Whenever the emergency stop is activated during operation, the alarm text Compr. motor er-
ror will appear in the display. Before the compressor can be restarted, deactivate the alarm
by means of the
F4
/RESET key and release the emergency stop.
Please note: If Unisab III is set at Remote or Auto, the compressor will restart automatically.
Technical data
Power supply:
Nominal VAC
Tolerance
Hz
85-250
47-63
Consumption:
32 VA
Ambient temperature:
0-55
°
C (during operation)
Humidity:
10-90% relative humidity (not condensing)
Tightness:
IP 54
Operating manual - Unisab III
005650-en 2013.10
3/48