I/O terminal blocks, ratings and requirements

Table 6: I/O terminal blocks, functions, ratings, requirements, and cables

Terminal block label

Terminal

label

Function, ratings, requirements

Determine wire size and

maximum cable length

+15 V

15 VDC Power Source

 for active (3-wire) input devices

connected to the Universal INn terminals.
Provides 100 mA total current.

Same as (Universal) 

IN

n.

Note: 

Use 3-wire cable for

devices that source power

from the +15 V terminal.

Analog Input - Voltage Mode (0–10 VDC)

10 VDC maximum input voltage
Internal 75k ohm Pull-down

See Guideline 

A

 in Table 8

Analog Input - Resistive Mode (0–600k ohm)

Internal 12 V. 15k ohm pull up
Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel

[Johnson Controls

®

 sensor], 1k Platinum, and A99B Silicon

Temperature Sensor), Negative Temperature Coefficient

(NTC) sensor 10k Type L (10K Johnson Controls Type II is

equivalent to Type L) or 2.252k Type 2

See Guideline 

A

 in Table 8.

IN

n

Binary Input - Dry Contact Maintained Mode

1 second minimum pulse width
Internal 12 V, 15k ohm pull up

See Guideline 

A

 in Table 8.

UNIVERSAL

(Inputs)

ICOM

n

Universal Input Common

 for all Universal IN terminals

Note: 

All Universal ICOM

n

 terminals are isolated from

all other commons.

Same as (Universal) 

IN

n

OUT

n

Binary Output - 24 VAC Triac (Internal Power)

Sources internal 24 VAC power (24~ HOT)

BINARY

(Output)

OCOM

n

Binary Output - 24 VAC Triac (Internal Power)

Connects OCOM

n

 to 24~ COM when activated.

Internal Power Source:
30 VAC maximum voltage to load
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current

See Guideline 

C

 in Table 8.

Analog Output - Voltage Mode (0–10 VDC)

10 VDC maximum output voltage
10 mA maximum output current
External 1k to 50k ohm load required.

See Guideline 

A

 in Table 8.

OUT

n

Binary Output - 24 VAC Triac

Connects OUT to OCOM when activated.
External Power Source:

30 VAC maximum voltage to load

0.5 A maximum output current

1.3 A at 25% duty cycle

40 mA minimum load current

See Guideline 

C

 in Table 8.

CONFIGURABLE

(Outputs)

OCOM

n

Analog Output Signal Common:

 All Configurable Outputs

defined as Analog Outputs share a common, which is isolated

from all other commons except the Binary Input common.

Binary Output Signal Common:

 All Configurable Outputs

defined as Binary Outputs are isolated from all other

commons, including other Configurable Output commons.

Same as (Configurable) 

OUT

n

.

VAV1717 and VAV1732 VAV Controllers Installation Guide

9

Содержание VAV1717

Страница 1: ...ls provide a cost effective upgrade and modernization path for customers with existing N2 controllers For installation and commissioning support and tips for efficient and safe replacement refer to th...

Страница 2: ...Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input 0 ohm to 600k ohm qualified sensors 0 ohm to 2k ohm potentiometer RTD 1k Nickel 1k Platinum or A99B Si NTC 10k Type L 10k...

Страница 3: ...Callout Description and references 15 SA bus modular port RJ 12 6 pin modular jack see SA bus port 16 LED status indicators see LED states VAV1717 and VAV1732 VAV Controllers Installation Guide 3...

Страница 4: ...n see Mounting the controller 7 Controller coupler see Mounting the controller 8 Coupler bolt see Mounting the controller 9 Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input...

Страница 5: ...ontroller Mount the controller so that the power transformer and other devices do not radiate excessive heat to the controller To mount the controller complete the following steps 1 Set all the switch...

Страница 6: ...N Risk of Electric Shock Disconnect the power supply before making electrical connections to avoid electric shock Important Do not connect supply power to the controller before you finish wiring and b...

Страница 7: ...on the SA bus 2 Daisy chained device on the SA bus 3 Cable shield connection 4 Connection to another device on the SA bus TSTAT port The TSTAT port on the face of the controller is an RJ 45 8 position...

Страница 8: ...ontroller does not require an earth ground connection However when you need to ground the secondary of the 24 VAC transformer make only one ground connection near the transformer See the following fig...

Страница 9: ...n for all Universal IN terminals Note All Universal ICOMn terminals are isolated from all other commons Same as Universal INn OUTn Binary Output 24 VAC Triac Internal Power Sources internal 24 VAC pow...

Страница 10: ...BUS SA BUS RJ 12 6 position modular port that provides communications and 15 VDC power for the following devices NS and NSA Series network sensors MAP Gateway 4 2 or later Bluetooth Commissioning Conv...

Страница 11: ...tput point 1 0 mm 18 AWG stranded copper 229 m 750 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 137 m 450 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted...

Страница 12: ...controller Table 9 Termination diagrams Type of field device Type of input or output Termination diagrams Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered U...

Страница 13: ...External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low Externally Sourced CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Swi...

Страница 14: ...th Phone Jack Fixed Address 199 SA Bus Note The bottom jack J2 on the TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection Network Stat with Terminals Addressable SA Bus...

Страница 15: ...ock at the top of the controller see Physical features Device addresses 4 through 127 are the valid addresses for these controllers on an MS TP FC bus The DIP switch block has eight switches numbered...

Страница 16: ...ch to OFF Note When the EOL switch is set to ON the EOL LED on the front of the controller is illuminated Commissioning the controller About this task To commission the controller use the Controller C...

Страница 17: ...ries Fan On off heating water valve and variable speed series fan 8 On Off Series Fan Single speed series fan 8 Incr HW Reheat Var Speed Series Fan Incremental heating water valve and variable speed s...

Страница 18: ...LED status indicator information for troubleshooting the controllers Note If you experience short circuits in the 24 VAC power supply causing protective devices such as breakers or fuses to trip make...

Страница 19: ...nd COM Ensure that no short circuit occurs Note Some installations require the secondary of the transformer to be earth grounded If this is the case verify that the earth ground connection is valid an...

Страница 20: ...BCPro Controller Firmware Package Files required for CCT TL MAP1810 0PA Portable MAP Gateway Australia China India Japan Malaysia New Zealand Singapore South Korea Thailand TL MAP1810 0PM Portable MAP...

Страница 21: ...er TE730 Analog sensors with occupancy option TSTAT port NSA7000 Network sensors with occupancy option and RH display option NS7000 NS8000 Network sensors with occupancy option CO2 display option and...

Страница 22: ...ded between the supervisory controller and the VAV controller SA bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VAV controller to network sensors and other senso...

Страница 23: ...ns consult the local Johnson Controls office Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products Repair information If the controller fails to oper...

Страница 24: ...anty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license ope...

Отзывы: