller Mount the controller so that the power transformer and other devices do not radiate excessive heat to the controller To mount the controller complete the following steps 1 Set all the switch...

Страница 6: ...N Risk of Electric Shock Disconnect the power supply before making electrical connections to avoid electric shock Important Do not connect supply power to the controller before you finish wiring and b...

Страница 7: ...on the SA bus 2 Daisy chained device on the SA bus 3 Cable shield connection 4 Connection to another device on the SA bus TSTAT port The TSTAT port on the face of the controller is an RJ 45 8 position...

Страница 8: ...ontroller does not require an earth ground connection However when you need to ground the secondary of the 24 VAC transformer make only one ground connection near the transformer See the following fig...

Страница 9: ...n for all Universal IN terminals Note All Universal ICOMn terminals are isolated from all other commons Same as Universal INn OUTn Binary Output 24 VAC Triac Internal Power Sources internal 24 VAC pow...

Страница 10: ...BUS SA BUS RJ 12 6 position modular port that provides communications and 15 VDC power for the following devices NS and NSA Series network sensors MAP Gateway 4 2 or later Bluetooth Commissioning Conv...

Страница 11: ...tput point 1 0 mm 18 AWG stranded copper 229 m 750 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 137 m 450 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted...

Страница 12: ...controller Table 9 Termination diagrams Type of field device Type of input or output Termination diagrams Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered U...

Страница 13: ...External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low Externally Sourced CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Swi...

Страница 14: ...th Phone Jack Fixed Address 199 SA Bus Note The bottom jack J2 on the TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection Network Stat with Terminals Addressable SA Bus...

Страница 15: ...ock at the top of the controller see Physical features Device addresses 4 through 127 are the valid addresses for these controllers on an MS TP FC bus The DIP switch block has eight switches numbered...

Страница 16: ...ch to OFF Note When the EOL switch is set to ON the EOL LED on the front of the controller is illuminated Commissioning the controller About this task To commission the controller use the Controller C...

Страница 17: ...ries Fan On off heating water valve and variable speed series fan 8 On Off Series Fan Single speed series fan 8 Incr HW Reheat Var Speed Series Fan Incremental heating water valve and variable speed s...

Страница 18: ...LED status indicator information for troubleshooting the controllers Note If you experience short circuits in the 24 VAC power supply causing protective devices such as breakers or fuses to trip make...

Страница 19: ...nd COM Ensure that no short circuit occurs Note Some installations require the secondary of the transformer to be earth grounded If this is the case verify that the earth ground connection is valid an...

Страница 20: ...BCPro Controller Firmware Package Files required for CCT TL MAP1810 0PA Portable MAP Gateway Australia China India Japan Malaysia New Zealand Singapore South Korea Thailand TL MAP1810 0PM Portable MAP...

Страница 21: ...er TE730 Analog sensors with occupancy option TSTAT port NSA7000 Network sensors with occupancy option and RH display option NS7000 NS8000 Network sensors with occupancy option CO2 display option and...

Страница 22: ...ded between the supervisory controller and the VAV controller SA bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VAV controller to network sensors and other senso...

Страница 23: ...ns consult the local Johnson Controls office Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products Repair information If the controller fails to oper...

Страница 24: ...anty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license ope...

Отзывы: