1.1.6 Changing set values
This example illustrates how to change set values, i.e. alarm limits, shutdown limits, set
points, timer starting value etc. First you must position the (dark) cursor on the value you
want to change. In this example it is the low shutdown limit for suction pressure. Proceed as
follows:
In the menu illustrated below, move the cursor to Control values with the and keys.
Press
to go to Suction and once again to go to (suction) Values and again to get to the
Suction/Values picture.
In the next picture, move the cursor down to Suction pressure with the key and then press
F2
/LIMITS to get to the (suction) limits picture.
Press four times to get to the Low shutdown value.
To change the low shutdown limit, press .
You must enter a password to continue. To change this low shutdown limit you must choose a
Superuser (or higher level) password.
Operating Unisab III control
20/48
Operating manual - Unisab III
005650-en 2013.10