background image

TFP485

Page 11 of 14

•  SYSTEM RELEASED

The red SYSTEM RELEASED LED 

turns on steady when the RAC cir-

cuit is activated. Activation of the 

RAC circuit energizes the Solenoid 

Valve to permit water to enter the 

sprinkler system piping. RAC1 is 

utilized, and RAC2 is spare.

•  EARTH FAULT

The yellow Earth Fault LED turns on 

steady when there is a wiring fault 

from circuit to Earth.

•  LAMP TEST

A lamp (LED) test can be per-

formed by pressing and holding the 

ACCEPT SIGNAL key for a duration 

of five seconds. Performing a lamp 

test lights all LEDs on the system 

and allows verification that all sys-

tem LEDs are functioning.

KEYS

•  ACCEPT SIGNAL

The system LEDs (ALARM, SUPER-

VISORY, and TROUBLE) flash to 

indicate the presence of an unac-

cepted alarm, supervisory, or trou-

ble condition somewhere in the 

system. The ACCEPT SIGNAL key 

acknowledges the presence of an 

alarm, supervisory, or trouble con-

dition. By momentarily pressing the 

ACCEPT SIGNAL key, the flash-

ing LED turns steady. The ACCEPT 

SIGNAL key is used to acknowl-

edge every abnormal status present 

in the system. For example, if there 

are two red alarms and three yel-

low troubles, the ACCEPT SIGNAL 

key must be pressed five times. The 

panel’s tone-alert (piezo) turns off 

when all abnormal conditions are 

accepted.

•  SIGNAL SILENCE

Pressing the SIGNAL SILENCE key 

silences the audible notification 

devices (horns). The yellow Alarm 

Silenced LED lights to indicate that 

an alarm is still active even if the 

audible alarms have been silenced.

•  SYSTEM RESET

Pressing the SYSTEM RESET 

key directs the panel to reset 

all attached devices and clear 

all accepted alarms, troubles, 

and supervisory conditions. All 

alarms must first be accepted via 

the ACCEPT SIGNAL key and all 

devices must be reset (normal sys-

tem air pressure re-established).

Note: After pressing the SYSTEM 

RESET key, the panel requires approx-

imately fifteen seconds to clear.

Operation

The system is automatically maintained 

at a normal system air pressure of 10 

to 14 psi (0,7 to 1,0 bar) via the Air 

Compressor. In the standby condition, 

water is prevented from entering the 

system piping until the Solenoid Valve 

in the Manifold Assembly is opened in 

response to the electronic control.

Operation sequence:

•  The normal standby condition is AC 

green light ON.

•  Closure of Main Control Valve, 

closure of System Control Valve, or 

a high system pressure condition 

results in a supervisory condition 

(SPM1).

During a Supervisory Condition, the 

Yellow SUPERVISORY LED flashes 

and the tone-alert sounds steady. 

After accepting, the tone-alert 

silences and the Yellow SUPERVI-

SORY LED stays on until the condi-

tion clears.

•  Opening of a sprinkler results in 

a low air condition of less than 

nominally 8 psi (0,6 bar) resulting 

in an alarm condition on IDC1, 

opening of the Solenoid Valve 

(RAC1), and operation of alarm noti-

fication devices (NAC1).

During an Alarm Condition, the 

Red ALARM LED, corresponding to 

Zone or SPM in alarm, flashes and 

the tone-alert pulses. After accept-

ing, the tone-alert silences and the 

Red ALARM LED stays on until the 

alarm condition clears.
During a Trouble Condition, the yel-

low Trouble LED, corresponding 

to the zone or SPM with a trouble 

condition, flashes and the tone-

alert sounds steady. After accept-

ing, the tone-alert silences and the 

Red ALARM LED stays on until the 

alarm condition clears.

Panel Reference

Name

Description

IDC

Initiating Device Circuit

Low Air Pressure

NAC

Notification Appliance Circuit

Optional Notification Appliance

RAC

Releasing Appliance Circuit

Solenoid Valve

SPM

Special Purpose Monitor

Main Control Valve Closure, 

System Control Valve Closure, 

or High System Air Pressure

KEYS

LEDs

ACCEPT

SIGNAL

SIGNAL

SILENCE

SYSTEM

RESET

TROUBLE

ALARM

TROUBLE

ALARM

TROUBLE

ALARM

ALARM

TROUBLE

ALARM SILENCED

AC POWER

SUPERVISORY (SMP1)

SYSTEM TROUBLE

(IDC4)

SPARE (RAC2) TROUBLE

SYSTEM RELEASED

EARTH FAULT

SPARE

SPARE

SPARE (NAC2) TROUBLE

(NAC1) TROUBLE

(RAC1) TROUBLE

SPRINKLER

SPARE

SPARE

(IDC3)

SPARE

(IDC2)

(IDC1)

SPARE

(SMP2)

(SMP1)

DRY PIPE SYSTEM

TROUBLE

ALARM

TROUBLE

FIGURE 5 

OPERATOR INTERFACE CARD (FRONT SIDE) 

DRY PIPE SYSTEM MODE

Содержание tyco RAPID RESPONSE RCP-1

Страница 1: ... Residential Sprinklers have undergone rigorous testing to meet UL1626 fire test criteria includ ing a 15 second delay for water deliv ery as required for residential sprinklers intended for use in dry pipe systems NOTICE The RAPID RESPONSE Residential Dry Pipe System described herein must be installed and maintained by qualified personnel in compliance with this docu ment and with the applicable ...

Страница 2: ...These wet and dry type residential sprinklers have undergone rigorous testing to meet UL1626 fire test criteria including a 15 second delay for water delivery as required for residential sprinklers intended for use in dry pipe systems TYCO CPVC Pipe and Fittings Another component of the Resi dential Dry Pipe System is TYCO BLAZEMASTER CPVC Pipe and Fit tings TYCO CPVC products provide the only com...

Страница 3: ...ments for Dry System Water Delivery per Section 8 3 4 3 of the 2010 edition of NFPA 13D applies Water deliv ery to the most remote single sprin kler for a residential hazard shall not exceed 15 seconds The use of the TYCO SprinkFDT Fluid Delivery cal culation program is recommended to assure a properly operating system can be achieved prior to constructing the actual installation Figures 1 and 2 p...

Страница 4: ...sed for this example 2 Horizontal Sidewall Sprinklers are used to allow the system to com pletely drain 3 The Model RCP 1 Panel outlet flow is based on the least available water flow to hydraulically support the two most remote sprinklers at 16 GPM each 4 Water delivery to the most remote sprinkler is calculated assuming the highest possible initial air pressure based on a 10 to 14 psi automatic a...

Страница 5: ...rature of 0 F was used for this example 2 Dry Type Residential Pendent Sprinklers 3 The Model RCP 1 Panel outlet flow is based on the least available water flow to hydraulically support the two most remote sprinklers at 15 GPM each 4 Water delivery to the most remote sprinkler is calculated assuming the highest possible initial air pressure based on a 10 to 14 psi automatic air supply 5 This examp...

Страница 6: ...MBLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm OPERATOR INTERFACE WINDOW OPERATOR INTERFACE SYSTEM AIR SUPPLY PRESSURE GAUGE SYSTEM WATER SUPPLY PRESSURE GAUGE OUTLET CONNECTION TO DRY PIPE FIRE PROTECTION SYSTEM FRONT LEFT SIDE FIGURE 3 MODEL R...

Страница 7: ...mple 3 Example 3 Sidewall b Example 3 Example 3 Dry Type c Pendent Example 4 Example 4 Dry Type c Pendent a Recessed Pendent TY2234 Data Sheet TFP400 Domed Concealed Pendent TY2234 Data Sheet TFP450 Flat Plate Concealed Pendent TY3596 Data Sheet TFP442 b Recessed Horizontal Sidewall TY1334 Data Sheet TFP410 c Dry Type Recessed Pendent TY2235 Data Sheet TFP460 CPVC DRY TYPE SPRINKLER TEE P N 80259 ...

Страница 8: ... for Horizontal Ceiling Maximum 2 in Rise for 12 in Run 155 F 68 C 175 F 79 C 12 x 12 3 7 x 3 7 12 3 7 13 GPM 49 2 LPM 7 0 psi 0 48 bar 13 GPM 49 2 LPM 7 0 psi 0 48 bar 14 x 14 4 3 x 4 3 14 4 3 14 GPM 53 0 LPM 8 2 psi 0 57 bar 14 GPM 53 0 LPM 8 2 psi 0 57 bar 16 x 16 4 9 x 4 9 16 4 9 15 GPM 56 8 LPM 9 4 psi 0 65 bar 15 GPM 56 8 LPM 9 4 psi 0 65 bar 18 x 18 5 5 x 5 5 18 5 5 18 GPM 68 1 LPM 13 5 psi...

Страница 9: ...when connecting a Dry Type Residential Pendent Sprinkler to CPVC piping in areas subject to freezing Notes a For coverage area dimensions less than or between those indicated use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated b The requirement is based on minimum flow in GPM LPM from each sprinkler The associated residual pressures are c...

Страница 10: ...x 12 3 7 x 3 7 12 3 7 12 GPM 45 4 LPM 8 2 psi 0 57 bar 12 GPM 45 4 LPM 8 2 psi 0 57 bar 13 GPM 49 2 LPM 9 6 psi 0 48 bar 13 GPM 49 2 LPM 9 6 psi 0 48 bar 14 x 14 4 3 x 4 3 14 4 3 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 GPM 60 6 LPM 14 5 psi 1 00 bar 18 GPM 68 1 LPM 18 4 psi 1 27 bar 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 16 4 9 x 4 9 16 4 9 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 GPM 60 6 LPM 14 5 psi 1...

Страница 11: ... a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Compressor In the standby condition water is prevented from entering the system piping until the Solenoid Valve in the Manifold Assembly is opened in response to the electronic control Operation sequence The normal standby condition is AC green light ON Closure of Main Control Valve closure of System Control Valve or a high s...

Страница 12: ...pressure of 10 to 14 psi Step 9 Reset the Electronic Control by pressing the SYSTEM RESET key Wait approximately fifteen seconds for the Electronic Control to clear A supervisory signal will remain because the Main Control Valve is still closed Press the ACCEPT SIGNAL key to accept the supervisory signal and silence the tone alert Step 10 Open the Main Control Valve The supervisory signal should c...

Страница 13: ... to 10 Verify that POSITIONs 1 to 10 light up as follows MODE 1 POSITION 6 for Dry Pipe MODE 2 POSITION 1 for Class B Initiating Circuit Style MODE 3 POSITION 1 for 0 Second Automatic Time Release Delay MODE 4 POSITION 1 for No RAC Cutout Timer MODE 5 POSITION 1 for 0 Second Manual Release Time Delay Step 2 Verify the Operator Interface Panel of the Electronic Control only indicates a green light ...

Страница 14: ...ial Dry Pipe System P N specify 1 in 52 310 2 601 1 1 2 in 52 310 2 602 Separately Ordered Parts Specify Bezel for use with the Model RCP 1 Residential Control Panel P N 52 310 2 603 Panel Replacement Parts Specify 8 0 Amp Battery for use with the Model RCP 1 Residential Control Panel quantity of 2 P N 2656 Sprinklers Refer to the specific technical data sheets describing Residential Sprin klers f...

Отзывы: