background image

TFP485

Page 12 of 14

wire insulation, can damage the pipe 

and fittings through contact resulting 

in damage/failure to the system.

Care and 

Maintenance

The following inspection/test procedure 

for the Rapid Response Model RCP-1  

Residential Control Panel must be per-

formed as indicated, in addition to any 

specific requirements of the NFPA. 

Any impairment must be immediately 

corrected.
Before closing a fire protection system 

control valve for inspection or main-

tenance work on the fire protection 

system that it controls, obtain per-

mission to shut down the effected fire 

protection system from the proper 

authorities and notify all personnel who 

may be affected by this action.
The following inspection/test proce-

dures will result in operation of the 

associated alarms. Notify the proper 

authorities and advise those respon-

sible for monitoring proprietary and/or 

central station alarms.
After placing a fire protection system 

in service, notify the proper authorities 

and advise those responsible for moni-

toring proprietary and/or central station 

alarms.
TYCO Sprinklers and CPVC Pipe and 

Fittings are to be inspected and main-

tained in accordance with their appli-

cable data sheets.
Owners are responsible for the inspec-

tion, testing, and maintenance of their 

fire protection system and devices in 

compliance with this document, as well 

as with the applicable standards of the 

NATIONAL FIRE PROTECTION ASSO-

CIATION (e.g., NFPA 25), in addition 

to the requirements of any authority 

having jurisdiction. The installing con-

tractor or product manufacturer should 

be contacted relative to any questions.
Automatic sprinkler systems are rec-

ommended to be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

Model RCP-1 Panel 

Inspection/Test Procedure

The Model RCP-1 Panel can be 

inspected and tested without having to 

flow water into the system piping. The 

inspection and testing, in accordance 

with the requirements of NFPA 25, must 

be performed annually.

General System Inspection/Test

Step 1.

 Verify the Air Pressure Gauge 

indicates a system air pressure of 10 

to 14 psi.

Step 2.

 Silence alarms by pressing the 

SIGNAL SILENCE key.

Step 3.

 Close the Main Control Valve.

Step 4.

 Place the Air Pressure Control 

Disconnect Switch to the OFF position.

Step 5.

 Open the Drain and Flow Test 

Valves.

Step 6.

 Replace operated sprinklers.

Step 7.

 After the system drains com-

pletely, close the Drain and Flow Test 

Valves.

Step 8.

 Place the Air Pressure Control 

Disconnect Switch to the ON position 

and allow the system to automatically 

reestablish its normal air pressure of 10 

to 14 psi.

Step 9.

 Reset the Electronic Control by 

pressing the SYSTEM RESET key.
Wait approximately fifteen seconds for 

the Electronic Control to clear.
A supervisory signal will remain 

because the Main Control Valve is still 

closed.
Press the ACCEPT SIGNAL key to 

accept the supervisory signal and 

silence the tone-alert.

Step 10.

 Open the Main Control Valve.

The supervisory signal should clear 

and the system is now set for service.

Installation

TYCO Sprinklers and CPVC Pipe and 

Fittings are to be installed in accor-

dance with their applicable data sheets.
The Rapid Response Model RCP-1 

Residential Control Panel described 

herein must be installed and main-

tained in compliance with TFP480, as 

well as with the applicable standards 

of the NATIONAL FIRE PROTEC-

TION ASSOCIATION, in addition to the 

requirements of any other authorities 

having jurisdiction. Failure to do so may 

impair the performance of this device.

NOTICE

Do not attempt to reprogram the Model 

RCP-1 Panel. If assistance is required, 

contact Technical Services at Johnson 

Controls.
Remove resistors only when instructed 

to do so. Failure to do so may lead 

to improper conditions or failure of 

the Model RCP-1 Panel to function 

properly.
The cover is electrically bonded to the 

enclosure ground terminal by means of 

an 18 AWG conductor. Do not remove 

the electrical bond.
Do not place any wiring in contact 

with CPVC pipe and fittings. Plasti-

cizers, such as those found in flexible 

In Case of 

Supervisory/ 

Trouble 

Condition

Step 1.

 Verify that a fire condition does 

not exist.

Step 2.

 Close the Main Control Valve 

to prevent inadvertent water flow into 

the system.

Step 3.

 Acknowledge the supervisory/

trouble notification by momentarily 

pressing the ACCEPT SIGNAL key. 

Doing so silences the tone-alert.

Step 4.

 Determine and correct the 

cause of the supervisory/trouble noti-

fication.  Examples of causes can be 

the following:

•  Loss of primary 120 VAC power
•  Low battery condition
•  High air pressure
•  Closure of the System or Main 

Control Valve

Step 5.

 Reset the system as soon as 

possible.

In Case of 

Alarm 

Condition

Step 1.

 Verify that a fire condition 

exists and take appropriate action (that 

is, evacuate the building and call fire 

department).

Step 2.

 After the fire is extinguished, 

reset the system.
If a fire condition does not exist and 

prior to resetting the system, silence 

alarms as follows:
•  First, momentarily press the ACCEPT 

SIGNAL key a sufficient number of 

times to stop the tone-alert.

•  Second, momentarily press the SIG-

NAL SILENCE key.

System 

Resetting

Step 1.

 Use the ACCEPT SIGNAL 

key to accept every abnormal status 

present in the system.
For example, when two red ALARM 

and three yellow TROUBLE conditions 

are present, the ACCEPT SIGNAL key 

must be pressed five times. The panel’s 

tone-alert turns off when all abnormal 

conditions are accepted.

Содержание tyco RAPID RESPONSE RCP-1

Страница 1: ... Residential Sprinklers have undergone rigorous testing to meet UL1626 fire test criteria includ ing a 15 second delay for water deliv ery as required for residential sprinklers intended for use in dry pipe systems NOTICE The RAPID RESPONSE Residential Dry Pipe System described herein must be installed and maintained by qualified personnel in compliance with this docu ment and with the applicable ...

Страница 2: ...These wet and dry type residential sprinklers have undergone rigorous testing to meet UL1626 fire test criteria including a 15 second delay for water delivery as required for residential sprinklers intended for use in dry pipe systems TYCO CPVC Pipe and Fittings Another component of the Resi dential Dry Pipe System is TYCO BLAZEMASTER CPVC Pipe and Fit tings TYCO CPVC products provide the only com...

Страница 3: ...ments for Dry System Water Delivery per Section 8 3 4 3 of the 2010 edition of NFPA 13D applies Water deliv ery to the most remote single sprin kler for a residential hazard shall not exceed 15 seconds The use of the TYCO SprinkFDT Fluid Delivery cal culation program is recommended to assure a properly operating system can be achieved prior to constructing the actual installation Figures 1 and 2 p...

Страница 4: ...sed for this example 2 Horizontal Sidewall Sprinklers are used to allow the system to com pletely drain 3 The Model RCP 1 Panel outlet flow is based on the least available water flow to hydraulically support the two most remote sprinklers at 16 GPM each 4 Water delivery to the most remote sprinkler is calculated assuming the highest possible initial air pressure based on a 10 to 14 psi automatic a...

Страница 5: ...rature of 0 F was used for this example 2 Dry Type Residential Pendent Sprinklers 3 The Model RCP 1 Panel outlet flow is based on the least available water flow to hydraulically support the two most remote sprinklers at 15 GPM each 4 Water delivery to the most remote sprinkler is calculated assuming the highest possible initial air pressure based on a 10 to 14 psi automatic air supply 5 This examp...

Страница 6: ...MBLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm OPERATOR INTERFACE WINDOW OPERATOR INTERFACE SYSTEM AIR SUPPLY PRESSURE GAUGE SYSTEM WATER SUPPLY PRESSURE GAUGE OUTLET CONNECTION TO DRY PIPE FIRE PROTECTION SYSTEM FRONT LEFT SIDE FIGURE 3 MODEL R...

Страница 7: ...mple 3 Example 3 Sidewall b Example 3 Example 3 Dry Type c Pendent Example 4 Example 4 Dry Type c Pendent a Recessed Pendent TY2234 Data Sheet TFP400 Domed Concealed Pendent TY2234 Data Sheet TFP450 Flat Plate Concealed Pendent TY3596 Data Sheet TFP442 b Recessed Horizontal Sidewall TY1334 Data Sheet TFP410 c Dry Type Recessed Pendent TY2235 Data Sheet TFP460 CPVC DRY TYPE SPRINKLER TEE P N 80259 ...

Страница 8: ... for Horizontal Ceiling Maximum 2 in Rise for 12 in Run 155 F 68 C 175 F 79 C 12 x 12 3 7 x 3 7 12 3 7 13 GPM 49 2 LPM 7 0 psi 0 48 bar 13 GPM 49 2 LPM 7 0 psi 0 48 bar 14 x 14 4 3 x 4 3 14 4 3 14 GPM 53 0 LPM 8 2 psi 0 57 bar 14 GPM 53 0 LPM 8 2 psi 0 57 bar 16 x 16 4 9 x 4 9 16 4 9 15 GPM 56 8 LPM 9 4 psi 0 65 bar 15 GPM 56 8 LPM 9 4 psi 0 65 bar 18 x 18 5 5 x 5 5 18 5 5 18 GPM 68 1 LPM 13 5 psi...

Страница 9: ...when connecting a Dry Type Residential Pendent Sprinkler to CPVC piping in areas subject to freezing Notes a For coverage area dimensions less than or between those indicated use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated b The requirement is based on minimum flow in GPM LPM from each sprinkler The associated residual pressures are c...

Страница 10: ...x 12 3 7 x 3 7 12 3 7 12 GPM 45 4 LPM 8 2 psi 0 57 bar 12 GPM 45 4 LPM 8 2 psi 0 57 bar 13 GPM 49 2 LPM 9 6 psi 0 48 bar 13 GPM 49 2 LPM 9 6 psi 0 48 bar 14 x 14 4 3 x 4 3 14 4 3 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 GPM 60 6 LPM 14 5 psi 1 00 bar 18 GPM 68 1 LPM 18 4 psi 1 27 bar 18 GPM 68 1 LPM 18 4 psi 1 27 bar 16 x 16 4 9 x 4 9 16 4 9 16 GPM 60 6 LPM 14 5 psi 1 00 bar 16 GPM 60 6 LPM 14 5 psi 1...

Страница 11: ... a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Compressor In the standby condition water is prevented from entering the system piping until the Solenoid Valve in the Manifold Assembly is opened in response to the electronic control Operation sequence The normal standby condition is AC green light ON Closure of Main Control Valve closure of System Control Valve or a high s...

Страница 12: ...pressure of 10 to 14 psi Step 9 Reset the Electronic Control by pressing the SYSTEM RESET key Wait approximately fifteen seconds for the Electronic Control to clear A supervisory signal will remain because the Main Control Valve is still closed Press the ACCEPT SIGNAL key to accept the supervisory signal and silence the tone alert Step 10 Open the Main Control Valve The supervisory signal should c...

Страница 13: ... to 10 Verify that POSITIONs 1 to 10 light up as follows MODE 1 POSITION 6 for Dry Pipe MODE 2 POSITION 1 for Class B Initiating Circuit Style MODE 3 POSITION 1 for 0 Second Automatic Time Release Delay MODE 4 POSITION 1 for No RAC Cutout Timer MODE 5 POSITION 1 for 0 Second Manual Release Time Delay Step 2 Verify the Operator Interface Panel of the Electronic Control only indicates a green light ...

Страница 14: ...ial Dry Pipe System P N specify 1 in 52 310 2 601 1 1 2 in 52 310 2 602 Separately Ordered Parts Specify Bezel for use with the Model RCP 1 Residential Control Panel P N 52 310 2 603 Panel Replacement Parts Specify 8 0 Amp Battery for use with the Model RCP 1 Residential Control Panel quantity of 2 P N 2656 Sprinklers Refer to the specific technical data sheets describing Residential Sprin klers f...

Отзывы: