background image

VAV1717 and VAV1732 VAV Controllers

Installation Guide

Applications

The VAV1717 and VAV1732 controllers are designed for

Variable Air Volume (VAV) applications. These controllers

operate on an RS-485 BACnet

®

 MS/TP bus as BACnet

Application Specific Controllers (B-ASCs).
These controllers feature 10 preloaded standard

applications that operate standard VAV box equipment

with a proven energy-efficient sequence of operation,

without the need for programming. For information on

configuring a controller to use a preloaded application,

see 

Setting a preloaded application

. These controllers

are also fully programmable using the Controller

Configuration Tool (CCT), which provides the flexibility to

create custom control sequences.
These controllers feature a combination of an integral

digital differential pressure transducer (DPT), a damper

actuator, and a 32-bit microprocessor. The small package

size of the controllers facilitates quick field installation and

efficient use of space without compromising high-tech

control performance. The controllers connect easily to

sensors for zone air temperature sensing.

Communications protocols

The VAV1717 and VAV1732 controllers can communicate

using BACnet MS/TP, N2, or wireless Zigbee

®

. The default

communications protocol for all new controllers is BACnet

MS/TP. The BACnet protocol is a standard for ANSI,

ASHRAE, and the International Standards Organization

(ISO) for building controls.
You can use the VAV1717 and VAV1732 controllers as

functional replacements for the following controllers:
• VMA1617 and VMA1632

• PCV1617 and PCV1632

• Legacy N2 controllers
These N2-capable MS/TP equipment controller models

provide a cost-effective upgrade and modernization path

for customers with existing N2 controllers. For installation

and commissioning support, and tips for efficient and

safe replacement, refer to the 

Modernization Guide for

Legacy N2 Controllers (LIT-12012005)

 and the controller-

specific documentation. For information about mapping

N2 objects in controllers with switchable communications

protocols, refer to the 

N2 Compatibility Options

 chapter of

the 

Controller Tool Help (LIT-12011147)

.

To configure VAV1717 and VAV1732 controllers to

communicate using the N2 communications protocol, see

Configuring N2 communications

.

Installation overview

Observe the following guidelines when you install a

controller:
• Transport the controller in the original container to

minimize vibration and shock damage to the controller.

• Do not drop the controller or subject it to physical

shock.

Parts included

• One controller with a removable FC bus terminal block

• One installation guide

• One self-drilling No. 10 x 25 mm (1 in.) screw

Materials and special tools needed

• Several 6 mm (1/4 in.) female spade terminals for

input and output wiring, and a crimping tool for spade

mounted terminal blocks

• A small, straight-blade screwdriver for securing wires in

the terminal blocks

• An 8 mm (5/16 in.) wrench or a 10 mm (3/8 in.) 12-point

socket to tighten the square coupler bolt

• Several shims or washers to mount the controller

• A power screwdriver, a 100 mm (4 in.) extension socket,

a punch, a drill, and 3.5 mm (9/64 in.) drill bits to mount

the controller

• Pliers to open and close the damper

• The required length from the 3.97 mm (5/32 in.) ID

pneumatic tubing and barbed fittings

Physical features

The following figures and tables show the physical

features of the controller.

*241145100027-*

Part No. 24-11451-00027 Rev. —

2021-06-08

(barcode for factory use only)

JC-VAV1717-0, JC-VAV1732-0

Содержание VAV1717

Страница 1: ...ls provide a cost effective upgrade and modernization path for customers with existing N2 controllers For installation and commissioning support and tips for efficient and safe replacement refer to th...

Страница 2: ...Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input 0 ohm to 600k ohm qualified sensors 0 ohm to 2k ohm potentiometer RTD 1k Nickel 1k Platinum or A99B Si NTC 10k Type L 10k...

Страница 3: ...Callout Description and references 15 SA bus modular port RJ 12 6 pin modular jack see SA bus port 16 LED status indicators see LED states VAV1717 and VAV1732 VAV Controllers Installation Guide 3...

Страница 4: ...n see Mounting the controller 7 Controller coupler see Mounting the controller 8 Coupler bolt see Mounting the controller 9 Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input...

Страница 5: ...ontroller Mount the controller so that the power transformer and other devices do not radiate excessive heat to the controller To mount the controller complete the following steps 1 Set all the switch...

Страница 6: ...N Risk of Electric Shock Disconnect the power supply before making electrical connections to avoid electric shock Important Do not connect supply power to the controller before you finish wiring and b...

Страница 7: ...on the SA bus 2 Daisy chained device on the SA bus 3 Cable shield connection 4 Connection to another device on the SA bus TSTAT port The TSTAT port on the face of the controller is an RJ 45 8 position...

Страница 8: ...ontroller does not require an earth ground connection However when you need to ground the secondary of the 24 VAC transformer make only one ground connection near the transformer See the following fig...

Страница 9: ...n for all Universal IN terminals Note All Universal ICOMn terminals are isolated from all other commons Same as Universal INn OUTn Binary Output 24 VAC Triac Internal Power Sources internal 24 VAC pow...

Страница 10: ...BUS SA BUS RJ 12 6 position modular port that provides communications and 15 VDC power for the following devices NS and NSA Series network sensors MAP Gateway 4 2 or later Bluetooth Commissioning Conv...

Страница 11: ...tput point 1 0 mm 18 AWG stranded copper 229 m 750 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 137 m 450 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted...

Страница 12: ...controller Table 9 Termination diagrams Type of field device Type of input or output Termination diagrams Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered U...

Страница 13: ...External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low Externally Sourced CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Swi...

Страница 14: ...th Phone Jack Fixed Address 199 SA Bus Note The bottom jack J2 on the TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection Network Stat with Terminals Addressable SA Bus...

Страница 15: ...ock at the top of the controller see Physical features Device addresses 4 through 127 are the valid addresses for these controllers on an MS TP FC bus The DIP switch block has eight switches numbered...

Страница 16: ...ch to OFF Note When the EOL switch is set to ON the EOL LED on the front of the controller is illuminated Commissioning the controller About this task To commission the controller use the Controller C...

Страница 17: ...ries Fan On off heating water valve and variable speed series fan 8 On Off Series Fan Single speed series fan 8 Incr HW Reheat Var Speed Series Fan Incremental heating water valve and variable speed s...

Страница 18: ...LED status indicator information for troubleshooting the controllers Note If you experience short circuits in the 24 VAC power supply causing protective devices such as breakers or fuses to trip make...

Страница 19: ...nd COM Ensure that no short circuit occurs Note Some installations require the secondary of the transformer to be earth grounded If this is the case verify that the earth ground connection is valid an...

Страница 20: ...BCPro Controller Firmware Package Files required for CCT TL MAP1810 0PA Portable MAP Gateway Australia China India Japan Malaysia New Zealand Singapore South Korea Thailand TL MAP1810 0PM Portable MAP...

Страница 21: ...er TE730 Analog sensors with occupancy option TSTAT port NSA7000 Network sensors with occupancy option and RH display option NS7000 NS8000 Network sensors with occupancy option CO2 display option and...

Страница 22: ...ded between the supervisory controller and the VAV controller SA bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VAV controller to network sensors and other senso...

Страница 23: ...ns consult the local Johnson Controls office Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products Repair information If the controller fails to oper...

Страница 24: ...anty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license ope...

Отзывы: