Johnson Controls VAV1717 Скачать руководство пользователя страница 15

Setup and adjustments

Important: 

Electrostatic discharge can damage

controller components. Use proper electrostatic

discharge precautions during installation, setup, and

servicing to avoid damaging the controller.

Configuring N2 communications

About this task:  

N2-capable controllers support the full range of possible

N2 device addresses provided by the N2 protocol

standards: 1 to 254.
To configure a controller to communicate using the N2

protocol, complete the following steps:

1. Disconnect the 24 VAC supply from the controller.
2. Set the address switches to the N2 address that

you want to use. For details about setting a device

address, see 

Setting the device address

.

3. Reconnect the 24 VAC supply to the controller.
4. Using an SA bus connection, download the

controller application file configured for N2 to the

controller.

Switching the communications protocol

from N2 to MS/TP

About this task:  

For N2 sites that are converting to BACnet MS/TP, you can

switch the communications protocol of N2-configured

MS/TP controllers back to BACnet MS/TP.
To switch the controller operating in N2 mode back into

BACnet MS/TP mode, complete the following steps:

1. Disconnect the 24 VAC supply from the controller.
2. Set the address switches to the BACnet MS/TP

address that you want to use. For details about

setting a device address, see 

Setting the device

address

.

3. Reconnect the 24 VAC supply to the controller.
4. Using an SA bus connection, download the

controller application file configured for BACnet

MS/TP to the controller.

Setting the device address

About this task:  

The VAV1717 and VAV1732 controllers are manager

devices on BACnet

®

 MS/TP (SA or FC) buses. Before

operating controllers on a bus, you must set a valid and

unique device address for each controller on the bus.
You set the device address by setting the positions of the

switches on the device address DIP switch block at the top

of the controller, see 

Physical features

. Device addresses 4

through 127 are the valid addresses for these controllers

on an MS/TP FC bus.
The DIP switch block has eight switches numbered 128,

64, 32, 16, 8, 4, 2, and 1. Switches 64 through 1 are the

device address switches. Switch 128 is OFF for all FC bus

applications. See the following figure for an example of a

DIP switch block set to 21 for a wired FC bus application.

Figure 11: Device address switches set to 21

Note: 

Controllers ship with switch 128 ON and the

remaining address switches OFF. This renders the

controllers wired subordinate devices, which do

not interfere on MS/TP buses and do not interfere

with bus operation. Set a valid and unique device

address on the controller before applying power to

the controller on the bus.

Refer to the 

MSTP Communications Bus Technical Bulletin

(LIT-12011034)

 for more information on field controller

device addresses and how to set them on MS/TP Buses.
To set the device address on the controller, complete the

following steps:

1. Set all of the switches on the DIP switch block (128

through 1) to OFF.

2. Set one or more of the seven address switches (64

through 1) to ON, so that the sum of the switch

numbers set to ON equals the intended device

address. See Table 10 for valid controller addresses.

Set the highest number switch that is less than or

equal to the intended device address to ON. Then

continue setting lower numbered switches until the

total equals the intended address. For example, if

the intended device address is 21, set switch 16 to

ON first, then set switch 4 to ON, followed by switch

1 (16+4+1=21). See Figure 11.

Table 10: Valid device addresses

FC bus
communicati
on mode

Valid device address range

Wired MS/TP 4 to 127

Note: 

Addresses 0 to 3 are reserved

and not for use on equipment

controllers.

Zigbee
wireless

4 to 127

Note: 

Addresses 0 to 3 are reserved

and not for use on equipment

controllers.

N2

1 to 254

Note: 

Addresses 0 and 255 are

reserved and not for use on

equipment controllers.

VAV1717 and VAV1732 VAV Controllers Installation Guide

15

Содержание VAV1717

Страница 1: ...ls provide a cost effective upgrade and modernization path for customers with existing N2 controllers For installation and commissioning support and tips for efficient and safe replacement refer to th...

Страница 2: ...Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input 0 ohm to 600k ohm qualified sensors 0 ohm to 2k ohm potentiometer RTD 1k Nickel 1k Platinum or A99B Si NTC 10k Type L 10k...

Страница 3: ...Callout Description and references 15 SA bus modular port RJ 12 6 pin modular jack see SA bus port 16 LED status indicators see LED states VAV1717 and VAV1732 VAV Controllers Installation Guide 3...

Страница 4: ...n see Mounting the controller 7 Controller coupler see Mounting the controller 8 Coupler bolt see Mounting the controller 9 Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input...

Страница 5: ...ontroller Mount the controller so that the power transformer and other devices do not radiate excessive heat to the controller To mount the controller complete the following steps 1 Set all the switch...

Страница 6: ...N Risk of Electric Shock Disconnect the power supply before making electrical connections to avoid electric shock Important Do not connect supply power to the controller before you finish wiring and b...

Страница 7: ...on the SA bus 2 Daisy chained device on the SA bus 3 Cable shield connection 4 Connection to another device on the SA bus TSTAT port The TSTAT port on the face of the controller is an RJ 45 8 position...

Страница 8: ...ontroller does not require an earth ground connection However when you need to ground the secondary of the 24 VAC transformer make only one ground connection near the transformer See the following fig...

Страница 9: ...n for all Universal IN terminals Note All Universal ICOMn terminals are isolated from all other commons Same as Universal INn OUTn Binary Output 24 VAC Triac Internal Power Sources internal 24 VAC pow...

Страница 10: ...BUS SA BUS RJ 12 6 position modular port that provides communications and 15 VDC power for the following devices NS and NSA Series network sensors MAP Gateway 4 2 or later Bluetooth Commissioning Conv...

Страница 11: ...tput point 1 0 mm 18 AWG stranded copper 229 m 750 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 137 m 450 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted...

Страница 12: ...controller Table 9 Termination diagrams Type of field device Type of input or output Termination diagrams Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered U...

Страница 13: ...External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low Externally Sourced CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Swi...

Страница 14: ...th Phone Jack Fixed Address 199 SA Bus Note The bottom jack J2 on the TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection Network Stat with Terminals Addressable SA Bus...

Страница 15: ...ock at the top of the controller see Physical features Device addresses 4 through 127 are the valid addresses for these controllers on an MS TP FC bus The DIP switch block has eight switches numbered...

Страница 16: ...ch to OFF Note When the EOL switch is set to ON the EOL LED on the front of the controller is illuminated Commissioning the controller About this task To commission the controller use the Controller C...

Страница 17: ...ries Fan On off heating water valve and variable speed series fan 8 On Off Series Fan Single speed series fan 8 Incr HW Reheat Var Speed Series Fan Incremental heating water valve and variable speed s...

Страница 18: ...LED status indicator information for troubleshooting the controllers Note If you experience short circuits in the 24 VAC power supply causing protective devices such as breakers or fuses to trip make...

Страница 19: ...nd COM Ensure that no short circuit occurs Note Some installations require the secondary of the transformer to be earth grounded If this is the case verify that the earth ground connection is valid an...

Страница 20: ...BCPro Controller Firmware Package Files required for CCT TL MAP1810 0PA Portable MAP Gateway Australia China India Japan Malaysia New Zealand Singapore South Korea Thailand TL MAP1810 0PM Portable MAP...

Страница 21: ...er TE730 Analog sensors with occupancy option TSTAT port NSA7000 Network sensors with occupancy option and RH display option NS7000 NS8000 Network sensors with occupancy option CO2 display option and...

Страница 22: ...ded between the supervisory controller and the VAV controller SA bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VAV controller to network sensors and other senso...

Страница 23: ...ns consult the local Johnson Controls office Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products Repair information If the controller fails to oper...

Страница 24: ...anty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license ope...

Отзывы: